Quadrafire Garnet Gas Stove Installation guide

Category
Fireplaces
Type
Installation guide
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/171
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
This appliance may be installed as an OEM installation
in manufactured home (USA only) or mobile home and
must be installed in accordance with the manufacturer’s
instructions and the manufactured home construction
and safety standard, Title 24 CFR, Part 3280 or Standard
for Installation in Mobile Homes, CAN/CSA Z240MH, in
Canada.
This appliance is only for use with the type(s) of gas
indicated on the rating plate.
In the Commonwealth of Massachusetts installation must
be performed by a licensed plumber or gas tter.
See Table of Contents for location of additional
Commonwealth of Massachusetts requirements.
- DO NOT store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other
appliance.
- What to do if you smell gas
DO NOT try to light any appliance.
DO NOT touch any electrical switch; do not use any
phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
- Installation and service must be performed by a qualied
installer, service agency, or the gas supplier.
Model:
GARN-MBK-IPI-B
NOTICE: DO NOT discard this manual!
R
WARNING: If the information in these instructions
is not followed exactly, a re or explosion may result
causing property damage, personal injury, or death.
!
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with
this appliance and shall be installed for the
protection of the children and other at-risk
individuals.
!
DANGER
Solitaire
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/172
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
Installation Standard Work Checklist ....................3
1 Product Specic and Important Safety Information
A. Appliance Certication ............................4
B. Glass Specications ..............................4
C. BTU Specications ...............................4
D. High Altitude Installations .......................... 4
E. Non-Combustible Materials Specication. . . . . . . . . . . . . . 4
F. Combustible Materials Specication .................4
G. Electrical Codes .................................4
H. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations ...............6
B. Tools and Supplies Needed ........................6
C. Inspect Appliance and Components ..................6
3 Framing and Clearances
A. Appliance Dimension Diagram ......................7
B. Clearances to Combustibles .......................8
C. Hearth Extension/Floor Protection ...................8
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances ...............9
B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
C. Approved Pipe ................................. 11
D. Use of Elbows .................................12
E. Measuring Standards ............................12
F. Venting Guidelines for Horizontal Runs .............. 13
G. Vent Diagrams .................................13
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles ..................25
B. Wall Penetration Framing/Firestops .................25
C. Ceiling Firestop/Floor Penetration Framing ...........26
D. Install Attic Insulation Shield .......................26
6 Appliance Preparation
A. Leveling the Appliance ...........................27
7 Venting and Chimneys
A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . . . . . . 28
B. Assemble Slip Sections ..........................29
C. Secure the Vent Sections .........................30
D. Disassemble Vent Sections .......................30
E. Vertical Termination Requirements ..................32
F. Horizontal Termination Requirements ...............34
8 Electrical Information
A. General Information .............................36
B. Wiring Requirements ............................ 37
9 Gas Information
A. Fuel Conversion ................................42
B. Gas Pressure ..................................42
C. Gas Connection ................................42
D. High Altitude Installations ......................... 42
E. Air Shutter Setting ..............................43
10 Appliance Setup
A. Remove Fixed Glass Assembly .................... 44
B. Remove the Shipping Materials ....................44
C. Clean the Appliance .............................44
D. Install the Log Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 45
E. Install Fixed Glass Assembly ...................... 46
F. Adjust Flue Restrictor ............................46
11 Reference Materials
A. Vent Components Diagrams ...................... 47
B. Accessories ...................................53
= Contains updated information.
