Slayton 42S Direct Vent Fireplace

kozy heat Slayton 42S Direct Vent Fireplace Operating instructions

  • I have reviewed the user manual for the Kozy Heat SLA-42S direct vent fireplace. This document contains detailed information regarding the fireplace's dimensions, installation procedures, and venting requirements. I am ready to answer your questions about the device and its features.
  • What are the gas line opening options?
    Where is the electrical access located?
    What is the minimum horizontal venting requirement for natural gas?
Please leave these reference guides at the installaon locaon unl the installaon is nished. See owners manual for full installaon and nishing
instrucons before making nal decisions as informaon is subject to change.
Model BTU
Height Front Width Back Width Depth Glass Viewing
Area
Actual Framing Actual Framing Actual Framing Actual Framing
SLA42S 42,000 329/16 383/8 50 551/4 50 551/4 1513/16 19
423/8 x 1511/16
Specicaons (all measurements are in inches)
Framing Opening
Finish Trim Kit
Finishing Clearances Mantel Clearances
Important!
If you are nishing around
the replace with le or
stone make sure that you
install the Finishing Trim
Kit at the framing stage.
The trim kit allows for
your nishing board and
your le/stone to nish
up against, creang a
shadowbox for the face
to sit inside.
Slayton 42S Direct Vent Fireplace
Dimension SLA42S
N 563/4
O 397/8
GAS LINE OPENING: LEFT/RIGHT SIDES ELECTRICAL ACCESS: RIGHT SIDE
Dimension SLA42S
A 621/4
B 383/8
C 551/4
D 19
CORNER INSTALLATION
HORIZONTAL TERMINATION
VERTICAL TERMINATION
E F G H I J K L M
19 551/4 19 551/4 9213/16 551/4 263/8 463/8 655/8
G
D
C
B
A
E
F
H
J
I
K
FRAMING STUDS MUST
MAINTAIN 1” CLEARANCE
TO VENTING
L
M
P Q R S T
42 141/4 171/4 2911/16 621/4
45o
NONCOMBUSTIBLE ZONE
S
T
Q
P
R
EACH SQUARE
REPRESENTS 1”
OF MANTEL
PROJECTION
3/4” NONCOMBUSTIBLE
MATERIAL ONLY
Dimension
12
9”
33/16”
33/16”
4”
Combusble Material Allowed
NonCombusble Material Only Combusble Material Allowed
N
NonCombusble Material Only
O
Lower cover panel combusble material
allowed, but no screws above the framing
12/19
Horizontal Terminaon Framing
Horizontal Venng Minimum Requirements
Heat Shield Requirements
Consult venng chart in
manual for opons above
minimum requirements
The vercal vent heat shield must be installed for EVERY type of
venng applicaon.
The horizontal vent heat shield must be installed when incorporang
minimum horizontal venng.
Dimension SLA42S
U 19
V 48
W 521/2
X 56
Minimum Natural Gas
Minimum LP Gas
Minimum Natural and LP Gas
U U U
V
W
X
800 Series FlexVent Kit Venng
Requirement SLA42S
(NG) Vercal Min 9 + 90o Elbow
(NG) Horizontal Min 9
(NG) Horizontal 12 .
Requirement SLA42S
(LP) Vercal Min 9 + 6 + 90o Elbow
(LP) Horizontal Min 9
(LP) Horizontal Max 8 .
Note specic gas type minimums
V = Vercal
H = Horizontal
H
H
MIN
MAX
MAX
MIN H
H
V
MIN
V
V
MIN
MIN
VENT HEAT SHIELD CORNER INSTALLATION
Vercal Heat Shield
PROPANE LOCATION
NATURAL GAS LOCATION
VENT STANDOFF TAB
A horizontal Wall
Thimble allowing a
1” clearance is
required
12/19
/