FIELD CONTROLS EvenAir T21WF User manual

Category
Thermostats
Type
User manual

This manual is also suitable for

FIELD CONTROLS EvenAir T21WF is a remarkable thermostat with airflow control that allows you to manage the heating, cooling, and airflow in your home, ensuring a uniformly comfortable environment. It comes with a temperature sensor to monitor the temperature in the sleeping area, and two modulating dampers to control the airflow to the living and sleeping areas. The EvenAir T21WF thermostat automatically adjusts the airflow to the space that needs it, providing a comfortable temperature throughout your home.

FIELD CONTROLS EvenAir T21WF is a remarkable thermostat with airflow control that allows you to manage the heating, cooling, and airflow in your home, ensuring a uniformly comfortable environment. It comes with a temperature sensor to monitor the temperature in the sleeping area, and two modulating dampers to control the airflow to the living and sleeping areas. The EvenAir T21WF thermostat automatically adjusts the airflow to the space that needs it, providing a comfortable temperature throughout your home.

P/N 780101703 3/18 Rev Awww.fieldcontrols.com
This device MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.The definition of
a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in,
and is responsible for, the installation and operation of HVAC applicances, who is experienced in such work, familiar with all the
precautions required, and has complied with all the requirements of the authority having jurisdiction.
READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.
Installed By:_______________________________________ Phone: _____________________ Installation Date: _____________
Please retain these instructions after installation.
The EvenAir WiFi thermostat controls heating, cooling and AIRFLOW to the sleeping and living
areas in a home and provides remote access to your HVAC system using a smart phone, tablet or
PC. The thermostat is installed in the downstairs living area, a temperature sensor is installed in the
upstairs bedroom area and two modulating dampers are installed to control the airflow to the
living and sleeping area.
The EvenAir thermostat monitors the temperature at the sensor and the temperature at the
thermostat every 2 minutes during heating and cooling calls. If the temperatures are different, the
EvenAir thermostat automatically adjusts the modulating dampers 2% so that more airflow is
directed to the space that needs it for a uniformly comfortable home.
COMPONENTS:
EvenAir T21WF Thermostat
EvenAir TS51 or TS52 Wired Temperature Sensor(s) (sold separately)
EvenAir AMT Type Motorized Damper, With Terminals (sold separately)
T21WF
R
INSTALLATION AND USER MANUAL
THERMOSTAT WITH AIRFLOW CONTROL
C
N
O
O
L
T
S
R
F
I
E
L
D
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
R
Wi
Fi
WiFi
R
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
UP/DOWN Keys
SYSTEM MODE Key
Displays the living area or
sleeping area temperature.
Displays the Thermostat Mode
HOLD, SCHEDULE or VACANT
Displays the time, day and
schedule. MORNING, DAYTIME,
EVENING or NIGHT
MENU Key
MODE Key
Displays the sleeping area airflow
Displays the heating or
cooling temperature
FAN MODE Key
Displays the living area airflow
NEXT Key
ENTER Key
SYSTEM MODES
Hold, Schedule or Vacant
Morning, Daytime, Evening and Night
Weekdays and weekend – 5/2
Temperature is held for 3 hours when adjusted in Schedule
mode.
FAN MODES
Airflow control can be turned off and the thermostat will operate
as a typical thermostat.
Maximum airflow limits can be set for heating and cooling
modes during installation.
NIGHTTIME OPERATION
Gas/electric equipment with 2-stage heating and 1-stage
cooling or 1-stage heating and 2-stage cooling and heat
pumps with 2-stage heating and 2-stage cooling.
One TS51 sensor or two TS52 temperature sensors can be used
in the sleeping area.
Round or rectangular dampers using the AMT actuator and up
to 1 inch static pressure.
Operates on 24VAC from the HVAC equipment using the R and
C wires.
Connects to the home WiFi network to provide remote access
via the internet using smart phone, tablet or PC.
FEATURES
The airflow to the living area or sleeping area can be adjusted.
After 3 hours, the thermostat returns to automatic airflow
control.
Displays User options.
Selects Thermostat Mode
HOLD, SCHEDULE or VACANT
OFF, HEAT, COOL or AUTO
AUTO or ON
Used to save options and
return to thermostat operation
Used to advance through
options
Off, Heat, Cool, Auto
Auto or Continuous
THERMOSTAT MODES
PROGRAMS PER DAY
PROGRAM FORMAT
TEMPERATURE OVERRIDE
AIRFLOW OVERRIDE
AIRFLOW CONTROL
AIRFLOW LIMITS
At night, the EvenAir thermostat uses the temperature sensor in
the sleeping area to control heating and cooling calls and
directs more airflow to the sleeping area.
COMPATIBLE EQUIPMENT
TEMPERATURE SENSOR
MODULATING DAMPERS
POWER
WiFI
THERMOSTAT OVERVIEW
R
Thank you for purchasing the EvenAir System from Field Controls. The EvenAir products are compatible
with any HVAC system having accessible 24VAC terminals.
WiFi
Displays WiFi status
Press the touchscreen with your fingertip only, using a firm touch. Do not use a sharp object such as a pen or pencil.
The touchscreen is a resistive touch and responds differently than touchscreens found in smart phones/devices.
!
page 2 of 16 P/N 780101703 3/18 Rev A
HOMEOWNER
Overriding Automatic Airflow
Terminating Automatic Airflow
THERMOSTAT OPERATION AND USER SETTINGS
Set Time and Day
Set System Mode
Set Fan Mode
Temperature Override
Set Thermostat Mode
Changing Setpoint Temperature
Displaying Upstairs Temperature
EvenAir Thermostat Operation
1
2
3
4
5
6
7
8
9
Install Batteries
Set Schedule
Turn Automatic Airflow Control On/Off
Turn Nighttime Airflow Control On/Off
Clean the Touchscreen
Turn Thermostat WiFi On
Start Linking WiFi Thermostat
Set Nighttime Airflow in Heating
Set Nighttime Airflow in Cooling
User Options
1
2
3
4
5
6
7
8
FEATURES
NIGHTTIME AIRFLOW CONTROL
The Nighttime Airflow Control option is an energy saving feature where the thermostat uses the temperature sensor
in the bedroom area to control heating and cooling calls and directs more airflow to the bedroom at night
and less airflow to the unoccupied living . Nighttime Airflow Control begins at 10:00pm but can be changed
by accessing the schedule in the User Options. The airflow to the bedroom space defaults to 130% but can be
adjusted for both heating and cooling in the User Options. Nighttime Airflow Control is defaulted to On but can be
turned Off in the User Options. The homeowner should consider turning this option off if bedrooms are located on
the same floor as the living area and using the same airflow trunk as the living area.
area
area
AUTOMATIC OR MANUAL AIRFLOW CONTROL
Automatic Airflow Control is the thermostat default and is typically used by homeowners to maintain uniform
comfort throughout the home. However, homeowners with unusual work schedules, home offices, etc. may want to
use the manual airflow control feature. This features allows the homeowner to change the airflow level as desired
and hold that level indefinitely. This feature needs to be enabled using Installer Option 18. The homeowner then
needs to turn automatic airflow control off using the User Options. The Nighttime Airflow Control option is still
enabled but can be turned off, if desired, using the User Options.
