Lumen Package
Max. Mounting Height (ft)
PS30250
12L 32
18L 60
24L 60
30L 40
35L 40
40L 40
45L 40
3.2 Installation of PS30250 Battery Backup
CAUTION: A potential electrical hazard exists even when AC power supply has been turned off. Disconnect
Battery Connector (2 red leads) before servicing.
IMPORTANT NOTES: Make sure that branch circuit feeds are derived from a common phase for both normal
lighting driver and PS30250 prior to installation.
The PS30250 can be used with a switched or unswitched (night) circuit. When used with a switched fixture it is
important to note that the power to the PS30250 inverter/charger must be provided by an unswitched circuit.
APPROXIMATE WORKING VOLTAGE
Inverter/charger input: 120 OR 277 VAC
3.2.1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
3.2.2. Before wiring to power supply, turn off electricity at fuse or circuit breaker.
3.2.3. To reduce the risk of electrical shock, disconnect AC power and unplug red battery connector before
servicing.
3.2.4. All servicing should be performed by qualified personnel.
3.2.5. Consult your local building code for approved wiring and installation.
3.2.6. Do not use outdoors. This product is for use with indoor fixtures except air handling heated outlets, and wet
or hazardous location fixtures.
3.2.7. The LED emergency driver must be connected to an unswitched AC power source (120 or 277 volts).
3.2.8. Do not mount near gas or electric heater.
3.2.9. Equipment should be mounted in location and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
3.2.10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
3.2.11 Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS INSTALLATION PROCEDURE
3.2.12 Inspect PS30250 and make sure the battery connector (2 red leads) are not connected.
3.2.13 Once luminaire is installed, mount the remote PS30250 Emergency Battery Pack securely to ceiling or
other solid surface.
3.2.14 Install the Junction box with test switch and indicator light.
3.2.15 This unit has more than one power supply connection point. To reduce the risk of electrical shock,
disconnect both the branch circuit breakers or fuse and emergency power supplies before servicing.
3.2.16 Make connections to “Switched” and “Unswitched” power within the junction box (Fig 8).
3.2.17 Apply continuous power to PS30250.
3.2.18 Connect the battery connector (red leads).
NOTE: Do not mount Emergency Battery Pack over A.C. Ballast.
Figure 8