Danfoss Controller type AKC 24A for liquid level control. Vers. 1.0x. AKA 21 Installation guide

Category
Measuring, testing & control
Type
Installation guide
ADAP-KOOL
®
RC.1N.H1.02 06-1996
Controller type AKC 24A
for liquid level control
Software version 1.0x
Menu operation via AKA 21
2 Menu operation RC.1N.H1.02 © Danfoss 06/96 AKC 24A Version 1.0x
System survey
A refrigerating plant fitted with ADAP-KOOL
®
refrigeration controls will mostly consist of several
controllers where each controller will regulate its own refrigeration appliance/cold room.
The system has been designed in such a way that contact can be made to each and every
controller via a data communication system. One specific controller is selected, and it will now
be possible to make settings and readouts for this unit.
The individual controllers can be operated in two ways:
1. With control panel type AKA 21.
Use this document when operation takes place in this
way.
2. With PC and system software type AKM.
Operation
Validity
This menu operation (dated June 1996), applies to AKC 24A with the following code
number:
084B2029 that is fitted with software version 1.0x.
AKC 24A Version 1.0x Menu operation RC.1N.H1.02 © Danfoss 06/96 3
All controllers that are connected to the same network can be operated with the control panel.
There may be as many as 125 controllers, and they are shown in groups of 16 on the display.
A system is shown here which consists of more than 16 controllers. The meaning of the letters
is, as follows:
A: AKC controller
E: Controller with active ERROR (on addresses 2, 11 and 12 in this example)
g: Gateway (to addresses 13 and 14 in this example)
G: Gateway with connected printer
: A blank field indicates that there is no unit with this address.
Select the unit that is to be operated by using the “+/On” or “-/Off” key, and push “Enter”. In this
example you select the controller with address 4.
If the system comprises more than 16 units or units with an address code higher than 16, you
may change to the next group by pushing "".
When a controller has been selected, you can make settings in it. This setting is performed, as
follows:
Shown in the upper right corner of the display is the setting with which the controller is
operating. Below that value a new setting may be made. Use the three keys “+/ON”, “-/OFF” and
“Digit” for setting the new value. This new value will not govern the regulation until you push the
key “Enter”.
Select a controller
Settings of a controller
5
-50 to +50 5
ON
OFF / ON ON
1 < 1 > 16
AEAAAAAAAAEEgg A
1 < 4 > 16
AEAAAAAAAAEEgg A
17 < 17 > 32
AAA
The keys enable you to move directly to the selected menus. The function keys have been
factory-programmed to menus of relevance for the individual controller. For each and every
controller in the system, you may select a new function for a function key. (The “Clear” key is
also a function key). Programming of a function key is performed, as follows:
1. Select the required menu on the display.
2. Push the “key” key.
3. Push one of the function keys.
Factory setting:
F1: Main Switch
F2: AKV OD %
F3: Level %
Function keys
4 Menu operation RC.1N.H1.02 © Danfoss 06/96 AKC 24A Version 1.0x
Level 1 Level 2 Level 3 Description
DANFOSS AKC 24 A Shows controller type, weekday and time
An E on the display means an error has been recorded.(See page 8)
1
Clock: Day Setting of week day (1 = Monday, 7 = Sunday)
(Mon)1 (Sun)7
1:01
|
Clock: Hour Setting of hours
0 23
1:02
|
Clock: Min. Setting of minutes
0 59
1:03
|
Code No. Reading of the actual controller code no. and programme version
Prog.Ver.
1:04
|
System address Reading of the actual controller system address
Addr. yyy xxx yyy=network no. and xxx=address.
1:05 The system address can only be set via PC
|
Address Reading of the actual controller’s address
xxx (Setting on the controller’s DIP-switch)
1:06
|
Alarm report to Reading of the system address (receiver) the alarms are to be sent to.
Addr. yyy xxx The system address can only be set via PC
1:07
|
Gateway Address Reading of the address on the nearest gateway which has to effect alarms
xxx (see 1:07).
1:08 The address can only be set via PC
|
Main Function Main function
2
Alarm message Error log. The menu is only visible in case of an active error
(At alarm, an E is shown on the display)
2:01
See page 8 for list of alarm messages
2:01:01
|
Main Switch Access to the main switch.
Ctrl(1)/Serv(-1)
2:02
Main Switch Main switch: 1: Regulation
-1 / 0 / 1 0: Controller stop
2:02:01 -1: Service mode
AKC 24A Version 1.0x Menu operation RC.1N.H1.02 © Danfoss 06/96 5
|
Injection Expansion valve function
Control
3
Alarm message Error log is only visible in case of an active error.
At alarm an E is shown on the display.
