  • Hello! I am an AI chatbot trained to assist you with the Robertshaw J10-809W and J10-810 Dehumidistat User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
J10-823-070
DeHumidista t
24V Hea ting/Cooling Thermostat
INSTALLATION DATA
J10-809W AND J10-810
DEHUMIDISTAT
Applicaon
The J10-809W and J10-810 are used to cycle an air condioning system
to help prevent mildew build-up associated with high humidity levels.
The J10-809W and J10-810 are designed to be wall-mounted and can
be wired in parallel or in series with any 24V thermostat.
Parallel Installaon
Advantages: Desired humidity is maintained regardless of ambient
temperature.
Disadvantages: The air condioning system could cycle on during low
ambient temperatures.
Series Installaon
Advantages: Air condioning system will not cycle on during low
ambient temperature periods.
Disadvantages: Humidity levels may be higher than desired during low
temperature periods.
Installaon Instrucons
1. Turn electrical power o.
2. Determine dehumidistat locaon. This control should be mounted
on an inside wall where normal air circulaon is present. For most
residenal applicaons, locate the control adjacent to the exisng
wall thermostat for easy installaon and wiring.
3. Remove cover from back plate and punch wiring knockout on
back plate.
4. Place back plate on at mounng surface, mark two mounng
hole locaons, and wire knockout hole.
5. Drill
3
/
16
” diameter holes for drywall anchors (if needed) and
insert dry wall anchors.
6. Drill ½” diameter hole for low voltage wires, pull wiring through
access hole and through back plate.
7. Mount back plate securely to wall with screws provided in
parts package. NOTE: Make sure the back plate is at without
any undue stress.
8. Connect wires to Terminals 1 and 2. Wires should not be taut
aer connecon. NOTE: All wiring should conform to NEC
recommendaons and any local codes.
9. Re-install front cover.
10. Turn electrical power back on.
Operaonal Test
Parallel Installaon
Turn dehumidistat down unl air condioner turns on. Cycle at least
three mes to assure proper system funcon. Return control knob
pointer to desired humidity seng.
NOTE: DO NOT USE parallel wiring if low temperature compressor
protecon is not present.
J10-823-070
DeHumidista t
24V Hea ting/Cooling Thermosta t
Customer Service Telephone 1.800.304.6563
Customer Service Facsimile 1.800.426.0804
Robertshaw® and Ranco® are trademarks of Robertshaw, its
subsidiaries and/or affiliated companies. All other brands mentioned
may be the trademarks of their respective owners.
For Technical Service
Telephone 1.800.445.8299
www.robertshaw.com
©2018 Robertshaw
11/18 – 352-00276-001
Series Installaon
Turn the thermostat to the highest temperature seng. Turn the
dehumidistat from lowest to highest seng. The air condioning
system should not start up. (If it does, wiring is incorrect.) Next, turn
the dehumidistat to the highest seng. Turn the thermostat from high
to lowest temperature seng. Again, the system should not start up.
Now, set the thermostat on the lowest temperature seng and the
dehumidistat to the lowest seng. The system should now operate.
NOTE: The use of a sling psychrometer is recommended to
determine relave humidity level.
/