ICM Controls ICM291 Application/Install Guide

Type
Application/Install Guide
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com LIAF098-1
Install New Control
1. Groundyourself.Whenhandlingcircuitboard,holditbytheedges.
2. Fastencircuitboardwithretainingscrews.
3. Connectalllinevoltage,lowvoltage,andaccessorywires.
4. Verifythesequenceofoperation.
Safety Considerations
Onlytrainedpersonnelshouldinstallorserviceheatingequipment.Whenworkingwithheating
equipment,besuretoreadandunderstandallprecautionsinthedocumentation,onlabels,andon
tagsthataccompanytheequipment.Failuretofollowallsafetyguidelinesmayresultindamageto
equipment,severepersonalinjuryordeath.
Introduction
TheICM291DSIgasignitioncontrolreplacesthefollowingCarriermodel:LH33WP003A.The
ICM291hasincorporatedLEDdiagnosticstoassistintroubleshooting.Faultcodeinformationcanbe
foundinthisapplicationguide.Pleasekeepthisapplicationguidewiththefurnaceinstallationmanual
forfuturereference.
Electrostatic Discharge (ESD) Precautions
CAUTION!
Use caution when installing and servicing the furnace to avoid and control electrostatic discharge;
ESD can impact electronic components. These precautions must be followed to prevent
electrostatic discharge from hand tools and personnel. Following the precautions will protect the
control from ESD by discharging static electricity buildup to ground.
1. Disconnectallpowertothefurnace.Donottouchthecontrolorthewiringpriortodischargingyour
body’selectrostaticchargetoground.
2. Togroundyourself,touchyourhandandtoolstoaclean,metal(unpainted)furnacesurfacenear
thecontrolboard.
3. Servicethefurnaceaftertouchingthechassis.Yourbodywillrechargewithstaticelectricityasyou
shufeyourfeetormovearound,andyoumustregroundyourself.
4. Regroundyourselfifyoutouchungroundeditems.
5. Beforehandlinganewcontrol,regroundyourself;thiswillprotectthecontrol.Storeusedandnew
controlsinseparatecontainersbeforetouchingungroundedobjects.
6. ESDdamagecanalsobepreventedbyusinganESDservicekit.
CAUTION!
To service control, and prior to disconnection, label all wires. Failure to do so may result in wiring
errors that can cause dangerous operation.
1. TurnthermostattoOFFpositionorsetittothelowestpossiblesetting.
2. TurnOFFelectricalsupplytofurnace.
3. TurnOFFgassupplytofurnace.
CAUTION:Failuretoturnoffgasandelectricsuppliescanresultinexplosion,re,death,or
personalinjury.
4. Removefurnaceblowerandcontrolaccessdoors.
5. Disconnectthermostatwiresandhumidierwires(ifequippedwithahumidier).
6. Disconnectlinevoltage,blower,electronicaircleanerwires(ifequipped),andtransformerwires.
7. Removescrewsandanyotherfasteners,andtheoldcircuitboard.
8. Examinecontrolandcontrolboxtocheckforwaterstains.
9. Makerepairsifanysourcesofwaterleakagearefound.Besuretocheckhumidiers,evaporator
coils,andventsystemsintheareaofthecontrol.
Remove Existing Control
ICM291
Gas Ignition Control Board
AWcallfromtheT’statwillengagethecombustionmotor.Ignitionsequencebegins,gasvalveand
sparkareengaged,providingthatsystemsafetyswitches(RS,LS,andCS)areclosedandthereis
feedbackfromthecombustionmotorHallEffectsensor.Theblowerandindoormotorswillengage45
secondsafterameisestablishedandsensed.Theydisengage45secondsafterWcallissatised.
AGcallfromtheT’statwillengageblowerandindoormotorsrightaway.Theydisengage25seconds
afterGcallisremoved.
Sequence of Operation
Flame not established
1. Ifameisnotestablishedduringthe5+2initialsequencethenthecontrolwillstartthenexttrialfor
ignitionin20seconds.
2. Theattempttoignitewillcontinuefor15minutesbeforetherespectivefaultcodeistriggeredand
ignitiontrialsarestopped.
3.Thegasvalveisenergizedonlyduringtheignitionsequenceof5+2seconds.
4. Blowerandindoorfanmotorsareoffuntilameisestablishedand45secondslater.
Flame out
1. Flameoutisconsideredwhenameislostduringheating.
2. WhenWsignalispresentandameissensedoutthenthesparkwillstartrightaway.
3. Ifameisnotestablishedontheimmediatesequence(2above)thenthecontrolwillcontinue
attemptsevery20secondsfor15minutesbeforetherespectivefaultcodeistriggeredandignition
trialsarestopped.
4. Blower&indoorfanmotorswillcontinuerunningduringameoutscenariofor15mins.+45secs.
5.Combustionmotorremainsonthroughouttheameoutscenario.
Flame out of sequence
1. FlameoutofsequencerepresentsascenariowhenameissensedwhileWsignalisnotpresent.
2. Combustion,blowerandindoorfanmotorswillbeengaged(ifnotalreadyrunning)rightawayand
keeprunningforaslongasthefaultconditionispresent.
3. Theunitisoperablebutwilldisplaythefaultcodeconstantlyuntilreplacedbyanotherfaultcodeor
powerreset.
No signal from the Hall affect sensor
1. OnaWcall,iftheinputfromtheHallaffectsensor(RA0)isnotpresentformorethanaminute,
thenthecombustionmotorwillcontinuerunningendlesslyandtherespectivefaultisashed.
2. DuringrunningstateiftheinputfromtheHallaffectsensorisnotsensedthenthegasvalvewill
shutoffrightaway,blowerandindoorfanmotorswillcontinuerunningfor30secondsandthen
turnoff,combustionmotorrunscontinuously.
Troubleshooting Tips
LED Fault Codes
# Of Flashes
represents Constant
ON Normal operation
Results
1Thecontrolhasmodiedthefanondelayto0andoffdelayto3mins.
duetosensingLStripwithin10minutesofacall
2a) LSisopenduetohightemperature(fanisn’tworkingscenario)
b) Theunitwillnotstartatrialforignitionuntiltheswitchclosesback
3
a) Flamesensedoutofsequence.
b) Theunitisoperable,howeverwilldisplaythisfaultcodeuntilpower
resetoranothercode
4a) LSopened4consecutivetimesduringacallforheating
b) ThefaultcodeisresetonthenextWcall
5a) Ignitionlockout.Thecontroltriedunsuccessfullytoignitefor15mins.
b) Theunitwillnotoperate.Requirespowerreset
6a) ThecombustionmotorisnotsensedrunningORCSopen
b) Theunitwillnotoperate.Requirespowerreset
7a) RStripped
b) Theunitwillnotoperate.Requirespowerreset
8a) Unusualgasvalveresponse
FEATURES
Direct Spark Ignition (DSI) control board
Microprocessor-based
Controls combustion, blower and indoor motors; spark ignitor; and the gas valve
Monitors timing, trial for ignition, ame sensing and lockout
100% lockout safety feature
Compatible with LP or Natural Gas
Status LED for fault codes to aid in troubleshooting
Replaces: Carrier LH33WP003A
SPECIFICATIONS
• Control voltage:24VAC(18-30VAC),60Hz
• Line voltage:208/230VAC,60Hz
• Power consumption:0.3Aplusgasvalvecurrentat24VAC
• Operating Temperature:-40°C(-40°F)to75°C(176°F)
LED indicators
• Red LED: SteadyON-normaloperation
  Flashing-faultcodes
Timing
• Pre-purge:45seconds
• Trial for Ignition:5+2seconds
• Retry period:every20sec.for15min.
• Lockout:manualreset
• Post-purge:45seconds
Inputs
• Power:RTandC
• Thermostat interface:R,WandG
• Safety switches:RS,LS,andCS
• CombustionmotorHallEffectsensor
• FlameSensing
Outputs
• Spark
• Gas Valve:GV
• Combustion motor:CM
• Blower motor:BM
• Indoor fan motor:IFO
Typical Wiring Diagram
LEGEND
Field Splice
Terminal (marked)
Terminal (unmarked)
Splice
Splice (marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only: Not to Represent Wiring
BR Blower Relay
C Contactor
CAP Capacitor
COMP Compressor Motor
CR Combustion Relay
EQUIP Equipment
FS Flame Sensor
FU Fuse
GND Ground
GVR Gas Valve Relay
HPS High Pressure Switch
HS Hall Effect Sensor
HV TRAN High Voltage Transformer
I Ignitor
ICM Integrated Control Motor
IDM Induced Draft Motor
IFM Indoor Fan Motor
IGC Integrated Gas Unit
Controller
IMR Indoor Motor Relay
LPS Low Pressure Switch
LS Limit Switch
MGV Main Gas Valve
OFM Outdoor Fan Motor
QT Quadruple Terminal
RS Rollover Switch
TRAN Transformer
Testing the Inducer Motor
Testing the Inducer Motor Hall Effect switch using a Voltmeter capable of reading DC Voltage
• Withthethreewireplugconnectedandpowerapplied,useaVoltmetersettoDCVandconnectthenegative (-) meter lead to pin 3andthepositive lead (+) to pin 1.Carefully
rotatetheinducerdraftmotorbyhand180degreesandthereadingshouldbeless than 1 Volt DC.Continuetorotatethemotorthrough180degreestowards360degrees.The
voltageshouldincreasetoareadingbetween6.5 VDC and 9VDCatthefull360degreemark.Iftherstreadingislessthan1VDCorthesecondreadingisnotbetween6.5&9
VDC,youshouldreplacethesensor.
• Next,movethepositive lead of the meter to pin 2leavingthenegative lead on pin 3.TakeareadingwithyourDCVmeterandthereadingshouldmeasurebetween16.5VDC
and 21VDC.Replacethesensorifthereadingisnotinrange.
• IfCode6ashesontheboard,checkforcontinuityacrossthejumperatJ2.Thejumpershouldnotbecutandshouldhavefullcontinuity.
1
2
3
  • Page 1 1
  • Page 2 2