Table of Contents
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/173
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): GARN-MBK-IPI-B
Date Installed:
Location of Stove:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
___________________________
Stove is installed level. (Pg. 26) ___________________________
Venting/Chimney Section 7 (Pg 27-34)
___________________________
Venting installed, locked and secured in place with proper clearance. ___________________________
___________________________
Attic insulation shield installed. ___________________________
___________________________
___________________________
Electrical Section 8 (Pg 35-39)
Unswitched power (110-120 VAC) provided for the appliance. ___________________________
Switch wires properly installed. ___________________________
Gas Section 9 (Pg 40-41)
___________________________
Was a conversion performed? ___________________________
___________________________
___________________________
Appliance Setup Section 10 (Pg 42-44)
All packaging and protective materials are from removed inside/under/on
the appliance). ___________________________
Logs and embers installed correctly. ___________________________
Glass assembly installed and secured. ___________________________
Accessories installed properly. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
gas leaks exist. ___________________________
2345-985_R2 03/17
= Contains updated information.
Hearth & Home Technologies recommends the following:
• That this checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in
this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/174
B. Glass Specications
This appliance is equipped with 5 mm ceramic glass.
Replace glass only with 5 mm ceramic glass. Please contact
your dealer for replacement glass.
C. BTU Specications
This product is listed to ANSI standards for “Vented Gas
Fireplace Heaters” and applicable sections of “Gas
Burning Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for Use
at High Altitudes”.
NOTICE: This installation must conform with local codes. In
the absence of local codes you must comply with the National
Fuel Gas Code, ANSI Z223.1- latest edition in the U.S.A. and
the CAN/CGA B149 Installation Codes in Canada.
A. Appliance Certication
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental
room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
1
Product Specic and Important Safety Information
MODELS: GARN-MBK-IPI-B
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: ANSI Z21.88-2014/CSA 2.33-2014
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above
2000 feet.
• In CANADA: Input ratings are certied without a reduction
of input rate for elevations up to 4500 feet (1370 m)above
sea level. Please consult provincial and/or local authorities
having jurisdiction for installations at elevations above
4500 feet (1370 m).
Check with your local gas utility to determine proper orice
size.
E. Non-Combustible Materials Specication
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC shall be considered non-
combustible materials.
F. Combustible Materials Specication
Materials made of or surfaced with wood, compressed paper,
plant bers, plastics, or other material that can ignite and burn,
whether ame proofed or not, or plastered or unplastered
shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
Models
(U.S. or Canada)
Maximum
Input BTU/h
Orice
Size
(DMS)
AFUE
State Steady
Efciency %
P4 %
GARN-MBK-IPI-B (NG)
(0-2000 ft)
14,500 49 68.6% 63% 62%
GARN-MBK-IPI-B (LP)
(0-2000 ft)
13,000 57 69.4% 63% 62%
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/175
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the
oor level where the gas equipment is to be installed. In
addition, the installing plumber or gas tter shall observe
that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional level
of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of hard
wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and
be ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print size no
less than one-half (1/2) in. in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part
for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
• The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all
venting instructions, all parts lists for venting instructions,
and/or all venting design instructions shall remain with the
appliance or equipment at the completion of the installation.
See Gas Connection section for additional
Commonwealth of Massachusetts requirements.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/176
2
Getting Started
A. Design and Installation Considerations
Quadra-Fire direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside. No
additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, re ofcials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system conguration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
Whether optional accessories—devices such as a fan or
remote control—are desired.
C. Inspect Appliance and Components
Carefully remove the appliance and components from
the packaging.
The vent system components and optional accessories
may be shipped in separate packages.
• If packaged separately, the log set must be installed.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
Read all of the instructions before starting the
installation. Follow these instructions carefully
during the installation to ensure maximum safety
and benet.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers Hammer
Phillips screwdriver Manometer
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Flat blade screwdriver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300 ºF minimum continuous exposure
rating)
One 1/4 in. female connection (for optional fan).
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied service
technician, service agency or your dealer.
Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
Installation and use of any damaged appliance or vent system
component.
Modication of the appliance or vent system.
Installation other than as instructed by Hearth & Home
Technologies.
Improper positioning of the gas logs or the glass door.
Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a re hazard.
Installation and service of this appliance should be
performed by qualied personnel. Hearth & Home
Technologies suggests NFI certied or factory trained
professionals, or technicians supervised by an NFI
certied professional (www.ncertied.org).
