Frick IDSC2 Evaporative Condenser Installation Operation and Maintenance Guide

Type
Installation Operation and Maintenance Guide
This manual contains rigging, assembly, start-up, and maintenance
instructions. Read thoroughly before beginning installation. Failure
to follow these instructions may result in personal injury or death,
damage to the unit, or improper operation.
Check www.FrickCold.com for the latest version of this publication.
IDSC2
Stainless Steel Evaporative Condenser
Form 140.020-IOM (OCT 2020)
INSTALLATION - OPERATION - MAINTENANCE
File: SERVICE MANUAL - Section 140
Replaces: NOTHING
Dist: 3, 3a, 3b, 3c
140.020-IOM (OCT 2020)
Page 2
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
Contents
General information
Safety instructions ............................................................3
Warranty statement ..........................................................3
Terminology ...................................................................... 4
Installation
Location layout ..................................................................7
Equipment layout ..............................................................7
Single/multiple unit layouts ..........................................8
Support Structure .......................................................10
Receiving and inspection................................................. 11
Rigging and hardware .....................................................11
Basin section .............................................................. 12
Upper casing section .................................................. 15
Ofoading and assembly ................................................. 18
Installing the basin......................................................18
Fitting the upper casing section .................................18
Connection joint ......................................................... 19
Installing the riser pipe coupling .................................19
Inlet louvers ................................................................ 19
Installing inlet louvers ................................................. 20
Removing inlet louvers ............................................... 20
Piping .............................................................................. 21
Storage ...........................................................................21
Electrical .........................................................................21
Field wiring ................................................................21
Electrical data .............................................................22
Water distribution pump ......................................... 22
Basin heaters ..........................................................22
Electronic water level controller ............................. 22
Electrical enclosures ...............................................22
Fan motors .............................................................22
EC motors ...............................................................22
Operation
Pre-start up inspection ...................................................25
General .......................................................................25
Cleaning .....................................................................25
Start-up ......................................................................25
Cold weather operation................................................... 26
Extended shutdown .........................................................27
Capacity control ..............................................................27
Normal operation .......................................................27
Cold weather operation ..............................................27
Maintenance
Maintenance requirements .............................................. 30
Removing the inlet louver ..........................................30
Removing the drift eliminators ...................................30
Cold water basin ........................................................31
Cleaning .................................................................31
General maintenance .............................................31
Electronic water level controller ............................ 31
Stainless steel casing and panels ...............................31
Water distribution system .......................................... 32
Maintaining water distribution system ...................32
Water distribution pump ............................................. 32
EC motors...................................................................32
Water quality and water treatment guidelines ................32
Bleed or blow down rate ........................................... 32
Water treatment guidelines ........................................33
Indicates an imminently hazardous situation which, if not avoided, will result in death or seri-
ous injury.
Indicates a potentially hazardous situation or practice which, if not avoided, will result in death
or serious injury.
SAFETY PRECAUTION DEFINITIONS
Indicates a potentially hazardous situation or practice which, if not avoided, will result in damage
to equipment and/or minor injury.
Indicates an operating procedure, practice, etc., or portion thereof which is essential to highlight.
WARNING
CAUTION
DANGER
NOTICE
140.020-IOM (OCT 2020)
Page 3
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
General information IDSC2 units are designed to provide optimum efciency
and an extended life when properly installed, operated
and maintained. As a result, it is highly recommended that
a comprehensive maintenance schedule be developed
and undertaken on a regular pre-determined basis. This
manual assists the owner – operator in developing such a
schedule.
This equipment is relatively complicated and the instal-
lation, operation, maintenance, and servicing must only
be carried out by suitable individuals who are qualied to
carry out these functions. These individuals must also be
familiar with and comply with all applicable governmental
standards and regulations pertaining to the function(s).
NOTICE
The type of refrigerant must comply with what is
indicated on the submittal drawings and/or unit’s
nameplate. Design operating pressures, as indicated
on the nameplate, must never be exceeded.
NOTICE
Evaporative condensers and uid coolers and all
piping systems must be correctly evacuated before
charging the system with refrigerant, to ensure the
complete removal of moisture and non – condens-
ables from the entire refrigerant circuit.
NOTICE
For evaporative condenser and uid coolers instal-
lations that are installed at or near coastal areas,
speak to your Frick representative to conrm the
material combination compatibility.
NOTICE
In locations where the uid within the evaporative
uid cooler could possibly freeze due to ambient
temperatures dropping below freezing, drain the uid
from the coil when the ambient temperature is at or
below 40˚F.