AIRFLOW OVERRIDE
DISPLAYING THE LIVING AND BEDROOM AREA TEMPERATURE
The living area temperature is normally displayed. The bedroom area temperature can be displayed by touching
Living on the touchscreen. The temperature will change to the bedroom space temperature, indicated by Sleeping.
Touch Sleeping to return to displaying the Living area temperature.
On occasion, homeowners may want to direct more airflow to an area. For example, during a party, more airflow
may be desired in the living area. The homeowner sets the airflow level to the area and the thermostat will hold
the airflow for 3 hours. After 3 hours, the thermostat returns to automatic airflow control.
Features
AIRFLOW CONTROL TURNED OFF
In some installations, the EvenAir thermostat has been installed to control the system only. The thermostat operates
just like any other thermostat. The airflow control options are disabled and airflow is no longer displayed on the
thermostat.
HOMEOWNER SECTION
This manual is separated into two different sections: one for the Homeowner and one for the System Installer.
The Homeowner section contains information on features and operation of the thermostat along with
optional user settings available to the homeowner.
WiFi REMOTE ACCESS
The EvenAir WiFi thermostat connects to the home’s WiFi network and provides remote access, via the internet, to your
home’s heating and cooling system from anywhere using a smart phone, tablet or PC.
page 3 of 16 P/N 780101703 3/18 Rev A
THERMOSTAT OPERATION
HOMEOWNER SECTION
Set Time and Day
ENTER
AM
Touch the
UP/DOWN keys to
change the HOUR.
Touch NEXT.
CHANGE THE HOUR
Touch the
UP/DOWN keys to
change the MINUTE.
Touch NEXT.
CHANGE THE MINUTE
Touch the
UP/DOWN keys to
change the DAY OF
THE WEEK.
Touch ENTER.
CHANGE THE DAY OF THE WEEK
Day
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
Touch here to change the time and day of the
week.
We
AM
ENTER
AM
Tu
AM
NEXT
NEXT
ENTER
Living
Sleeping
Living
1
Depending on the mode, setting the time
may reset the setpoint temperature to the
factory default heating or cooling setpoint.
i
Living
Schedule
AUTO
Set To
FAN
SYSTEM
Heat
OFF
Tu
Day
Living
MENU MODE
AM
Sleeping
Airflow %
Living
Tu
Day
Living
Schedule
AUTO
MENU MODE
Set To
AM
Sleeping
Airflow %
FAN
SYSTEM
Heat
HEAT
Living
Schedule
AUTO
Set To
FAN
SYSTEM
Cool
COOL
Tu
Day
Living
MENU MODE
AM
Sleeping
Airflow %
Living
Tu
Day
Living
Schedule
AUTO
Set To
AM
Sleeping
Airflow %
SYSTEM
Heat
AUTO
MENU MODE FAN
Heating and cooling
systems are off.
OFF
HEAT
Only heating calls are
enabled and heating
setpoint is displayed.
“HEAT” will blink in
an active heating call.
Only cooling calls are
enabled and cooling
setpoint is displayed.
“COOL” will blink in
an active cooling call.
COOL
AUTO
Heating or Cooling
calls are enabled.
“HEAT” will blink in
an active heating call
or “COOL” will blink
in an active cooling
call.
Set System Mode
2
Touch the SYSTEM key to display the SYSTEM
MODES: OFF, HEAT, COOL or AUTO. In AUTO
or OFF, the setpoint for the last system call is
displayed.
Set Fan Mode
Touch the key to change the FAN MODES -
AUTO or ON.
FAN
Tu
Day
Airflow %
COOL
Schedule
MENU MODE
Cool
Set To
AM
AUTO
ON
Fan is activated only
during heating or
cooling calls. This is
the most commonly
used setting.
Fan is continuously
on.
SYSTEM
Living
Living
Sleeping
FAN
3
AUTO
Tu
Day
Airflow %
COOL
Schedule
MENU MODE
Cool
Set To
AM
SYSTEM
Living
Living
Sleeping
FAN
ON
Set Thermostat Mode
4
Touch the key to display the THERMOSTAT
MODES: HOLD, VACANT and SCHEDULE.
MODE
Tu
Day
Airflow %
COOL
AUTO
FANMENU
Cool
Set To
SYSTEM
AM
SCHEDULE MODE
HOLD MODE
VACANT MODE
Setpoint temperatures
are changed at
scheduled times
defined by the user.
Setpoint temperatures
are set by the user.
No schedule is used.
Setpoint temperatures
are kept at the vacant
temperatures set by
the installer.
MODE
Living
Living
Sleeping
Tu
Day
Airflow %
COOL
AUTO
FANMENU
Cool
Set To
SYSTEM
AM
MODE
Living
Living
Sleeping
Tu
Day
Airflow %
COOL
AUTO
FANMENU
Cool
Set To
SYSTEM
AM
Schedule
MODE
Living
Living
Sleeping
Hold
Vacant
Changing the Setpoint Temperature
The UP/DOWN keys are used to change the
setpoint temperature.
Tu
Day
Airflow %
Schedule
MENU MODE
Cool
Set To
AM
Living
Living
Sleeping
5
Tu
Day
Airflow %
Schedule
MENU MODE
AM
Living
Living
Sleeping
Heat
Set To
COOL
AUTO
FAN
SYSTEM
Touch the UP key to
raise setpoint
temperature.
Touch the DOWN
key to lower setpoint
temperature.
COOL
AUTO
FAN
SYSTEM
Touch here to display
and change the
opposing setpoint
temperature.
Touch the UP/DOWN keys to change the setpoint
temperature for the opposing system. The
thermostat will return to displaying the active
setpoint after about 30 seconds.
An active heating call is indicated by HEAT
blinking. An active cooling call is indicated by
COOL blinking.
To override the setpoint temperature:
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
Touch the UP/DOWN
keys to adjust the
setpoint temperature.