RISK OF FIRE, EXPLOSION OR ELECTRIC SHOCK!
DO NOT use this appliance if any part has been under
water. Call a qualied service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
WARNING
!
WARNING
!
RISK OF FIRE OR EXPLOSION! Damaged parts
could impair safe operation. DO NOT install damaged,
incomplete or substitute components. Keep appliance
dry.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/177
3
Framing and Clearances
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only.
Figure 3.1 - Appliance Dimensions
Location Inches Millimeter Location Inches Millimeter
A 17-7/8 454 E 18-1/8 451
B 15-3/8 391 F 17-3/8 441
C 23-5/8 600 G 14-1/4 362
D 8-15/16 227 H 18 457
NOTE: Side view diagram show gas appliance equipped with optional blower, Part # BK-GAS
GAS
LINE
ELECTRICAL
CORD
SIDE
BACK
FRONT
TOP
E
D
C
A
B
H
G
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/178
B. Clearances to Combustibles
When selecting a location for the appliance it is important to
consider the required clearances to walls. See Figure 3.2.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access. Due
to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
NOTICE: Illustrations reect typical installations and are FOR
DESIGN PURPOSES ONLY. Illustrations/diagrams are not
drawn to scale. Actual installation may vary due to individual
design preference.
NOTICE: Some carpet materials may be sensitive to radiant
heat from the appliance causing discoloration or odor.
Figure 3.2 - Appliance Locations
A
B
F
E
A
"A"
measurement is from
stove top, not side
or *B
D* G*
H
G**
D**
EXTERIOR
WALL
CEILING
C
C
or *C
or *C
A
G*
A
G**
C. Hearth Extension/Floor Protection
CAUTION! Risk of Fire or Injury! Install appliance on a
stable, level, platform or oor strong enough to support
appliance without tipping.
A non-combustible hearth pad is not required. However,
the floor beneath the appliance must be stable, level, and
strong enough to support the appliance without a tipping
hazard. It is permissible to place the appliance on carpet.
NOTE: Flooring beneath appliance may reach 90° plus room
ambient temperature. Check with flooring manufacturer for
maximum temperature allowed on flooring surfaces.
Note: Dimensions are minimums as shown and may not be typical for all applications. An alcove installation is shown
above on left.
Note: If optional BK-GAS fan kit is desired, appliance should be changed to *B or *C dimensions.
Alcove Installation
Model A B *B C *C D* D** E F G* G** H
GARN-MBK-IPI-B
Inches
6 2 5 2 5 55-1/4 43 36 30 32-1/2 20-1/4 3
Millimeters
152 51 127 51 127 1403 1092 762 762 826 514 76
D* and G*= Vented with minimum vertical pipe as shown.
D** and G**= Horizontally vented, no vertical component.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/179
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 4.1 - Minimum Height From Roof To Lowest Discharge Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4
Termination Location and Vent Information
Fire Risk.
Maintain vent clearance to combustibles as
specied.
DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and re.
Figure 4.2 - Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Term
ination
Cap **
A *
*
If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
WARNING
!
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1710
B. Chimney Diagram
Figure 4.3 - Minimum Clearances for Termination
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
B = 12 inches.................clearance to window or door that may
be opened, or to permanently closed
window
C = 18 inches.................clearance below unventilated soft
18 inches.................clearance below ventilated soft
30 inches.................clearance below vinyl soffits and
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator
G = 3 ft ...........................clearance to gas service regulator vent
outlet
H = 12 inches.................clearance to non-mechanical
(unpowered) air supply inlet,
combustion air inlet or direct-vent
termination
i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet
All mechanical air intakes within 10 feet of a termination cap must
be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway.
A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings.