WARNING
Failure to comply with any of these requirements could
result in serious damage to the equipment and/or
the property where it is installed, as well as personal
injury and/or death to themselves and/or people at the
specic location.
Warranty statement
Frick warrants the product to be free from defects in
workmanship and materials under normal usage for a peri-
od of 24 months from the date of purchase (the “Warranty
Period”), provided that the product is correctly installed
and operated within the recommended limits of Frick’s
technical documentation. This warranty is only valid if the
product is given normal and proper use and complies with
Frick‘s installation and maintenance instructions.
Safety instructions
Only qualied personnel who are familiar with this type
of equipment must carry out installation and mainte-
nance.
Always wear safety glasses, gloves, and head protec-
tion when working on the equipment.
Avoid contact with sharp edges as these can cause
painful lacerations.
All units must be properly evacuated before charging
the system.
Before undertaking any work, verify that the power is
switched off and that the unit is properly disconnected,
locked out, and tagged out.
Never apply heat to a sealed refrigeration system.
Keep hands away from fans when the unit is running.
Ensure all mounting bolts are tight and are the correct
length for the specic application.
Do not remove any of the safety labels from the unit.
Maintain all safety labels on the unit in good condition.
If required replace with new.
WARNING
Although halocarbon refrigerants are classied as safe
refrigerants, certain precautions must be observed
when handling them. Refrigerants can be harmful if
inhaled. When released to the atmosphere in the liquid
state, refrigerants evaporate rapidly, freezing anything
they contact. Use and recover refrigerants responsibly.
Failure to follow this warning may result in personal
injury or death.
DANGER
Anhydrous Ammonia (NH3):
Specic precaution must be adhered to when people
are working with or are exposed to Anhydrous Am-
monia.
Ammonia is considered a high health hazard because
it is corrosive to the skin, eyes, and lungs. Exposure to
300 parts per million (ppm) is life threatening. Am-
monia is also ammable at concentrations of approxi-
mately 15% to 28% by volume in air. When mixed with
lubricating oils, its ammable concentration range is
increased. It can explode if released in an enclosed
space with a source of ignition present, or if a vessel
containing anhydrous ammonia is exposed to re.
Personal protective equipment must be worn at all
times when working with Ammonia. For systems that
have an operating charge greater than 10,000 lb a pro-
cess safety management program is mandatory. More
information on this topic is available from OSHA.
Failure to follow this warning may result in personal
injury or death
.
140.020-IOM (OCT 2020)
Page 4
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
Frick assumes no responsibility for repairs to a product
sustaining damages resulting from user modications, at-
tachments to the product, misuse, alteration or negligent
use.
Frick, at its option, shall repair or replace, free of charge
to the buyer, all components of the product which are, or
become, defective during the Warranty Period because
of defects in design, workmanship or materials, ordinary
wear and tear excluded, provided however, that:
The product is applied correctly.
All operating and installation instructions for the prod-
uct are complied with.
System component and piping design is in accordance
with state-of–the-art HVAC practice.
Nitrogen or an inert gas is introduced into the piping
during the brazing of the piping installation.
In all instances, industry standard refrigeration practices
must be observed and followed by certied refrigeration
technicians, mechanics, pipe tters, design engineers, and
any other personnel involved in installing and servicing
FRICK products. This warranty shall not include ordinary
maintenance or cleaning of the product, defects in the
installation of the product or defects in turning and moving
parts. This warranty also does not cover physical damage
to the product, during transit or otherwise, after purchase
of the product but before installation.
The buyer must request repair or replacement of the
defective component through a written notice delivered
to Frick no later than two business days after the buyer
becomes aware of the defect. The buyer must provide
Frick with the time and opportunity to make repairs or re-
placement. Otherwise, Frick will be released from liability
for the defect. Under no circumstances will Frick make
any repair or replacement without Frick’s prior written
consent, except to the limited extent permitted by Frick’s
Service Policy.
Any transport and exchange costs for the repair or re-
placement shall be borne by the buyer. Frick shall also
not be liable for costs incurred in dismantling or tting
replacement parts or for any independent inspection un-
dertaken by the buyer. The buyer shall return any allegedly
defective goods, postage or freight paid, to Frick at the
address below. Upon receipt of the goods and inspection
thereof, Frick shall repair or replace, at Frick’s discretion,
the defective components and shall return the same to the
buyer, return postage and freight paid. This shall constitute
full compliance with Frick’s warranty obligations here-
under. Frick accepts no liability for the direct or indirect
consequences of any modications of or repairs to the
product made by the buyer or by a third party without the
prior consent of Frick. Frick reserves the right to inspect
the product for customer abuse during the warranty pe-
riod if abnormal claims against the equipment arise.