The thermostat displays the temperature in the
downstairs living area and is indicated by Living.
The temperature in the upstairs sleeping area is
indicated by Sleeping. When the thermostat enters
Night Mode, the upstairs sleeping area temperature
will be displayed, indicated by Sleeping.
Displaying the Upstairs Temperature
MENU
Airflow %
We
Day
AUTO
FANMODE
Cool
Set To
SYSTEM
AM
Press Living to display
the upstairs Sleeping
area temperature.
Temperature Override
Schedule
Sleeping
COOL
Sleeping
Living
MENU
Airflow %
We
Day
AUTO
FANMODE
Cool
Set To
SYSTEM
AM
Schedule
Living
COOL
Sleeping
Living
The upstairs Sleeping
area temperature is
now displayed.
6
7
Overriding Automatic Airflow
Terminating Airflow Override
Touch the Airflow %
area to override
AUTOMATIC AIRFLOW
to the living area or
the upstairs sleeping
area.
To terminate Airflow
Override, touch the
AIRFLOW% area.
Touch the UP key to
increase the airflow to
the sleeping area or
touch the DOWN key
to increase airflow to
the living area.
Airflow % will blink to indicate airflow override.
After 3 hours, the thermostat returns to automatic
operation. The override range is defined by the
installer during set up.
8
9
COOL
AUTO
FANMENU
Cool
Set To
SYSTEM
PM
MODE
Living
Hold
We
Eve
COOL
Hold
AUTO
FANMENU MODE
SYSTEM
PM
Airflow %
Living
Sleeping
Living
Airflow %
Sleeping
Living
Eve
We
COOL
AUTO
FANMENU
Cool
Set To
SYSTEM
PM
MODE
Living
Hold
We
Eve
COOL
Hold
AUTO
FANMENU
SYSTEM
PM
Airflow %
Living
Sleeping
Living
Airflow %
Sleeping
Living
Eve
We
MODE
Then touch the
MODE key.
The thermostat returns to automatic airflow
control. The AIRFLOW % returns to the airflow
prior to the override.
Press Sleeping to
display the Living
area temperature.
After 3 hours, the
thermostat returns to
normal thermostat
operation.
page 4 of 16 P/N 780101703 3/18 Rev A
USER OPTIONS
HOMEOWNER SECTION
Change Factory Set Schedule
Touch the
key to display
SCHEDULE. If no
key is touched, the
thermostat returns to
normal operation
after about 30
seconds.
MENU
WeTuMo ThFr
Schedule
Touch the UP key to
select the weekday
schedule
(MoTuWeThFr) or
touch the DOWN
key to select the
weekend schedule
(SaSu). Touch NEXT.
SELECTING THE WEEKDAY OR
WEEKEND SCHEDULE
WeTuMo
Morn
ThFr
Schedule
MENU NEXT ENTER
AM
WeTuMo
Morn
ThFr
Schedule
Heat
Set To
AM
Touch the
UP/DOWN keys to
change the Morning
Start Time. Touch
NEXT.
SETTING THE MORNING
SCHEDULE START TIME.
Touch the
UP/DOWN keys to
change the Morning
Heating Setpoint.
Touch NEXT.
SETTING THE MORNING
HEATING TEMPERATURE.
MENU NEXT ENTER
1
Day
Airflow %
COOL
Schedule
AUTO
FANMODE
Cool
Set To
SYSTEM
Tu
AM
Living
Sleeping
Living
MENU
Nighttime Airflow Control On or Off
NIGHTTIME AIRFLOW CONTROL defaults to On
and is used to save energy. The thermostat uses
the temperature sensor in the sleeping area for
controlling heating and cooling calls. The airflow
is increased to 130% to the sleeping area and the
airflow is reduced to 70% to the unused living
area. The thermostat displays the sleeping area
temperature.
Night
Upstairs
Airflow %
Automatic Airflow Control On or Off
Thermostat defaults
to Automatic Airflow
Control On and
automatically directs
more airflow to where
it’s needed.
Airflow %
NEXT
To turn Automatic
Airflow Control OFF,
touch the DOWN
key. The user must
set the airflow when
airflow control is off.
MENU NEXT ENTER
MENU
2
i
This option is only displayed if User Airflow
Control has been turned On by the installer in
the Installer Options.
ENTER
Touch the key to save and go to next
option or touch the ENTER key to save the options
and return to normal thermostat operation.
MENU
3
This option is not displayed if Nighttime
Airflow Control has been turned off by the
installer using the Installer Options.
If bedrooms are located downstairs, consider
turning the Nighttime Airflow Control OFF.
Homeowners with an unusual schedule, home
office, etc. may want to use this option.
With Automatic Airflow Control Off, the
Nighttime Airflow option is still enabled. If
desired, the homeowner can turn the
Nighttime Airflow option off using User
Options.
Default start time for Nighttime Airflow is
10:00pm but can be changed using User
Option 1 to change the Night Schedule Start
Time.
Default airflow level upstairs is 130%. If a
different airflow level is desired, use User
Option 4 to change the airflow level in heating
and User Option 5 to change the airflow level
in cooling.
i
i
i
i
i
i
Touch the MENU key to save and go to next
option or touch the ENTER key to save the options.
Airflow %
NEXTMENU ENTER
Touch the MENU key until the following
thermostat screen is displayed.
Night
Upstairs
Airflow %
MENU NEXT ENTER
Touch the MENU key
to display
NIGHTTIME
AIRFLOW indicated
by nAF On or Off.
Touch the UP key to
turn the option ON.
Touch the DOWN
key to turn the
option OFF.
MENU NEXT ENTER
SETTING THE MORNING
COOLING TEMPERATURE.
WeTuMo
Morn
ThFr
Schedule
MENU
Cool
Set To
AM
Touch the
UP/DOWN keys to
change Morning
Cooling Setpoint.
Touch NEXT.
Continue setting the start times, heating setpoints,
cooling setpoints for the Day, Evening and Night
schedules.
NEXT ENTER
Touch ENTER to save the schedule.
Factory Set Schedule
Morn
Day
Even
Nite
Monday - Friday
The thermostat comes pre-set with the
following energy-saving schedule for
weekdays (Mon-Fri) and weekends (Sat-Sun).
Using these settings can reduce your heating
/cooling expenses.
6:00 AM
8:00 AM
6:00 PM
10:00 PM
70
62
70
62
Time Heat Cool
Morn
Day
Even
Nite
Saturday & Sunday
6:00 AM
8:00 AM
6:00 PM
10:00 PM
70
62
70
62
75
75
83
83
75
75
78
78
Time Heat Cool
Nighttime Airflow Control (cont.)
