Callaway 50

kozy heat Callaway 50 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the kozy heat Callaway 50 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Please leave these reference guides at the installaon locaon unl the installaon is nished. See owners manual for full installaon and nishing
instrucons before making nal decisions as informaon is subject to change.
Model BTU
Height Front Width Back Width Depth Glass Viewing
Area
Actual Framing Actual Framing Actual Framing Actual Framing
CLW50 35,500 (NG)
35,000 (LP). 39 441/2 591/2 641/2 591/2 641/2 1815/16 22 497/8 x 133/8
Specicaons (all measurements are in inches)
Framing Opening
Finishing Clearances Mantel Clearances
Callaway 50 Direct Vent Fireplace
CORNER INSTALLATION
GAS LINE OPENING: LEFT SIDE ELECTRICAL ACCESS: RIGHT SIDE
P Q R S T U
48 18 211/2 271/2 22 48
Dimension
Dimension CLW50
A 441/2
B 48
C 641/2
D 22
A
B
C
D
HORIZONTAL TERMINATION
E F G H I J K L M
22 641/2 22 641/2 10613/16 641/2 257/8 537/16 759/16
VERTICAL TERMINATION
M
E
F
G
H
I J
K
L
3”
3”
3”
STEEL FRAMING REQUIRED
STEEL FRAMING REQUIRED
MANTEL
PROJECTION:
Each square
represents 1”
of projecon
NONCOMBUSTIBLE ZONE
6”
9”
12”
P
Q
R
S
45o
FINISHING EDGE
T
U
STEEL
FRAMING
3/4” Trim
COMBUSTIBLE FLOORING
(no vinyl or carpet)
Dimension CLW50
N 66
O 483/4
NonCombusble Material Only
Provided Steel Framing Required
O
N
Lower cover panel combusble material
allowed, but no screws above the framing
NonCombusble Material Only Combusble Material Allowed
8/19
Horizontal Terminaon Framing
Horizontal 5” X 8” Venng Minimum Requirements
*The horizontal vent heat shield must be installed when using a horizontal
45o elbow of the back of the appliance
Heat Shield Requirements
Decreaser Minimum Requirements
4” x 65/8”
V = Vercal
H = Horizontal
A Kozy Heat
#800WPT series
wall pass thru is
required with use
of the exvent kit.
800 Series FlexVent Kit Venng
Dimension CLW50
V 22
W 343/8
X 443/4
Y 42
V V V
W *X Y
Rigid Pipe Venng
*Requirement when inially
using 45o Elbow Vercally
45o Vercal
posion
Requirement CLW50
(NG/LP) Vercal Min 45o Elbow
(NG/LP) Horizontal Min 6
(NG/LP) Horizontal Max 24
Requirement* CLW50
(NG/LP) Vercal Min 45o Elbow + 90o Elbow
(NG/LP) Horizontal Min 6
(NG/LP) Horizontal Max 48
Consult venng
chart in the
manual for all
opons above
minimum
requirements
STEEL
FRAMING
STEEL
FRAMING
STEEL
FRAMING
*Requirement when inially using 45o Elbow Vercally
H
H
MAX
MIN
MAX
H H
MIN
V
V
MIN
MIN
Requirement CLW50
(NG/LP) Vercal Min 45o Elbow + 24 + Decreaser
(NG/LP) Horizontal Min 90o Elbow
(NG/LP) Horizontal Max 48
Requirement CLW50
(NG/LP) Horizontal Min 45o Elbow + Decreaser
(NG/LP) Vercal Min 10
(NG/LP) Vercal Max 50 .
COLINEAR 3” X 3” FLEX PIPE
VERTICAL VENTING
H H
MAX
MIN
4” x 65/8”
DECREASER
24” Vercal ( 5” x 8”) MIN
COAXIAL TO
COLINEAR ADAPTER
4” x 65/8”
DECREASER
V
MIN
V
MAX
8/19
/