C
J
B
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
V
H
A
V
V
H
X
= AIR SUPPLY INLET
V
= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
O
N
P
R
Q
Electrical
Service
V
K
V
K
V
L
C
V
Q
MIN
R
MAX
1 cap 3 feet 2 x Q
ACTUAL
2 caps 6 feet 1 x Q
ACTUAL
3 caps 9 feet 2/3 x Q
ACTUAL
4 caps 12 feet 1/2 x Q
ACTUAL
Q
MIN
= # termination caps x 3 R
MAX
= (2 / # termination caps) x Q
ACTUAL
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soft and overhang
42 inches ......... vinyl soft and overhang
P = 8 ft.
Measure horizontal clearances from this surface.
Measure vertical clearances from this surface.
CAUTION! Risk of Burns! Termination caps are HOT, consider
proximity to doors, trafc areas or where people may pass or
gather (sidewalk, deck, patio, etc.). Listed cap shields available.
Contact your dealer.
Local codes or regulations may require different clearances.
Vent system termination is NOT permitted in screened porches.
Vent system termination is permitted in porch areas with two or
more sides open.
Hearth & Home Technologies assumes no responsibility for the
improper performance of the appliance when the venting system
does not meet these requirements.
Vinyl protection kits are suggested for use with vinyl siding.
M = 18 inches .................... clearance under veranda, porch, deck,
balcony or overhang
42 inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the oor.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the
electrical service.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1711
C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies SLP, Simpson Duravent and ICC venting
systems. Refer to Section 11.A for vent component
information and dimensions.
DO NOT mix pipe, ttings or joining methods from different
manufacturers.
The pipe is tested to be run inside an enclosed wall. There
is no requirement for inspection openings at each joint
within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving a
separate solid fuel burning appliance.
DO NOT USE FIELD-FABRICATED VENTING
COMPONENTS.
This product is approved to be vented either horizontally,
through the side wall or vertically through the roof. You may
vent through a Class A or masonry chimney if an approved
adapter is used.
This appliance is a direct vent heater. All combustion air must
come directly from the outside of the building. The vent pipe
for this unit consists of an inner and an outer pipe. The inner
pipe carries the appliance exhaust out of the system, and
the outer pipe brings fresh combustion air into the appliance.
A round support box/wall thimble or heat shield is required
when the venting passes through a combustible wall.
A support box or ceiling restop is required when the
venting passes through a ceiling.
• Roof ashing and a storm collar are required when venting
passes through the roof.
• Follow instructions provided with the venting for installation
of these items.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1712
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects
when calculating the effects. Use the rise for the vertical
aspect and the run for the horizontal aspect. See Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow. On
45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm)
horizontal run and 8-1/2 in. (216 mm) vertical run. A length
of straight pipe is allowed between two 45º elbows. See
Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for SLP
elbows.
Figure 4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
Vent Type
X
Inches Millimeters
SLP 11-1/4 286
Figure 4.5 - Vertical and Horizontal Offset for SLP Elbows
Vent
Type
X Y
Inches Millimeters Inches Millimeters
SLP 5 127 11-3/4 298
SLP
Pipe
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
SLP4 4 102 2-3/4 70
SLP6 6 152 4-1/4 108
SLP12 12 305 8-1/2 216
SLP24 24 610 17 432
SLP36 36 914 25-1/2 648
SLP48 48 1219 34 864
SLP6A 3 to 6 76 to 152
2-1/8-4-1/4 54-108
SLP12A 3 to 12 76 to 305
2-1/8-8-1/2 54-216
E. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards:
• Pipe measurements are shown using the effective length of
pipe. See Figure 11.1 for SLP for information on effective
length of pipe components.
Horizontal terminations are measured to the outside
mounting surface (ange of termination cap) (see Figure
4.3).
Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with 1/4 inch rise per foot.
Y
X
X
X
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1713
G. Vent Diagrams
General Rules:
SUBTRACT 3 ft. from the total H measurement for each
90º elbow installed horizontally.
SUBTRACT 1 ft. from the total H measurement for each
45º elbow installed horizontally.
A maximum of three 90º elbows (or six 45º elbows) may
be used in any vent conguration. Some elbows may be
installed horizontally. See specic vent diagrams.
