Danfoss AKV 10-n (n=1-8) Installation guide

Type
Installation guide
Installation Guide
Solenoid Valve
Types AKV 10-n (n = 1 – 8)
© Danfoss A/S (AC-MCI / jmn), 2012-12 DKRCC.PI.VA1.A2.02 / 520H6997 1
068R9524
068R9524
AKV 10-n
AKV 10-1, AKV 10-2,
AKV 10-3, AKV 10-4,
AKV 10-5, AKV 10-6
AKV 10-7, AKV 10-8
a 1.9 in. 1.9 in.
b 1.8 in. 1.8 in.
c 3.0 in. 2.9 in.
d 2.6 in. 3.0 in.
Refrigerants:
R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contact Danfoss.
The valve should be mounted at least 7 times the outside
diameter of the refrigerant line from the distributor.
The coil must be removed and
the valve must be wrapped with
awet cloth prior to soldering.
max. 150 °C (300 °F)
AKV 10-n
AKV 10-1, AKV 10-2,
AKV 10-3, AKV 10-4,
AKV 10-5, AKV 10-6
AKV 10-7, AKV 10-8
A
In are
3
/
8
in.
1
/
2
in.
B
Out are
1
/
2
in.
5
/
8
in.
C
In solder
3
/
8
in.
1
/
2
in.
D
Out solder
1
/
2
in.
5
/
8
in.
B D
A
C
Warning
Never switch on power to the
coil when the coil is dismounted
from the valve. Otherwise the
coil may be damaged and there
is risk of injuries and burns.
New Used
45 Nm
2 DKRCC.PI.VA1.A2.02 / 520H6997 © Danfoss A/S (AC-MCI / jmn), 2012-12
Do not insulate
Max. working
pressure
AKV 10 -1
PS/MWP = 28 bar / 400 psig
AKV 10-2
AKV 10-3
AKV 10-4
AKV 10-5
AKV 10-6
AKV 10-7
AKV 10-8
Max. test pressure P
e
= 36 barg / 520 psig
Max. dierential pressure
MOPD = P
1
- P
2
=18 bar / 260 psi
The gasket must be exchanged, if the valve is dismantled