This warranty shall not apply to Frick products which have
been improperly installed or repaired, or altered in any
way outside of the manufacturer’s factory or have been
subject to misuse, negligence, or accident. Equipment or
component parts such as valves, electric motors, electric
heaters, and electric accessories manufactured by others
and used as part of or in connection with Frick products,
carry only the warranty of the manufacturer thereof. This
warranty shall be void if equipment has been subjected to
negligence, abuse, misuse, low voltage, corrosive chemi-
cals, excessive pressure, accident, outward damage, or
hidden damage while in transit, or if operated contrary to
the manufacturer’s recommendations.
This warranty applies only to the repair or replacement of
the product and/or its components and expressly excludes
responsibility for damages not occurring to the product
and/or its components themselves and for consequential
damages. This warranty is the buyer‘s exclusive remedy,
and any implied warranty of merchantability or tness is
excluded. FRICK shall not be liable to the buyer or to any
customer of the buyer under any circumstances for any
direct or indirect damages, injury to persons or property
or any consequential or incidental damages or loss of
prots, including, without limitation, loss of refrigerant,
loss of stored goods, lost sales, orders, prots or income,
either gross or net, arising, directly or indirectly, from
defective goods or workmanship or from any other cause
whatsoever.
NOTICE
Failure to comply with the water guidelines laid out
in the water quality and treatment section of this
manual voids all related warranty consideration.
Terminology
The following descriptions are provided to ensure all per-
sons working with the IDSC2 equipment are familiar with
the terminologies used.
Basin: An assembly located at the base of the unit de-
signed to hold a volume of recirculated water while pro-
viding connections for the water recirculation pump, drain,
and overow. It is also known as a pan or sump.
Water recirculation pump: Closed-coupled, centrifugal
type impeller, with mechanical seal required to circulate a
specied ow rate of water over the heat exchange coil(s).
Basin section (induced draft unit): An assembly com-
prised of the basin, support columns, air inlet louvers,
make-up water connection, and other small parts required
for proper unit operation in the eld. The basin section is
usually shipped separate from the rest of the unit.
Basin section (forced draft unit): An assembly comprised
of the basin, support columns, axial motors/fans, enclosure
panels, make-up water connection, and other small parts
required for proper unit operation in the eld. The basin
section is usually shipped separate from the rest of the
evaporative unit.
Inlet louvers: Enables ambient air to enter the unit at the
basin section, while preventing water from splashing out
and direct line of sight into the basin during unit operation.
There are many different proles, sizes, and materials of
construction.
Sump/strainer connection: Appropriately sized cross-sec-
tional area, box or pipe, that is greater than or equal to the
suction connection size of the water recirculation pump.
140.020-IOM (OCT 2020)
Page 5
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
Strainer: An assembly used to catch large suspended par-
ticles in the recirculating water before entering the water
recirculation pump. Periodic maintenance is required to
keep the strainer clean.
Drain connection: Appropriate sized pipe, usually MPT,
extending from the lowest point of the basin to facilitate
basin drainage.
Overow connection: Appropriate sized pipe, usually
MPT, extending from the highest point of the basin, con-
nection end to prevent spill out from the air inlet louver
section and bleed off.
Casing: Perimeter panels of the fan and/or coil section of
the unit which house all interior components.
Coil section: An assembly comprised of the heat exchange
coil(s), tube sheets (IDSC2 only), casing, and any other
structural members required.
Condensing coil: An assembly comprised of tubes, head-
ers, connections, and framing, in a specic serpentine
arrangement such that circulating refrigerant is condensed
when operating with other unit components. It is also
known as the heat transfer coil.
Axial fan section: An assembly comprised of the fan(s),
fan motor(s), fan nozzle(s), fan motor mount(s), framing,
casing, drift eliminators, and water distribution system.
Fan motor mount: An assembly comprised of heavy
gauge sheet metal, or structure, to rigidly support a single
motor and fan coupled together.
Drift eliminators: Located above the water distribution
system to remove entrained water droplets in the leaving
air stream.
Water distribution system: An assembly comprised of
a water distribution box (or header), water distribution
branches (or pipes), water spray nozzles and other minor
parts to fasten, seal, and secure all parts in place.
Riser pipe: Water pipe which connects the discharge side
of the water recirculation pump to the water distribution
box (header) entrance.