3:01
See page 8 for list of alarm messages
3:01:01
|
Injection Ctrl. Reading of measurement values related to the expansion valve function
Measurements
3:02
Level % Actual level in % of input signal size (measuring range)
3:02:01
|
AKV OD % Opening degree of expansion valve in %
3:02:02
|
Injection Ctrl. Setting of expansion valve function
Settings
3:03
MaxLevel % Setting of upper value of regulation range
2 100 (level where the valve must close completely when regulation is carried out at
3:03:01 low pressure)
|
MinLevel % Setting of lower value of regulation range
0 98 (level where the valve must be completely open when regulation is carried out at
3:03:02 low pressure)
|
mA=0/Vol=1 Definition of input to be used for level signal
0 1 0: 4-20 mA input
3:03:03 1: 0-10 volt input
|
LP=0 / HP=1 Definition of regulating principle
0 1 0: On low-pressure side (valve closes at rising liquid level)
3:03:04 1: On high-pressure side (valve opens at rising liquid level)
|
PWM per. s AKV output period in seconds
3 12
3:03:05
|
Digital Output DO1 - DO3 functions
Functions
4
Alarm message Error log is only visible in case of an active error.
At alarm an E is shown on the display.
4:01
See page 8 for list of alarm messages
4:01:01
|
Digital Output DO1 - DO3 output status
Measurements
4:02
DO1 DO1 output status
4:02:01 (in pos. OFF the liquid level is above the set "DO1 High %" limit)
|
DO2 DO2 output status
4:02:02 (in pos. OFF the liquid level is above the set "DO2 High %" limit)
|
DO3 DO3 output status
4:02:03 (in pos. OFF the liquid level is below the set "DO3 Low %" limit)
6 Menu operation RC.1N.H1.02 © Danfoss 06/96 AKC 24A Version 1.0x
|
Digital Output DO1 - DO3 settings
Settings
4:03
DO1 High % Setting of limit value where output DO1 cuts out
0 100
4:03:01
|
DO1 Del. s Setting of time delay for DO1 (seconds)
0 300
4:03:02
|
DO2 High % Setting of limit value where output DO2 cuts out
0 100
4:03:03
|
DO2 Del. s Setting of time delay for DO2 (seconds)
0 300
4:03:04
|
DO3 Low % Setting of limit value where output DO3 cuts out
0 100
4:03:05
|
DO3 Del. s Setting of time delay for DO3 (seconds)
0 300
4:03:06
|
Service Mode Service function
5
Measurements Measurements
5:01
0 - 10 Volt Voltage measured at input
5:01:01
|
4 - 20 mA Current measured at input
5:01:02
|
P1 Bar Pressure measured with pressure transmitter connected to P1 inlet
5:01:03
|
P2 Bar Pressure measured with pressure transmitter connected to P2 inlet
5:01:04
|
S5 °C Temperature measured on inlet
5:01:05
|
S6 °C Temperature measured on inlet
5:01:06
|
S7 °C Temperature measured on inlet
5:01:07
|
S8 °C Temperature measured on inlet
5:01:08
|
S9 °C Temperature measured on inlet
5:01:09
|
S10 °C Temperature measured on inlet
5:01:10
|
DI 1 Statement of force closing at terminal DI 1
5:01:11
AKC 24A Version 1.0x Menu operation RC.1N.H1.02 © Danfoss 06/96 7
|
Manual Control Forced servo operation of outlets (service)
>>
5:02
Man. Ctrl. ON: Manual setting allowed (se 2:02:01)
OFF ON PLEASE NOTE: No monitoring
5:02:01 When manual setting has been completed, setting must be changed to OFF
|
AKV 1 % Forced servo operation of the expansion valve
0 100
5:02:02
|
AKV 2 % Forced servo operation of the expansion valve
0 100
5:02:03
|
AKV 3 % Forced servo operation of the expansion valve
0 100
5:02:04
|
DO1 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:05
|
DO2 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:06
|
DO3 Forced servo operation of outlet
OFF ON On = normal Off = alarm
5:02:07
|
Alarm Relay Forced servo operation of alarm relay outlet
OFF ON On = normal Off = alarm
5:02:08
8 Menu operation RC.1N.H1.02 © Danfoss 06/96 AKC 24A Version 1.0x
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material.
Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such
alternations can be made without subsequential changes being necessary in specifications already agreed.
AC-RDT
Error Log
The following readouts are only visible if there is an active error
AKA 21 operation:
When the error is corrected, the error message can be removed by pressing ENTER.
AKM operation:
A sensor fault will activate the alarm output and a message will be sent out via DANBUSS®.
The PC user of the AKM programm can set whether the other alarms are "to activate the alarm
output and send via DANBUSS®", only "send via DANBUSS®" or "whether they are not to be
displayed".
Sx Error ( ) Sx sensor error Check sensor connection/sensor resistance
Px Error ( ) Pressure Check connections
transmitter error
Standby Mode Control stopped Function switch (Main switch) is either in pos. "Controller stopped" or
"Service" (cf. 2:02:01)
High level Level alarm Set limit value has been exceeded
alarm1
High level Level alarm Set limit value has been exceeded
alarm2
Low level alarm Level alarm Set limit value has been exceeded
4 - 20 mA Signal failure Received signal is outside the measuring range
signal error
0 - 10 V Signal failure Received signal is outside the measuring range
signal error
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Danfoss Controller type AKC 24A for liquid level control. Vers. 1.0x. AKA 21 Installation guide

Category
Measuring, testing & control
Type
Installation guide