3
Set the Nighttime Airflow in Heating
This option is used to change the default
nighttime airflow in heating of 130% to a user
desired airflow level, not to exceed installer limits.
Night
Sleeping
Airflow %
Heat
Touch the key to display NIGHTTIME,
UPSTAIRS AIRFLOW IN HEATING indicated by
nAF Heat.
Use the UP/DOWN keys to adjust the airflow.
Touch the MENU key to save and go to next
option or touch the ENTER key to save the option.
MENU
Set the Nighttime Airflow in Cooling
This option is used to change the default
nighttime airflow in cooling of 130% to a user
desired airflow level, not to exceed installer limits.
Night
Sleeping
Airflow %
Cool
Touch the MENU key to display NIGHTTIME,
UPSTAIRS AIRFLOW IN COOLING indicated by
nAF Cool.
Use the UP/DOWN keys to adjust the airflow.
Touch the MENU key to save and go to next
option or touch the ENTER key to save the
options.
MENU ENTER
NEXT
MENU ENTER
NEXT
5
4
This option is not displayed if Airflow Control
has been turned off.
This option is not be displayed if Airflow
Control has been turned off.
i
i
page 5 of 16 P/N 780101703 3/18 Rev A
Clean the Touch Screen
This option disables the touch screen for 30
seconds to enable the user to clean the touch
screen by wiping down with a soft, damp cloth.
Touch the MENU key
to display CLEAN
DISPLAY option
indicated by CL. To
exit the option, touch
NEXT.
NEXT ENTERMENU
OFF
Touch ENTER to start
the 30 second count
down. The touch
screen is disabled
during this time.
INSTALL / REPLACE AA BATTERIES
Two AA batteries power
the clock when 24VAC
power is lost. Slide the
battery cover downward
and install the two AA
batteries, paying
attention to the polarity.
- + - +
USER OPTIONS (continued)
HOMEOWNER SECTION
Monday through Friday
6:00 AM
8:00 AM
6:00 PM
10:00 PM
70
62
70
62
Time Heat Cool
Saturday and Sunday
6:00 AM
8:00 AM
6:00 PM
10:00 PM
70
62
70
62
75
75
83
83
75
75
78
78
Time Heat Cool
Morn
Morn
Even
Even
Day
Nite
Day
Nite
Time Heat Cool
01
Factory Set Schedule
Schedule
Default Settings
Record User Selection if Changed
from Default Setting
Record User Selection if Changed
from Default Setting
Display Range Default
Automatic Airflow Control (requires Installer Option 18
enabled or will not show up as a User Option
Nighttime Airflow Control
Set the Nighttime Airflow in Heating (will only show if
Nighttime Airflow Control is ON)
Set the Nighttime Airflow in Cooling (will only show if
Nighttime Airflow Control is ON)
Turning WiFi On/Off
Link Thermostat to Wireless network
Clean the Touch Screen (in seconds)
02
03
04
05
06
07
08
A Ac
n AF
nAF + Heat
nAF + Cool
nEt
Lnc
CL
On or Off
On or Off
%
%
On or Off
On or Off
N/A
On
On
130%
130%
Off
Off
30
N/A
N/A
NA
User Options (Homeowner)
Time
Heat
Cool
Turn Thermostat WiFi On
7
This option turns WiFi access On or Off.
Touch the MENU
key to display WiFi
On or Off option
indicated by NEt.
MENU ENTER
NEXT
Touch the UP key to
turn WiFi ON.
MENU ENTER
NEXT
Start Linking WiFi Thermostat
This option starts the linking of the EvenAir
thermostat to the home’s WiFi network.
COOL
SYSTEM
AUTO
FAN
Touch the MENU
key to display WiFi
linking option On
or Off indicated by
Lnc.
Touch the UP key to
select ON. Touch
the ENTER key to
start the linking
sequence.
linked, “WiFi” will be on continuously indicating a
connection.
6
8
ENTER
Living
Tu
Day
Sleeping
Living
Airflow %
Schedule
Cool
Set To
MENU MODE
AM
WiFi
ENTER
During the linking
sequence “WiFi” will
blink indicating the
thermostat is trying
to link to the home
network. Once the
thermostat has
page 6 of 16 P/N 780101703 3/18 Rev A
CAUTIONS
Use cautions when mounting components to surfaces
that may have concealed wiring beneath the surface.
!
INSTALLATION
Before installing the EvenAir comfort system, turn off
all power to your HVAC system.
Read and follow all instructions carefully.
Follow all local electrical codes during installation. All
wiring must conform to local and national electrical
codes.
i
ATTENTION INSTALLER
REMOVE SUBBASE
ATTACH SUBBASE TO WALL
Attach the subbase to an interior wall and about 5-feet above
the floor as shown using the screws and wall anchors supplied.
The wires to the dampers,
HVAC equipment and the
temperature sensor pass
through the opening
between the terminals.
Place a slotted screwdriver in the
slots as shown and rotate to
remove subbase from the
thermostat housing.
INSTALLER SECTION
This manual is separated into two different sections: one for the Homeowner and one for the System Installer.
The Installer section contains setup and installation information of the thermostat with optional user
settings available to the homeowner.
Read entire manual before installing EvenAir products.
When servicing EvenAir system or accessing products,
turn off all power to these items.
R
C
WOB
EQUIPMENT
Y
G
TS
COM
COM
CLS
CLS
OPN
OPN
Sleeping
Living
W2E/Y2
T21
TS
Nighttime Airflow Control is defaulted to ON. If
bedrooms are located downstairs, consider turning this
option Off using the User Options if bedrooms are not
on the same trunk.
Install and wire components to the thermostat.
(see Wiring section)
Airflow Control Off Option 17 turns off Airflow Control.
The thermostat controls the system, dampers fully open,
nighttime airflow control is disabled and airflow is no
longer displayed on the thermostat.
User Airflow Control can be enabled using Option 18.
User turns off automatic airflow control in the User
Options.
Place the thermostat on the subbase. Do not install
batteries.
Turn power to the HVAC equipment On.
Check for Error Messages. (see Error Message section)
Set equipment options 1-5 if different than factory
default settings. (see Installer Options section).
1)
3)
2)
4)
5)
Test the installation using the Installer Test Menu.
(see Installer Test Menu section on page 13)
6)
Install batteries and set the time and day (see Installing
Batteries and Set Time and Day section)
7)
page 7 of 16 P/N 780101703 3/18 Rev A
Install a damper with an AMT actuator in the duct supplying air
to the sleeping area and wire the terminals to the
corresponding terminals on the T21. Install a second damper
with an AMT actuator in the duct supplying air to the living area
and wire it to the T21. Each damper uses 2.4VA of power.