When penetrating a combustible wall, a wall shield restop
must be installed.
When penetrating a combustible ceiling, a ceiling restop
must be installed.
F. Venting Guidelines for Horizontal Runs
C
L
Figure 4.6
C
L
REAR VENT
(WITH VERTICAL RISE)
2 FT.
MINIMUM
Max Horizontal Run,
Rear Vent (No Rise)
8 in. (203 mm)
See Figure 4.6.
Max Horizontal Run 8 ft (2.4 m) when vertical rise is
8 ft (2.4 m)
Rear Vent with Vertical
Rise
Min of 2 ft vertical (610 mm)
must be used prior to any
horizontal run. See Figure 4.6.
Horizontal Run requires a non-combustible support every
3 ft (914 mm), i.e., plumbing tape
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1714
Rear Vent - Horizontal Termination
No Elbow
Figure 4.7
H
1
Natural Gas:
H
1
= 14 in. (356 mm) Maximum
Propane:
H
1
= 8 in. (203 mm) Maximum
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1715
Rear Vent - Horizontal Termination - (continued)
Back to Back 90° Elbows Only
Figure 4.8
H
1
= 24 in. (610 mm) Maximum
H
1
Note: This conguration is recommended for corner installations.
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1716
Rear Vent - Horizontal Termination - (continued)
Note: Flue restrictor may need to be adjusted as vertical
dimension increases.
Note: For optimum ame appearance, air shutter may need to
be adjusted as vertical dimension increases.
2 Elbows to Max. Horizontal
V
1
Minimum H
1
Maximum H
1
+ H
2
Maximum
2 ft .61 m 8 in. 203 mm 18 in. .46 m
4 ft. 1.2 m 8 in. 203 mm 3 ft., 3 in. 1 m
6 ft. 1.8 m 8 in. 203 mm 6 ft. 1.8 m
8 ft. 2.4 m 8 in. 203 mm 8 ft. 2.4 m
10 ft. 3.1 m 8 in. 203 mm 7 ft., 3 in. 2.2 m
12 ft. 3.7 m 8 in. 203 mm 6 ft., 4 in. 1.9 m
14 ft. 4.3 m 8 in. 203 mm 5 ft., 5 in. 1.6 m
16 ft. 4.9 m 8 in. 203 mm 4 ft., 6 in. 1.4 m
18 ft. 5.5 m 8 in. 203 mm 3 ft., 7 in. 1.0 m
20 ft. 6.1 m 8 in. 203 mm 2 ft., 8 in. 813 mm
22 ft. 6.7 m 8 in. 203 mm 1ft., 10 in. 559 mm
Figure 4.9
H
1
H
2
V
1
Two Elbows
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1717
Three Elbows
Note: Flue restrictor may need to be adjusted as vertical
dimension increases.
Note: For optimum ame appearance, air shutter may need to
be adjusted as vertical dimension increases.
3 Elbows to Max. Horizontal
V
1
Minimum H
1
Maximum H
Total
6 ft. 1.8 m 8 in. 203 mm 3 ft. 914 mm
8 ft. 2.4 m 8 in. 203 mm 5 ft. 1.5 m
10 ft. 3.1 m 8 in. 203 mm 4ft., 3 in. 1.3 m
12 ft. 3.7 m 8 in. 203 mm 3 ft., 4 in. 1.0 m
14 ft. 4.3 m 8 in. 203 mm 2 ft., 5 in. 737 mm
16 ft. 4.9 m 8 in. 203 mm 1ft., 6 in. 457 mm
Figure 4.10
INSTALLED
HORIZONTALLY
H
3
H
1
H
2
V
1
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1718
Rear Vent - Vertical Termination
H
1
Minimum H
1
Maximum V
1
Minimum V
1
Maximum
6 in. 152 mm 14 in. 357 mm 6 ft. 1.8 m 25 ft. 7.6 m
Note: Flue restrictor may need to be adjusted as vertical
dimension increases.
