Rockwell Automation Publication 1606-RM052A-EN-P - August 2018 5
Power Supply Reference Manual - 24V, 40 A Single-phase Input
Output
Attribute Value
Output nom 24V DC
Adjustment range min 24-28V DC guaranteed
max 29V DC
(1)
(1) BonusPower®, short-term power capability (up to typ 4 s) The power supply is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-term duration is hardware that is
controlled by an output power manager. This BonusPower® is repeatedly available. If the power supply is loaded longer with the BonusPower® than shown in the Bonus-time diagram (See Figure 8 on page 6
), the max output
power is automatically reduced to 960 W. If the power requirement is continuously above 960 W and the voltage falls below approx. 20V (due to the current regulating mode at overload), the unit shuts-off and makes periodical
restart attempts. This behavior is called hiccup mode that is described below. If the voltage is above 20V, the unit continuously delivers current.
at clockwise end position of potentiometer
Factory setting typ 24.1V DC ±0.2%, at full load, cold unit, in “single use” mode
typ 24.1V DC ±0.5%, at full load, cold unit, in “parallel use” mode
typ 25.1V DC at no load, cold unit, in “parallel use” mode
Line regulation max 10 mV 85…300V AC
Load regulation max 50 mV in “single use” mode: static value, 0 A..40 A, see Figure 6 on page 6
typ 1000 mV in “parallel use” mode: static value, 0 A..40 A, see Figure 10 on page 7
Ripple and noise voltage max 100mVpp 20 Hz to 20 MHz, 50 Ohms
Output current nom 40 A continuously available at 24V, see Figure 6 and Figure 10 on page 7
nom 34.3 A continuously available at 28V, see Figure 6 and Figure 10 on page 7
nom 60 A short-term available BonusPower®, at 24V for typical 4 s, see Figure 6 and Figure 10 on
page 7
nom 51.5 A short-term available BonusPower®, at 28V for typical 4 s, see Figure 6 and Figure 10 on
page 7
typ 110 A up to 10 ms, output voltage stays above 20V, see Figure 8 on page 6, This peak current is
available once every second. See Peak Current Capability
on page 21 for more peak
current measurements.
Output power nom 960 W continuously available at 24-28V
nom 1440 W
(2)
(2) HiccupPLUS Mode Up to 4 s of overloading, the power supply delivers continuous output current. After this, the output power is reduced to nearly zero for approx. 17 s before a new start attempt is automatically performed. If the
overload has been cleared, the device will operate normally. If the overload still exists, the output current will be delivered for 2s to 4s (depending on the overload) again followed by a 17 s rest time. This cycle is repeated as long
as the overload exists. See Figure 7 on page 6
. During the off-period, a small rest voltage and rest current is present on the output.
short-term available BonusPower® at 24…28V
BonusPower® time typ 4 s duration until the output voltage dips, see Figure 8 on page 6
BonusPower® recovery time typ 7 s overload free time to reset power manager, see Figure 12 on page 7
Overload behavior cont. current output voltage > 20V DC, see Figure 6 on page 6
HiccupPLUS mode
(3)
(3) Discharge current of output capacitors is not included
output voltage < 20V DC, see Figure 6 on page 6
Short-circuit current min 60 A
(4)
(4) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed value that can be achieved. The typical value is about 28.5V.
load impedance 25mOhm, see Figure 7 on page 6
max 70 A load impedance 25mOhm, see Figure 7 on page 6
max 23 A average (R.M.S.) current, load impedance 25mOhm, see Figure 7 on page 6
typ 130 A up to 10 ms, load impedance <10mOhm, see Figure 11 on page 7
Output capacitance typ 10 200 μF included in the power supply