Green LED
Red LED
INSTALL DAMPERS
Ensure that damper installation does not cause obstruction
to the damper blade.
!
DAMPER WIRING
Warning!
!
Turn the power to the HVAC equipment off before wiring.
Use 3-conductor, 18 or 20 gage, thermostat cable to wire from
the T21 Thermostat to the sleeping and living area dampers.
There are separate terminals for the sleeping and living area
dampers.
Multiple dampers can be used to construct the sleeping or living
zones. Daisy chain terminals– COM to COM, OPN to OPN and
CLS to CLS.
Closes Damper
Opens Damper
Common
FunctionDamper
Terminal
COM
CLS
OPN
Wire Color
White
Red
Green
T21
Terminal
COM
CLS
OPN
i
Ensure the damper for the sleeping area is wired to the
terminals labeled SLEEPING and the damper for the living
area is wired to the terminals labeled LIVING.
When two or more dampers are required to define the sleeping
or living area, the damper may be wired in parallel. LEDs on
the damper actuator indicate when the damper is fully open
(green) or fully closed (red). When properly installed, the
dampers will never fully close.
Gas/Electric, 2H/1C
Gas/Electric, 1H/2C
Use 6-conductor, 18 or 20 gage, thermostat cable.
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
T21
Terminal
R
R
C
C
W/OB
W/OB
Y1
Y1
G
G
W2E/Y2
W2E/Y2
Wire Color
Wire Color
Red
Red
Blue
Blue
White
White
Yellow
Yellow
Green
Green
Brown
Brown
Equipment
Terminal
Equipment
Terminal
R, Rc, Rh
R, Rc, Rh
C
C
W, W1
W, W1
Y, Y1
Y, Y1
G
G
W2
Y2
Function
Function
24VAC Power
24VAC Power
Common
Common
Stg1 Heating
Stg1 Heating
Fan
Fan
Stg2 Heating
Stg2 Cooling
Cooling
Stg1 Cooling
Heat Pump, 1 Compressor
Heat Pump, 2-Compressor
Use 6-conductor, 18 or 20 gage, thermostat cable.
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
T21
Terminal
R
R
C
C
WOB
WOB
Y1
Y1
G
G
W2E/Y2
W2E/Y2
Wire Color
Wire Color
Red
Red
Blue
Blue
White
White
Yellow
Yellow
Green
Green
Brown
Brown
Equipment
Terminal
Equipment
Terminal
R, Rc, Rh
R, Rc, Rh
C
C
O or B
O or B
Y, Y1
Y, Y1
G
G
W, W2 or E
Y2
Function
Function
24VAC Power
24VAC Power
Common
Common
Rev Valve
Rev Valve
Fan
Fan
Aux Heat
Stg2 Compressor
Compressor
Stg1 Compressor
WIRING
Warning!
!
Turn the power to the HVAC equipment off before wiring.
INSTALLER SECTION
page 8 of 16 P/N 780101703 3/18 Rev A
R
COM
CLS
OPN
COM
CLS
OPN
C
W/OB
EQUIPMENT
SleepingLiving
Y1
G
W2E/Y2
TS
Model AMT
PN 580011401
Damper Actuator
Modulating
24VAC,2.4VA
COM
OPN
CLS
Made in USA
COM
OPN
CLS
G G
W2
Y2
GE HP
E
Y2
HVAC System
Sleeping Area
Damper
Model T21WF
Thermostat (in living area)
Model TS51 (one)
Temperature Sensor
for Sleeping Area
Living Area
Damper
Y Y
W
O or B
C C
R R
WIRING DIAGRAM
T21WF
TS
C NO O LT SR
F I E L D
Model AMT
PN 580011401
Damper Actuator
Modulating
24VAC,2.4VA
Made in USA
C NO O LT SR
F I E L D
TEMPERATURE SENSOR WIRING
Place wire between brass washer
and the printed circuit board and
hand tighten screw.
The TS5 sensor can be installed
in a single gang box or directly
to the wall using the hardware
provided.
HAND
TIGHTEN
Printed circuit board
Brass washer
Use 2-conductor, 18 or 20 gage, thermostat cable to wire from
the T21WF Thermostat to the temperature sensor in the sleeping
area.
Thermistor
Thermistor
FunctionSensor
Terminal
SNR
SNR
Wire Color
White
Red
T21WF
Terminal
TS
TS
i
Single Sensor Installation
Use one (1) Model TS51 sensor.
i
Dual Sensor Installation
Use two (2) Model TS52 sensors.
Model TS52 (two)
Temperature Sensors
for Sleeping Area
(temperatures are
averaged)
Warning!
!
Turn the power to the HVAC equipment off before wiring.
-OR-
INSTALLER SECTION
Reference Electrical Wiring DWG: 780301202
page 9 of 16 P/N 780101703 3/18 Rev A
Option
01
02
03
06
07
08
09
10
11
12
Description
Equipment Type
Reversing Valve
Compressor Stages
Compressor Minimum Off Time (minutes).
Gas Minimum Off Time (minutes).
Minimum Run Time (minutes).
On-Off Temperature Differential
Smart Recovery.
Vacant Heating Setpoint.
Vacant Cooling Setpoint.
o o
0 Cooling On 1 above setpoint, Off at setpoint. Heating On1 below setpoint, Off at setpoint.
o o o o
1 Cooling On 1 above setpoint, Off .5 below setpoint. Heating On1 below setpoint, Off .5 above setpoint.
o o o o
2 Cooling On 1 above setpoint, Off 1 below setpoint. Heating On1 below setpoint, Off 1 above setpoint.
Display
+ Heat
+ Cool
rEV
Cpr
Cot
HOt
o
O O
S r
V A C
V A C
Range
GE or HP
o or b
0 or 1 (GE),
0 to 2 (HP)
0 to 9
0 to 9
0, 1 or 2
0n(Up) or
Off(Down)
44 to 75
74 to 95
Default
Gas/Electric
O
1 (GE),
2 (HP)
2
0
1
Off
65
80
INSTALLER OPTIONS
r n t
0 to 9
2
13
Calibrate Living Area Sensor
C A L
+/- 5
0
05
Fan Operation.
Fan
GA(Down)
or EL(Up)
GA
(Only displayed if GE selected in Option 1)
04 Heating Stages Htg 0, 1 or 2 1
(Only displayed if HP selected in Option 1)
14
15
16
17
18
19
21
20
22
23
Night Level LCD Backlight
Airflow Control On or Off
Enable User Airflow Control
Up Stage Time
Maximum Airflow in Heating to the
Sleeping Area.
Maximum Airflow in Heating to the
Living Area.
Maximum Airflow in Cooling to the
Sleeping Area.
Maximum Airflow in Cooling to the
Living Area.
Maximum Temperature Difference
Between Sleeping and Living area.
BL
AFC
UAC
USt
HAF+Heat
HAF+Heat
CAF+Cool
CAF+Cool
diF
On(Up) or
Off(Down)
On(Up) or
Off(Down)
On(Up) or
Off(Down)
100 to 160%
5 to 30 minutes
100 to 160%
100 to 160%
100 to 160%
0 to 10F
On
On
Off
10
150%
150%
140%
140%
2F
+ Night
Airflow Update Time
A F t
1 to 20 minutes 2
Calibrate Sleeping Area Sensor.
C A L
+/- 5
0
Factory Restore
Fr
No(Next or Enter) or
Yes(UP Key then ENTER)
24
25
These set up features should only be accessed by a qualified installer during initial EvenAir thermostat
installation set up. The homeowner would not normally access these product set up features.
Record Installed
Selection if Changed
from Default Setting
INSTALLATION NOTES:
N/A
No
INSTALLER SECTION
page 10 of 16 P/N 780101703 3/18 Rev A
Use the UP key to
select ON to turn on
smart recovery or
the DOWN key to
select OF to turn
smart recovery off.
Smart recovery initiates a heating or cooling call
so that the space is at temperature when the
setback period ends.
Option
Use the UP/DOWN
keys to select the
heating temperature
when the space is
vacant.
Option
Use the
keys to select the
cooling temperature
when the space is
vacant.
UP/DOWN
Option
Cool
Vacant
Vacant
Heat
12 Vacant Cooling Setpoint
11 Vacant Heating Setpoint
o o
Range: 44 F to 75 F
o
Factory Default: 65 F.
10 Smart Recovery
Factory Default: Off. Range: On or Off.
Use the UP/DOWN
keys to change the
minimum off time
(minutes) before
restarting the
compressor.
Option
Option
Use the UP/DOWN
keys to change the
minimum off time
(minutes) before
restarting a gas
furnace or electric
strip heater.
06 Compressor Minimum Off Time
Factory Default: 2 Min. Range: 0 to 9 Min.
07 Heating Minimum Off Time
Factory Default: 0 Min. Range: 0 to 9 Min.
NEXT ENTER
NEXT ENTER
NEXT ENTER
NEXT ENTER
NEXT ENTER
o o
Range: 74 F to 95 F
o
Factory Default: 80 F.
Option
Use the UP key to
select “EL” for electric
operation where the
thermostat activates
the indoor fan (G
terminal) during
05 Setting the Fan Operation
Factory Default: Gas. Range: GA or EL
(Only displayed if Gas/Electric equipment,
GE, is selected in Option 01)
Touch NEXT or ENTER.
NEXT ENTER
heating calls or DOWN key to select GA for gas
operation where the equipment plenum sensor
activates the indoor fan in heating calls.
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Touch NEXT or ENTER.
ACCESSING INSTALLER OPTIONS
!
Press the touchscreen with your fingertip
only, using a firm touch. Do not use a sharp
object such as a pen or pencil.
!
The NEXT key is used to display the next
option.
!
The ENTER key is used to save options and
return to normal thermostat operation.
!
The hidden BACK key is used to return to
previous options and is located to the left of
the NEXT key.
To access the Installer Options, and
the hidden Enter key for 7 seconds until
the first Option appears on the screen.
TOUCH
HOLD
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU
Cool
Set To
SYSTEM
AM
TOUCH HOLD and this key
for 7 seconds to access the
Installer Options.
The hidden BACK
key can be used to
return to previous
options.
MODE
Use the UP/DOWN
keys to select
Option
01 Selecting the Equipment Type
This option is used
to select gas/electric
or heat pump
equipment.
Option
Use the UP/DOWN
keys to select o for
This option is used
to select an O or B
type reversing valve.
Factory Default: GE. Range: GE or HP
02 Reversing Valve
Factory Default: O. Range: o or b
(Only displayed if Heat Pump equipment,
HP is selected in Option 01)
NEXT
NEXT ENTER
gas/electric (GE) or heat pump (HP).
Touch NEXT or ENTER.
O-Type or b for B-Type.
Touch NEXT or ENTER.
Use the UP/DOWN
keys to set 0 or 1
stage.
Touch NEXT or
ENTER.
Option
03 Setting the Compressor Stages
This option is used to set the number of
compressor stages.
Factory Default: 1 . Range: 0 or 1
NEXT ENTER
Option
Use the UP/DOWN
keys to set 0, 1 or 2
stage.
Touch NEXT or
ENTER.
Factory Default: 1 Stage. Range: 0, 1 or 2
04 Setting the Heating Stages
NEXT ENTER
Use the UP/DOWN
keys to select 0, 1,
2.
Touch NEXT or
ENTER.
Option
Differential Mode0
Differential Mode1
Differential Mode2
o
1.0 On/Off Span.
o
1.5 On/Off Span.
o
2.0 On/Off Span.
09 Setting On-Off Temp Differential
Factory Default: #1. Range: 0, 1 or 2.
Option
Use the UP/DOWN
keys to change the
minimum run time
(minutes) before
turning a system off.
08 Minimum Run Time
Factory Default: 2 Min. Range: 0 to 9 Min.
NEXT ENTER
NEXT ENTER
Touch NEXT or ENTER.
INSTALLER SECTION
page 11 of 16 P/N 780101703 3/18 Rev A
ENTER
Use the
keys to select the
maximum allowable
airflow in heating to
the sleeping area.
UP/DOWN
Use the
keys to set the time at
which second stage
heating or cooling is
activated.
UP/DOWN
Sleeping
Airflow %
Option
Option
Heat
For options 20 - 23, use the installer test
o
imum allowable airflow.
n the following page to determine the
max
20 Maximum Airflow in Heating to Sleeping Area
19 Upstaging Time
Factory Default: 150%. Range: 100% to 160%.
Factory Default: 10 min. Range: 5 to 30 min.
NEXT ENTER
NEXT ENTER
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in cooling to
the sleeping area.
UP/DOWN
Sleeping
Airflow %
Option
Cool
21 Maximum Airflow in Cooling to the Sleeping Area
Factory Default: 140%. Range: 100% to 160%.
NEXT ENTER
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in heating to
the living area.