Bleed valve: Located on the lower portion of the riser pipe
where the discharge side of the valve connects to the top
of the overow drain connection (basin). It is necessary to
set the appropriate amount of water “bleed” from the unit
to maintain the appropriate cycles of concentration. Also
known as a blowdown valve.
Lifting lug: Heavy gauge or multiple heavy gauge plates,
joined together, with a large hole to accommodate the
attachment of an industrial lifting connection, for example,
screw pin shackle. Also called a lifting ear.
Mechanical oat make-up assembly: Make-up water
valve with armature and circular or pancake type oat for
basin water level adjustment.
Make-up water connection: Appropriate sized pipe,
usually MPT, extending from the vertical louver support
at the connection end. This connects to the mechanical
oat make-up assembly located inside the basin section to
facilitate make-up water feed.
The following are possible accessories available for IDSC2
units.
External service walkway package: OSHA approved, self
–supporting, external walkway assembly, which includes a
vertical access ladder, connected to the unit. This enables
access to the unit fan section, eliminators, and water
nozzles.
Remote sump: A separate basin, or water tank, located
inside a structure that must be kept above freezing tem-
peratures. It is used to hold/circulate the water used by
the unit instead of the standard basin with pump supplied.
A remote sump connection in the unit basin is provided for
this option.
Electric heaters: Electric immersion heaters to ensure
the basin water does not freeze. Basin water temperature
maintained is approximately +40°F.
Electronic water level control: External stand pipe with
level sensor elements to control a separate solenoid valve
to provide make-up water to the basin.
Motor davit: An assembly connected to the unit used to
facilitate lifting the fan and/or motor from the fan motor
mount.
Water silencers: Located in the basin above the operating
water level. This option reduces the overall noise level of
the unit.
140.020-IOM (OCT 2020)
Page 6
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION - OPERATION - MAINTENANCE
This page intentionally left blank
140.020-IOM (OCT 2020)
Page 7
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Installation Ensure that there is sufcient space for maintenance.
Ensure that all liquid-carrying components, connec-
tions, lines, and all electrical connections and lines are
easy to access.
Ensure that the pipe connection points are visible.
NOTICE
Lightning protection rods beside the unit are recom-
mended.
If you intend to put the units into a dual or quad position,
increase the height of the louver section in the single box
sizes to ensure sufcient air intake. See Figure 1 to Figure
4 and Table 1.
WARNING
Refer to the submittal package for specic unit infor-
mation.
Equipment layout
Location layout
Ensuring optimum performance of the unit with unobstruct-
ed airow is the responsibility of the installing contractor. In
order not to compromise the performance of the unit, loca-
tions on open rooftops or at ground level with no obstruc-
tions such as walls or adjacent buildings are optimal.
When optimal locations are not possible, position units so
that the discharge air is either level or higher than these
adjacent obstacles. It is imperative that the location allows
for unrestricted airow into each unit and that there is no
recirculation of the saturated discharge air. It is also advis-
able that the discharge air is not in the direction of, or in
close proximity to, any air intake location for the building’s
ventilation system.
Other points to consider when selecting the installation
location include the following:
Place the unit so you can monitor and control it from
all sides at all times.
H
L
H
L
Figure 1: Single unit
Figure 2: Dual unit, end to end
Figure 3: Dual units, side by side Figure 4: Quad units
H
L
H
L
140.020-IOM (OCT 2020)
Page 8
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
The IDSC2 is an induced-draft, counter-ow, evaporative-
cooled product line consisting of a four-sided air entry
conguration. Properly evaluating equipment location
leads to a successful installation, and subsequently, proper
operation. This manual provides suggestions for vari-
ous layout scenarios including placing equipment in close
proximity to an obstruction, such as a wall. In addition,
Frick offers both dual and quad unit congurations which
increase the air inlet openings appropriately, in com-
parison to a single unit, to enable the absolute minimum
clearance between units. See Figure 5 to Figure 10 for
details.
The list of minimum clearances between an obstruction
and the air inlet side or end is a guideline only. There
are always circumstances, for example prevailing winds,
coupled with eld experience, which lead to alternate lay-
outs that would increase a minimum clearance presented
in this manual to achieve proper operation.
It is best practice to place the equipment in a free-eld
environment when possible, to ensure the required ambi-
ent airow and prevent recirculation of the saturated
discharge air. Units on open rooftops or at ground level
with no obstructions, such as walls or adjacent buildings,
are the optimum location. However, in many instances this
is not possible. Positioning in wells, next to high walls,
adjacent buildings, occupied areas, or specic enclosures
all pose a risk of recirculating the saturated discharge air.
This increases the wet bulb temperature of the intake
air and compromises the performance of the condenser,
which can result in higher condensing temperatures. Use
discharge hoods or duct extensions in such instances.
Single/multiple unit layouts
All minimum clearance values indicated are for IDSC2
induced draft units only. In addition, overall nominal unit
lengths are also indicated. A unit is a specic model num-
ber which consists of a single nominal box size or multiple,
single boxes arranged in very close proximity. See Table
1 for model dimensions. There are three different unit
congurations available: single, dual, and quad. A dual
unit, for example, can be two, 12 ft x 12 ft single boxes
positioned end-to-end which is designated as one model
number and is considered one unit. Figure 5 to Figure 10
highlight different potential layouts in which you can prop-
erly locate a unit or units on-site.
Figure 5: No obstruction/two units
Table 2: No obstruction/two units
Unit conguration Unit
length (ft)
C3 and C4
(ft)
Single 9 3
Single 12 6.5
Single 18 6.5
Dual (end-to-end) All 8.5
Dual (side-to-side) All 13
Quad All 13
Table 1: IDSC2 congurations and air inlet and basin heights (in.)
Unit
size
(ft)
Single unit Dual end-to-end Dual side-by-side Quad unit
Inlet louver
height (L)
Basin
height (H)
Inlet louver
height (L)
Basin height
(H)
Inlet louver
height (L)
Basin
height (H)
Inlet louver
height (L)
Basin
height (H)
8.5 x 12
30 57.5 — — —
10 x 12
36 63.5 48 75.5 — — —
12 x 12
36 63.5 48 75.5 78
105.5
78
105.5
10 x 18
48 75.5 48 75.5 — — —
12 x 18
48 75.5 78 105.5 78
105.5
78
105.5
Note: Consult factory for additional information. This is for reference only; use certied drawings for design purposes.
C4
C3
140.020-IOM (OCT 2020)
Page 9
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 8: Two walls/two units
Table 5: One wall/two units (ft)
Unit conguration Unit
length
C1
and C2
C3
and C4
Single 9 3 6
Single 12 3.5 7
Single 18 4.5 9
Dual (end-to-end) All 4.5 9
Dual (side-to-side) All 7 14
Quad All 7 14
Figure 9: Two walls (corner)/single and multiple units
Table 6: Two walls (corner)/single and multiple units
(ft)
Unit conguration Unit
length
C5, C6,
C7, and
C2
C3
and C4
Single 9 3 6
Single 12 3.5 7
Single 18 4.5 9
Dual (end-to-end) All 4.5 9
Dual (side-to-side) All 7 14
Quad All 7 14
Figure 6: One wall/one unit
Table 3: One wall/one unit (ft)
Unit conguration Unit
length
C1 and C2
Single 9 3
Single 12 3.5
Single 18 4.5
Dual (end-to-end) All 4.5
Dual (side-to-side) All 7
Quad All 7
Figure 7: Two walls/one unit
Table 4: Two walls/one unit (ft)
Unit conguration Unit
length
C1 and C2
Single 9 3
Single 12 3.5
Single 18 4.5
Dual (end-to-end) All 4.5
Dual (side-to-side) All 7
Quad All 7
C2
C1
C2
C2
C1 C1
C2
C2 C2
C2
C2
C6
C5
C4
C8 C8
C7
C7
C4
C3
C3
C4 C4
C3
C2
C1 C1
C1
C1 C1
C1
140.020-IOM (OCT 2020)
Page 10
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 10: Three walls/single and multiple units
Table 7: Three walls/single and multiple units (ft)
Unit conguration Unit
length
C7
and C7
C3
and C4
Single 9 3 6
Single 12 3.5 7
Single 18 4.5 9
Dual (end-to-end) All 4.5 9
Dual (side-to-side) All 7 14
Quad All 7 14
Support structure
Use two parallel I-beams traversing the entire length of the
unit to structurally support the units. See Figure 11.
Figure 11: IDSC2 steel support dimensions
B2
B1
B4
B3
A1 A2 A3 A4
NOTICE
Refer to the submittal package for specic unit infor-
mation.
Use Neoprene gasketing between the I-beams and the
base of the unit.
NOTICE
If Neoprene gasketing is not used, corrosion may oc-
cur between the dissimilar materials.
I-beams must be level, with no deviance greater than 1/8
in. over a 6 ft span. