Lennox G24M SERIES Unit Information

Category
Water heaters & boilers
Type
Unit Information
Page 1
ã 1998 Lennox Industries Inc.
Litho U.S.A.
Corp. 9723-L12
G24M
Service Literature
Revised 07-2001
G24M SERIES UNITS
G24Mseriesunitsaremid-efficiencygasfurnacesmanufac-
tured with tubular steel heat exchangers formed of alumi-
nizedsteel.G24Munitsareavailableinheatingcapacitiesof
45,000 to 140,000 Btuh and cooling applications up to 5
tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
availableforconversiontoLPGoperation.EarlymodelG24M
units use electronic (direct spark) ignition. Late model G24M
model units feature the Lennox SureLightT silicon-nitride
ignition system. The G24MX unit meets the California Nitro-
gen Oxides (NO
x
) Standards and California Seasonal Effi-
ciency requirements. All units use a redundant gas valve to
assure safety shut-off as required by A.G.A. or C.G.A.
Unitsmaybeinstalledinupflow,downfloworhorizontalposi-
tion. The heat exchanger is designed for upright or horizon-
tal use only. When the unit is installed in the downflow posi-
tion,theheatexchangerisfieldremovedandreinstalled soit
isuprightwhen thecabinetis inverted.Nofield conversionis
required when the unit is installed in the horizontal position.
The heat exchanger, burners and manifold assembly can
easily be removed for inspection and service by simply dis-
connecting gas, unplugging wiring harness and spark wires
and removing four screws holding the heat exchanger in
place. Then the heat exchanger slides out of the cabinet.
All specifications in this manual are subject to change. Pro-
cedures outlined in this manual are presented as a recom-
mendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
SPECIFICATIONS
Model No. G24M2(X)-45 G24M2-60 G24M3(X)-60 G24M2-75 G24M3(X)-75
Input Btuh (kW) 45,000 (13.2) 60,000 (17.6) 75,000 (22.0)
Output Btuh (kW) 36,900 (10.8) 49,200 (14.4) 61,700 (18.1)
lA.F.U.E. 80.1% 80.5% 80.5% 80.1% 80.0%
California Seasonal Efficiency 75.4% 76.4% 75.9% 76.8% 76.8%
Flue size connection diameter in. (mm) round 3 (76) 4 (102)
Temperature rise range _F (_C) 30 - 60 (17 - 33) 45 - 75 (25 - 42)
High static certified by A.G.A./C.G.A. in wg. (Pa) .50 (125)
Gas Piping Size I.P.S. Natural or LPG/propane 1/2 (13)
B
l
o
w
e
r
w
h
e
e
l
n
o
m
i
n
a
l
in. 9 x 7 10 x 7 9 x 7 10 x 7
B
l
o
w
e
r
w
h
e
e
l
n
o
m
i
n
a
l
d
i
a
m
e
t
e
r
x
w
i
d
t
h
mm 229 x 178 254 x 178 229 x 178 254 x 178
Blower motor output hp (W) 1/4 (187) 1/3 (224) 1/4 (187) 1/3 (224)
N
o
m
i
n
a
l
c
o
o
l
i
n
g
Tons 1, 1-1/2 or 2 2, 2-1/2 or 3 1, 1-1/2 or 2 2, 2-1/2 or 3
N
o
m
i
n
a
l
c
o
o
l
i
n
g
t
h
a
t
c
a
n
b
e
a
d
d
e
d
kW 3.5, 5.3 or 7.0 7.0, 8.8 or 10.6 3.5, 5.3 or7.0 7.0, 8.8 or 10.6
Shipping weight lbs. (kg) 1 package 130 (59) 135 (61)
Electrical characteristics 120 volts 60 hertz 1 phase (less than 12 amps) All models
b Optional Accessories (Must Be Ordered Extra) b
LPG/propane kit LB-69845L (38K84)
Twinning Kit 96J69 5 lbs. (2 kg)
Up-Flow/Horizontal Filter and Filter Rack Kits
}No. & size of filters - in. (mm)
Single (32J02) Ten Pack (66K64)
(1) 16 x 20 x 1 (406 x 508 x 25)
¡
D
o
w
n
-
f
l
o
w
Catalog No.
LB-69843A (32J01) 3 lbs. (1 kg)
¡
D
o
w
n
-
f
l
o
w
Filter Kit
No. & Size of Filters in. (mm)
(2) 16 x 20 x 1 (406 x 508 x 25)
Down-flow Combustible Floor Base
LB-79239A (67J91) 10 lbs. (4 kg)
Sidewall Power Venting Kit 79J15 25 lbs. (11 kg)
Hanging Bracket Kit
LB-69957 (46J66) 15 lbs. (8 kg)
lAnnual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
}Polyurethane frame type filter is furnished with kit.
¡Filters are not furnished with kit and must be ordered extra.
G24M
PARTS I DENTIFICATION
4
1
2
3
5
6
Page 8
I-UNIT COMPONENTS (Figures 1, 2, 3)
G24M unit components are shown in figure 1. The blower
controls, gas valve and burners can be accessed by reĆ
moving the front access panel. A separate blower access
door is located behind the front access panel. Electrical
control components are mounted to the blower access
door.
G24M units are factory equipped with bottom return air panels
in place. The panels are designed to be field removed as reĆ
quired for bottom air return. Indentations on side of units,
show where side return opening should be cut during installaĆ
tion.
A-Blower Door Components (Figure 4)
Electrical burner control and blower control components
are located on the outside surface of the blower access
door. Jackplugs allow the blower door to be easily reĆ
moved for blower service.
Located on the blower door are the unit transformer (T1),
the furnace control (A3) and door interlock switch (S51).
Furnace control (A3) combines the function of a burner
ignition control and blower control.
1- Control Transformer (T1)
A transformer located on the blower door provides power
to the low voltage section of the unit. Transformers on all
models are rated 30VA with a 120V primary and a 24V secĆ
ondary.
2-Door Interlock Switch (S51)
A door interlock switch rated 16A at 125VAC is located on
the blower access door. The switch is wired in series with
line voltage. When the blower door is removed the unit will
shut down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
3- SureLight Ignition System (A3)
Late Model G24M Units
Late model G24M units are equipped with the Lennox
SureLight ignition system. The system consists of ignitor
(figure 5) and ignition control board (figure 6 with control
terminal designations in table 1). The board and ignitor
work in combination to ensure furnace ignition and ignitor
durability. The SureLight integrated board controls all
major furnace operations. The board also features two
LED lights for troubleshooting and two accessory termiĆ
nals rated at (4) four amps. See table 2 for troubleshootĆ
ing diagnostic codes. Table 3 and 4 show jack plug termiĆ
nal designations. Units equipped with the SureLight
board can be used with either electronic or electro-meĆ
chanical thermostats without modification. The SurĆ
eLight ignitor is made of durable silicon-nitride. Ignitor
longevity is also enhanced by voltage ramping by the
control board. The board finds the lowest ignitor temperaĆ
ture which will successfully light the burner, thus increasĆ
ing the life of the ignitor.
a-flame sensor
The flame sensor uses flame rectification to sense comĆ
bustion. During operation, flame is sensed by current
passed through the flame and sensing electrode. Figure 7
shows the gap between tip of the electrode and the burner
surface.
FIGURE 5
SURELIGHT IGNITOR BURNER ASSEMBLY
FLAME SENSOR
FLAME RETENTION RING
UPPER BURNER
MOUNTING RAIL
ORIFICE
SURELIGHT IGNITOR
Page 9
SURELIGHT CONTROL BOARD
LATE MODEL G24M UNITS
FIGURE 6
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
Blower - Cooling Speed (Line Volt)
Blower - Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
TABLE 1
FIGURE 7
NORMAL FLAME SIGNAL > 0.7 MICROAMPS
LOW FLAME SIGNAL < 0.7 MICROAMPS
MINIMUM FLAME SIGNAL < 0.15 MICROAMPS
FLAME SENSOR TO BURNER GAP
BURNER
FLAME
SENSOR
SIDE VIEW END VIEW
1/4 in. 7 mm
¦ 1/32 in. 0.79
mm
3/16 in.
4.7 mm
11/16 in. 18 mm
¦ 1/32 in. 0.79
mm
TABLE 2
DIAGNOSTIC CODES
MAKE SURE TO ID LEDS CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1 LED #2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
SLOW FLASH
Power - Normal operation
Also signaled during cooling and continues fan.
SIMULTANEOUS FAST
FLASH
SIMULTANEOUS FAST
FLASH
Normal operation - signaled when heating demand initiated at thermostat.
SLOW FLASH ON
Primary or Secondary limit open. Units with board 63K8901 or 24L85: Limit must
close within 5 trials for ignition or board goes into one hour limit Watchguard.
Units with board 56L83 or 97L48: Limit must close within 3 minutes or board
goes into one hour limit Watchguard.
OFF SLOW FLASH
Pressure switch open or has opened 5 times during a single call for heat; OR:
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
ALTERNATING SLOW
FLASH
ALTERNATING SLOW
FLASH
Watchguard - burners fail to ignite.
SLOW FLASH OFF
Flame sensed without gas valve energized.
ON SLOW FLASH
Rollout switch open. OR: 9 pin connector improperly attached.
ON
ON
OFF
ON
OFF
ON
Circuit board failure or control wired incorrectly.
FAST FLASH SLOW FLASH
Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH
Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
ALTERNATING FAST
FLASH
ALTERNATING FAST
FLASH
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Open ignitor circuit.
NOTE - Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microAmps
Page 10
TABLE 3
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Ignitor
2
Not Used
3
Ignitor Neutral
4
Combustion Air Blower Line Voltage
5
Not Used
6
Combustion Air Blower Neutral
TABLE 4
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Primary Limit In
2
Gas Valve Common
3
Roll Out Switch Out
4
Gas Valve 24V
5
Pressure Switch In
6
Pressure Switch and Primary Limit Out
7
Not Used
8
Roll Out Switch In
9
Ground
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnaces
electronic controls. Precautions will help to
avoid control exposure to electrostatic dis-
charge by putting the furnace, the control and
the technician at the same electrostatic poten-
tial. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface,
such as the gas valve or blower deck, before per-
forming any service procedure.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
b-Electronic Ignition
On a call for heat the SureLight control monitors the com-
bustion air inducer prove switch. The control will not begin
theheatingcycle iftheprove switchisclosed (by-passed).
Once the prove switch is determined to be open, thecom-
bustion air inducer is energized. When the differential in
the prove switch is great enough, the prove switch closes
and a 15-second pre-purge begins. If the prove switch is
not proven within 2-1/2 minutes, the control goes into
Watchguard-Pressure Switch mode for a 5-minute re-set
period.
NOTE - The G24M furnace contains electronic com-
ponents that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
After the 15-second pre-purge period, the SureLight igni-
tor warms up for 20 seconds after which the gas valve
opensfor a 4-secondtrial for ignition.The ignitor staysen-
ergized for the first second of the 4-second trial. G24M
units with 63K89, 24L85 or 56L83: the ignitor stays ener-
gizedthefirstsecondofthe4secondtrial.G24Munitswith
board 97L48: ignitor stays energized during the 4-second
trialuntilflameissensed.Ifignitionisnotprovedduringthe
4-secondperiod,thecontrolwilltryfourmoretimeswithan
inter purge and warm-up time between trials of 35 sec-
onds.After a totalof five trialsfor ignition (including theini-
tial trial), the control goes into Watchguard-Flame Failure
mode.Aftera 60-minuteresetperiod,thecontrol willbegin
the ignition sequence again.
The SureLight control board has an added feature that
prolongs the life of the ignitor. After a successful ignition,
theSureLightcontrolutilizeslesspower toenergizetheig-
nitoron successive callsfor heat. Thecontrol continues to
rampdown the voltageto theignitor untilit findsthe lowest
amount of power that will provide a successful ignition.
Thisamount of poweris used for255 cycles. Onthe 256th
callfor heat, thecontrol will againramp down until thelow-
est power is determined and the cycle begins again.
c-Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the bloweroperates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped witha factoryfan off setting of 90seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 8.
NOTEIf fan off time is set too low, residual heat in
heat exchanger may cause primary limit S10 to trip re-
sulting in frequent cycling of blower. If this occurs, ad-
just blower to longer time setting.
FIGURE 8
FAN-OFF TIME ADJUSTMENT
To adjust fan-off timing, flip dip switch to desired setting.
60sec. 90sec. 120sec. 180sec.
4-- R am Control (A3)
Early Model G24M Units
DANGER
DANGER
B--Blower Motors and Capacitors
C--Combustion Air Blower (B6)
D--Flame Rollout Switches (S47)
E--Primary Limit Control (S10)
F--Secondary Limit Controls (S21)
G--Spark Electrode and Flame Sensor
Early Model G24M Units
H--Gas Valve
I--Combustion Air Blower Prove
(Pressure) Switch (S64)
II--PLACEMENT AND INSTALLATION
III--START-UP
A--Preliminary and Seasonal Checks
B--Heating Start-Up
WARNING
C--Safety or Emergency Shutdown
IMPORTANT
D--Extended Period Shutdown
IV--HEATING SYSTEM SERVICE CHECKS
A--A.G.A./C.G.A. Certification
B--Gas Piping
C--Testing Gas Piping
D--Testing Gas Supply Pressure
E--Check Manifold Pressure
IMPORTANT
Page 18
F- Proper Gas Flow
Furnace should operate at least 5 minutes before checkĆ
ing gas flow. Determine time in seconds for two revoluĆ
tions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to time
in table 10 below. Adjust manifold pressure on gas valve
to match time needed.
NOTE- To obtain accurate reading, shut off all other
gas appliances connected to meter.
TABLE 10
GAS METER CLOCKING CHART
Seconds for One Revolution
G24M
Natural LP
Unit
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
-45 80 160 200 400
-60 60 120 150 300
-75 48 96 120 240
-100 36 72 90 180
-120 30 60 75 150
-140 26 52 64 128
Natural-1000 btu/cu ft LP-2500 btu/cu ft
NOTE- To obtain accurate reading, shut off all other
gas appliances connected to meter.
G-High Altitude Derate
NOTE-In Canada, certification for installation at altiĆ
tudes over 4500 ft. (1372m) above sea level is the jurisĆ
diction of the local authorities.
G24M-1 through -9 Models
This unit does not require gas pressure adjustment, or
pressure switch change when operating at elevations of 0
to 7500 ft. (0 to 2248m). Check gas line pressure with unit
firing. The minimum pressure as shown on the nameplate
for natural and propane gases must be maintained. No oriĆ
fice change is required.
NOTE-This is the only permissible field derate for this
appliance.
G24M-10 and -11 Models
Table 11 shows manifold pressure settings for installations
at different altitudes. Refer to table 12 for pressure switch
replacement for models at elevations of 4500 feet (1372m)
and greater.
TABLE 11
ALTITUDE
feet (m)
GAS FUEL
MANIFOLD
PRESSURE
in. W.C. (kPa)
0 - 4500
Natural 3.5 (0.87)
0
4500
(0 - 1372)
Propane/LP 9.5 (2.36)
4500 - 5500
Natural 3.4 (0.86)
4500
5500
(1372 - 1676)
Propane/LP 9.2 (2.29)
5500 - 6500
Natural 3.3 (0.82)
5500
6500
(1676 - 1981)
Propane/LP 8.9 (2.21)
6500 - 7500
Natural 3.2 (0.80)
6500
7500
(1372 - 2286)
Propane/LP 8.6 (2.14)
TABLE 12
Unit Model Pressure Switch Part Number
G24M-45 No Change
G24M-60 No Change
G24M-75 88J8001
G24M-100 18L2401
G24M-120 18L2401
G24M-140 No Change
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
H-Flame Signal
A microamp DC meter is needed to check the flame signal
on the primary ignition control.
Flame (microamp) signal is an electrical current which
passes from the furnace control through the sensor elecĆ
trode during unit operation. Current passes from the senĆ
sor through the flame to ground to complete a safety cirĆ
cuit.
To Measure Flame Signal:
1 - Place meter in series between furnace control and
sensor wire. Connect the positive (+) lead of meter to
the ignition control sensor connection and the negaĆ
tive (-) lead of the meter to the sensor wire. See figure
21.
2 - Set thermostat for a heating demand and check flame
signal with unit operating. For G24M series with a RAM
control, a reading of 1 to 5 microamps DC should occur.
The furnace control must see at least 1.0 microamps in
order to keep the gas valve energized. G24M units with
the SureLight control should read 0.7 microamps or
more.
FIGURE 22
STATIC PRESSURE
TEST
MANOMETER
G24M UNIT
Page 19
FLAME SIGNAL TEST
FIGURE 21
IGNITION
CONĆ
TROL
SENSE"
TERMINAL
SENSOR
WIRE
D.C. MICROAMP
METER
FLAME
SENSOR
RAM CONTROL
SHOWN
Flame signal from the Ram control may rise above 5 microĆ
amps for the first few seconds after ignition then level off within
the range.
WARNING
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
V-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
NOTE- The following is a generalized procedure and
does not apply to all thermostat controls.
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat subĆ
base fan switch. With fan switch in ON position, blower
operates continuously on low speed. With fan switch in
AUTO position, blower cycles with demand or runs conĆ
tinuously while heating or cooling circuit cycles.
3 - In all cases, blower and entire unit will be off when the
system switch is in OFF position.
B-Temperature Rise
Temperature rise for G24M units depends on unit input,
blower speed, blower horsepower and static pressure as
marked on the unit rating plate. The blower speed must be
set for unit operation within the range of AIR TEMP. RISE
°F" listed in the unit rating plate.
To Measure Temperature Rise:
1 - Place plenum thermometers in the supply and return
air plenums. Locate supply air thermometer in the first
horizontal run of the plenum where it will not pick up raĆ
diant heat from the heat exchanger.
2 - Set thermostat to highest setting.
3 - After plenum thermometers have reached their highĆ
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check
the firing rate. Provided the firing rate is acceptable, inĆ
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
C-External Static Pressure
1 - Measure tap locations as shown in figure 22.
2 - Punch a 1/4" diameter hole
in supply and return air pleĆ
nums. Insert manometer
hose flush with inside edge
of hole or insulation. Seal
around the hose with perĆ
magum. Connect the zero
end of the manometer to the
discharge (supply) side of the system. On ducted sysĆ
tems, connect the other end of manometer to the reĆ
turn duct as above. For systems with non-ducted reĆ
turns, leave the other end of the manometer open to
the atmosphere.
3 - With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blowĆ
er motor speed to deliver the air desired according to
the job requirements.
4 - External static pressure drop must not be more than
0.5" W.C.
5 - Seal around the hole when the check is complete.
Page 20
D-Blower Speed Taps Leadless Motors
Blower speed tap selection is accomplished by changing the
taps at the blower motor harness connector. Disconnect harĆ
ness connector from motor to expose speed selectors.
Blower speed selections are listed in table 13.
To Change Blower Speed:
1 - Turn off electric power to furnace.
2 - Remove front panel and blower access door. See
figure 4.
3 - Disconnect blower motor harness from motor.
4 - Select desired speeds for heating and cooling (refer to
unit wiring diagram).
5 - Depress harness connector tab to release wire termiĆ
nal. Select connector location for new speed (refer to
unit wiring diagram). Insert wire terminal until it is seĆ
curely in place. See figure 23.
6 - Replace harness connector to motor.
FIGURE 23
BLOWER SPEED TAP SELECĆ
TION
LEADLESS MOTORS
HARNESS
CONNECTOR
MOTOR
DEPRESS TAB TO RELEASE
WIRE TERMINAL. SELECT
CONNECTOR LOCATION
FOR NEW SPEED (REFER TO
UNIT WIRING DIAGRAM). INĆ
SERT WIRE UNTIL IT IS SEĆ
CURELY IN PLACE.
E-Blower Speed Taps Leaded Motors
Blower speed tap changes are made on the SureLight
control board. See figure 6. Unused taps must be secured
on dummy terminals "PARK M1" and or "PARK M2" on the
SureLight board. The heating tap is connected to the "ACB
HEAT " terminal and the cooling tap is connected to the
"ACB COOL" terminal. The continuous blower tap is conĆ
nected to the "ACB LOW" terminal.
To change existing heat tap, turn off power then switch out
speed tap on "ACB HEAT" with tap connected to "PARK
M1" or "PARK M2". See table 14 for blower motor tap colĆ
ors for each speed.
TABLE 13
TABLE 14
VI-MAINTENANCE
At the beginning of each heating season, the system
should be checked as follows:
A-Filters
A filter must be used in order to ensure long life and proper
operation. The filter is located in the return air duct or return
air register. Filters must be cleaned or replaced when dirty
to assure proper unit operation.
B-Heat Exchanger and Burners
NOTE-Use papers or protective covering in front of furĆ
nace while cleaning furnace.
Due to dimples designed in the heatexchanger, cleaning is
not recommended. Removal is for inspection only.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36