UP/DOWN
Living
Airflow %
Option
Heat
22 Maximum Airflow in Heating to the Living Area
Factory Default: 150%. Range: 100% to 160%.
NEXT ENTER
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
airflow in cooling to
the living area.
UP/DOWN
Living
Airflow %
Option
Cool
23 Maximum Airflow in Cooling to the Living Area
Factory Default: 140%. Range: 100% to 160%.
NEXT ENTER
Touch NEXT or ENTER.
Use the
keys to set the time
in minutes to update
the sleeping and
living area airflow.
UP/DOWN
Option
This is the frequency, in minutes, that the damper
position is updated.
15 Airflow Update Time
Factory Default: 2 Min. Range: 1 to 20 Min.
NEXT ENTER
Touch NEXT or ENTER.
Option
Night
Use the key to
turn the low level
UP
The LCD has a low
level backlight that
can be used as a
night light.
16 Night Level LCD Backlight
Factory Default: On. Range: On or Off.
NEXT ENTER
backlight ON or touch the key to turn
OFF.
DOWN
Use the key to
select ON for airflow
control or touch the
key to select
OFF to disable
airflow control.
UP
DOWN
Sleeping
Living
Airflow %
Option
This option turns the automatic airflow control on
or off. If off, the dampers fully open, nighttime
airflow options are disabled and airflow is no
longer displayed on the thermostat.
17 Airflow Control, On or Off
Factory Default: On. Range: On or Off.
NEXT ENTER
If Airflow Control was off and is now being turned on,
the Nighttime Airflow option can be turned on using the
User Options.
Touch NEXT or ENTER.
Use the key to
select ON to enable
the user to turn off
automatic airflow
control in the user
options.
UP
Homeowners with an unusual work schedule,
home office, etc. may want to use this option.
When turned On, this option enables the user to
turn off automatic airflow control in the User
Options. Airflow is adjusted by the homeowner.
Nighttime Airflow option is still enabled but can
be turned off using the User Options.
Option
18 Enable USER Airflow Control
Factory Default: Off. Range: On or Off.
NEXT ENTER
Touch NEXT or ENTER.
Use the UP/DOWN
keys to change the
Living area
temperature to the
temperature that the
user feels is correct.
Living
Option
13 Calibrate Living Area Temperature Sensor
Factory Default: None.
Use the UP/DOWN
keys to change the
Sleeping area
temperature to the
temperature that the
user feels is correct.
Sleeping
Option
14 Calibrate Sleeping Area Temperature Sensor
NEXT ENTER
o
Range - +/-5
NEXT ENTER
Factory Default: None.
o
Range - +/-5
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Touch NEXT or ENTER.
Use the
keys to select the
maximum allowable
temperature
difference between
the sleeping and
living area.
UP/DOWN
Option
This is the maximum allowable temperature
difference between the sleeping and living area
temperatures. When the temperature difference is
equal to or greater than the allowed differential,
the airflow is adjusted.
24 Maximum Temperature Differential
o
Factory Default: 2 F.
o o
Range: 0 to 10 F
25 Factory Restore
NEXT
To restore factory
settings, touch the
key to display
YES then touch
ENTER.
UP
Option
WARNING! Factory Restore resets ALL settings.
NEXT
Option
NEXT ENTER
ENTER
Touch NEXT or ENTER.
ENTER
To exit this option,
touch or NEXT
ENTER, or the hidden
Back key.
INSTALLER SECTION
page 12 of 16 P/N 780101703 3/18 Rev A
05-06 Testing Cooling Airflow Limits
In TEST 5, the system
is Off.
Touch to go to
TEST 6 to activate
cooling. Verify the
equipment is
operating.
To determine the
maximum allowable
airflow to the
sleeping area, touch
NEXT
This test is used to determine the maximum
allowable airflow to the Sleeping and Living
Areas in COOLING.
Maximum Allowable Airflow in Cooling
to the Sleeping Area
To determine the
maximum allowable
airflow to the Living
Area, touch the
key until the
airflow is too great
DOWN
Maximum Allowable Airflow in cooling
to the Living Area
Touch to end testing and return to normal
thermostat operation.
ENTER
Enter the maximum airflow limits using Options
20 through 23 of the installer menu.
The test can also be used to perform the HERS
Total Airflow test. The test activates a cooling call
and opens both dampers to 100%.
Airflow %
Cool
Airflow %
Cool
Test
Test
NEXT
NEXT ENTER
ENTER
Sleeping
Living
Sleeping
Living
Airflow %
Cool
Test
NEXT ENTER
Sleeping
Living
the key until the airflow is too great and
causes noise or annoyance. Lower the airflow
using the key until it is acceptable. This is
the maximum allowable airflow in cooling to the
sleeping area. Record the airflow value.
UP
DOWN
and causes noise or annoyance. Increase the
airflow using the key until it is acceptable. This
is the maximum allowable airflow in cooling to
the living area. Record the airflow value.
UP
01-02 Testing Indoor Fan Operation
In TEST 1, the Fan is
Off.
Touch to go to
TEST 2 to turn on the
indoor fan. Verify the
fan is operating and
delivering airflow to
the sleeping and
living area.
Touch to go to
Testing Heating
Airflow Limits.
NEXT
NEXT
This test is used to verify that the indoor fan is
operating correctly.
Sleeping
Living
Airflow %
Test
Airflow %
Test
NEXT
NEXT
Sleeping
Living
FANENTER
FANENTER
03-04 Testing Heating Airflow Limits
In TEST 3, the system
is Off.
Touch to go to
TEST 4 to activate
heating. Verify the
equipment is
operating.
To determine the
maximum allowable
airflow to the
Sleeping Area, touch
NEXT
This test is used to determine the maximum
allowable airflow to the sleeping area and the
living area in HEATING.
Maximum Allowable Airflow in Heating
to the Sleeping Area
Airflow %
Test
Airflow %
Test
Sleeping
Living
Sleeping
Living
NEXT
NEXT
ENTER
ENTER
Heat
Heat
the key until the airflow is too great and
causes noise or annoyance. Lower the airflow
using the key until it is acceptable. This is
the maximum allowable airflow in heating to the
sleeping area. Record the airflow value.
UP
DOWN
Sleeping
Living
Airflow %
Heat
Test
NEXT ENTER
To determine the
maximum allowable
airflow to the living
area, touch the
key until the
airflow is too great
DOWN
and causes noise or annoyance. Increase the
airflow using the key until it is acceptable. This
is the maximum allowable airflow in heating to
the living area. Record the airflow value.
UP
Maximum Allowable Airflow in Heating
to the Living Area
Touch to go to Testing Cooling Airflow
Limits.