Note: For optimum ame appearance, air shutter may need to
be adjusted as vertical dimension increases.
Figure 4.11
H
1
V
1
One Elbow
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1719
Rear Vent - Vertical Termination - (continued)
Three Elbows
Note: Flue restrictor may need to be adjusted as vertical
dimension increases.
Note: For optimum ame appearance, air shutter may need to
be adjusted as vertical dimension increases.
3 Elbows to Maximum Vertical
V
1
Minimum H
1
Maximum H
Total
V
1
+ V
2
MAXIMUM
6 ft. 1.8 m 8 in. 203 mm 3 ft. 914 mm 19 ft., 7 in. 6.0 m
8 ft. 2.4 m 8 in. 203 mm 5 ft. 1.5 m 14 ft., 11 in. 4.5 m
10 ft. 3.1 m 8 in. 203 mm 4 ft., 3 in. 1.3 m 16 ft., 10 in. 5.1 m
12 ft. 3.7 m 8 in. 203 mm 3 ft., 4 in. 1.0 m 19 ft. 5.8 m
14 ft. 4.3 m 8 in. 203 mm 2 ft. 5 in. 737 mm 20 ft., 9 in. 6.3 m
16 ft. 4.9 m 8 in. 203 mm 1 ft., 6 in. 457 mm 23 ft., 2 in. 7.1 m
V
2
V
1
H
2
H
1
Figure 4.12
Quadra-Fire • GARN-MBK-IPI-B Installation Manual • 2345-983_R8 • 07/1720
Class A Metal Chimney
Prior to installing the gas stove, ensure that the existing
chimney is functionally sound and clean.
Have the chimney and adjacent structure inspected
and cleaned by qualied professionals. Hearth & Home
Technologies recommends that NFI or CSIA certied
professionals, or technicians under the direction of
certied professionals, conduct a minimum of a NFPA
211 Level 2 inspection of the chimney.
Replace component parts of the chimney and replace
as specied by the professionals.
See section 11 for venting components
Figure 4.15
Figure 4.16
5. Pull the flex pipe down through the ceiling support box,
until it protrudes approximately 3 in. (76mm). Connect
the flex pipe to the retro connector, and attach with sheet
metal screws.
6. Push the flex pipe back up into the ceiling support box,
center the retro connector, and attach it to the support
box with sheet metal screws.
7. The connection between the appliance and the retro
connector may be completed with sections of direct vent
pipe.
Top Adapter
(Included in Link-Stove Kit)
Sheet Metal Screws
4” Flex Pipe
(Included in Link-Stove Kit)
Figure 4.14
High Wind Termination Cap
(Part SLP-TVHW)
Sheet Metal Screws
Drill Four 1/8 in.
(3mm) Diamater
Holes
TERMINATION CAP
(Includ. in Link-Stove Kit)
EXISTING METAL
CHIMNEY SYSTEM
TOP ADAPTOR
(Includ. in Link-Stove Kit)
DIRECT VENT PIPE
(Length as required)
FLASHING
(Includ. in Link-Stove Kit)
4 in. (102mm) FLEX PIPE
(Includ. in Link-Stove Kit)
RETRO CONNECTOR
(Includ. in Link-Stove Kit)
Figure 4.13
1. Remove existing chimney cap.
2. Measure the distance from the top of the chimney to the
bottom of the ceiling support box, add 3 in. (76mm) to
this measurement, and cut a section of 4 in. (101mm)
flex pipe to that length (the flex should be fully extended).
3. Connect the end of the flex pipe section to the underside
of the top adapter, using four sheet metal screws. See
Figure 4.14.
4. Pass the flex pipe down through the center of the
chimney system, and center the top adapter on the top
of the chimney pipe. Drill four 1/8 in. (3mm) diameter
holes through the top adapter, and into the chimney top,
preferably from the side of the top adapter. Ensure that
you are drilling into the metal on the chimney. Twist lock
the high wind termination cap onto the top adapter. See
Figure 4.15 and Figure 4.16.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53