FläktGroup DC_10525GB 20201118_R0 Specifications are subject to alteration without notice
SETTING THE RESPONSE TIME
The response time affects how fast the transmitter reacts to changes
in the pressure conditions in the system. The response time defines
the time the measuring instrument needs in order to reach 63 % of
the measured value. For unstable pressure conditions, select a longer
response time.
Example:
Selected response time: 4.0 seconds
Result: The output signal reaches a new value in 20 seconds
(response time * 5)
In order to change the response time, install or remove a jumper in
slot J4.
- Jumper in slot J4 - 4.0 seconds response time.
- No jumper in slot J4 = 0.8 seconds response time
ZERO POINT SETTING
Connect the voltage supply one hour before the zero point setting!
1. Remove both hoses from the pressure connections ⊕ and ⊖.
2. Press the zero button until the red LED switches on.
3. Wait until the LED switches off again and install the hoses to the
pressure connections again.
4. In normal operation, we recommend that a zero point calibration is
carried out every 12 months.
MAINTENANCE
This product is maintenance free except for zero point calibration that
must be carried out before first use and then once a year.
Repairs must only be carried out by the manufacturer or appropriately
qualified skilled personnel.
DISPOSAL
Decommissioned devices and left over parts should be
taken to a recycling site that specializes in electronic
waste. Always take local legislations into consideration.
SPECIFICATIONS
DIMENSIONAL DRAWINGS (MM)
Accuracy ±2 Pa ± 1.5 %
Media compatibility Dry air or non-aggressive gases
Overpressure Maximum operating pressure 20 kPa
Measuring element Piezo measuring cell
Power supply Output signal 0 ... 10 V: DC 14 ... 30 V or AC
24 V ±10 %
Output signal 4 ... 20 mA: DC 9 ... 30 V or AC
24 V ±10 %
Electrical connection Cable gland M16
Screw terminals max. 1.5 mm2
Output signal DC 0 … 10 V, 3-wire, 4 … 20 mA, 3-wire
Current consumption < 1.0 W (0 … 10 V), < 1.2 W (4 … 20 mA)
Process connection Connecting nozzle (ABS), lower mount, for
hoses with inner diameter 4 or 6 mm
Case Plastic (ABS)
Permissible temperatures
- Ambient temperature
- Storage temperature
- Medium temperature
-20 … +70 °C
-50 … +70 °C
-10 … +50 °C
Ingress protection IP54
Weight 150 g
CONFORMANCE
Meets requirements for
CE marking
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
WEEE Directive 2012/19/EU
67.3
85.3
20
52
70
∅4.5
∅7.5
19
23
151012