NEXT
ACCESSING THE TEST MENU
To access the Test Menu, and the
hidden Next key for 7 seconds until the fan test
screen (TEST 01) appears.
TOUCH HOLD
The Test Menu is used to test the Indoor Fan
Operation, Allowable Heating Airflow Limits and
Allowable Cooling Airflow Limits.
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
TOUCH HOLD and this key for 7 seconds
to access the Installer Options.
The Test Menu can also be used to perform the
HERS Total Airflow test. TEST 05-06 activates a
cooling call and opens both dampers to 100%
enabling the installer to perform the test.
INSTALLER SECTION
page 13 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
Error Messages:
!
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
nP is displayed when there is
no power to the system. If the
message is displayed when
the system is powered, check
the wiring from the thermostat
to the system for errors.
No Power Message
When the equipment is
powered up, a blank LCD
indicates that there is no power
to the thermostat. Check the
wiring from the thermostat to
the equipment for errors.
Blank LCD
Living
Tu
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
AM
When the nS message is displayed, the thermostat will
continue to control the system and automatically opens
both dampers and disables airflow control until the
sensor error is corrected.
Sensor Error Message
nS is displayed when there
is an error with the
temperature sensor(s).
Check for open wires or
shortages.
ENTER
AM
Touch the UP/DOWN keys to
change the HOUR. Touch NEXT.
CHANGE THE HOUR
Touch the UP/DOWN keys to
change the MINUTE. Touch NEXT.
CHANGE THE MINUTE
Touch the UP/DOWN keys to
change the DAY OF THE WEEK.
Touch ENTER to save and return to
normal thermostat operation.
CHANGE THE DAY OF THE WEEK
We
AM
ENTER
AM
NEXT
NEXT
ENTER
Set Time and Day
Living
Day
Sleeping
Living
Airflow %
COOL
Schedule
AUTO
FANMENU MODE
Cool
Set To
SYSTEM
Touch here to change the time
and day of the week.
Tu
AM
Press the touchscreen with your fingertip only,
using a firm touch. Do not use a sharp object
such as a pen or pencil. The touchscreen is a
resistive touch and responds differently than
touchscreens found in smart phones/devices.
!
INSTALL BATTERIES
The batteries power the clock
when 24VAC power is lost. Slide
the battery cover downward and
install the two AA batteries as
shown.
Install batteries only after successfully testing
the installation using the Installer Test Menu.
!
page 14 of 16 P/N 780101703 3/18 Rev A
MAINTENANCE AND TROUBLESHOOTING
SPARE PARTS AND ACCESSORY LIST
Field Controls
Part Number
Model
Number
Description
580011101
580011102
580011301
580011302
580011401
580011405
580011406
T21
T21WF
TS51
TS52
AMT
IS
DS
MD-#
MD-LxH
Programmable wired thermostat w/ airflow control for GE equipment with 1H/1C, 2H/1C or 1H/2C,
or HP equipment with 2H/2C
Programmable wired thermostat w/ airflow control for GE equipment with 1H/1C, 2H/1C or 1H/2C,
or HP equipment with 2H/2C. WiFi Enabled
Wired temperature sensor for the sleep area. Single sensor installation.
Wired temperature sensor for the sleep area. Dual sensor installation.
Replacement modulating actuator control, 3 wire.
Replacement idler shaft for AMT and AMJ actuators.
Replacement drive shaft for AMT and AMJ actuators.
EvenAir Round Balance Damper, 3 Wire. Sizes - 4” - 20” diameter.
EvenAir Rectangular Balance Damper, 3 Wire. Sizes - 8”, 10” and 12” Heights, up to 24” Length.
DAMPER OPERATION
Problem - No airflow to the sleeping area AND living
area registers
Turn system off immediately. Both dampers may be wired
backwards at the subbase or at the damper actuator (closing
rather than opening).
Problem - No airflow to the sleeping area OR living
area registers
Turn system off. One of the dampers may be wired backwards
at the subbase or at the damper actuator (closing rather
than opening).
Problem - When directing airflow to the sleeping area, the
airflow is actually directed to the living area, and when
directing the airflow to the living area, the airflow is actually
directed to the sleeping area.
Turn system off. Check if the dampers are switched (sleeping
area damper is wired to the living area terminals and the
living area damper is wired to the sleeping area terminals.)
SENSOR INSTALLATION
Problem - nS message on thermostat.
Check that the sensor is wired correctly. Check for a short in
the sensor wiring.
Problem - Sleeping area temperature reading very high or
very low.
Check that the correct sensor(s) have been used. One TS51
sensor is used in a single sensor installation. Two TS52
sensors are used in a dual sensor installation.
COMFORT CONCERNS
Problem - Downstairs bedroom is too cold or too hot at night.
The Nighttime Airflow Control option directs more airflow to the
sleeping area and less airflow to the unoccupied living area. If
the downstairs bedroom is on the same HVAC trunk as the
living area, the downstairs bedroom may become uncomfortable
at night. Turn off the Nighttime Airflow Control option using the
User Options.
Problem - The room temperature on the thermostat seems
too high or too low.
The thermostat is factory calibrated within 1 degree.
However, if a homeowner finds the temperature “feels
too high or too low, the thermostat can be calibrated to
what the homeowner feels is the correct temperature using
Installer option 13 for the living area and option 14 for
the sleeping area.
page 15 of 16 P/N 780101703 3/18 Rev A
This manual may be downloaded and printed from the Field Controls website (www.fieldcontrols.com)
WARRANTY
For warranty information about this or any Field Controls product, visit:
www.fieldcontrols.com
Field Controls Technical Support
1.800.742.8368
fieldtec@fieldcontrols.com
Phone: 252.522.3031 Fax: 252.522.0214
www.fieldcontrols.com
Field Controls, LLC
c
Field Controls Customer Service
1.252.522.3031
sales@fieldcontrols.com
9154 Stellar Ct
Corona, CA 92883
2630 Airport Road
Kinston, NC 28504
P/N 780101703 3/18 Rev A
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

FIELD CONTROLS EvenAir T21WF User manual

Category
Thermostats
Type
User manual
This manual is also suitable for

FIELD CONTROLS EvenAir T21WF is a remarkable thermostat with airflow control that allows you to manage the heating, cooling, and airflow in your home, ensuring a uniformly comfortable environment. It comes with a temperature sensor to monitor the temperature in the sleeping area, and two modulating dampers to control the airflow to the living and sleeping areas. The EvenAir T21WF thermostat automatically adjusts the airflow to the space that needs it, providing a comfortable temperature throughout your home.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI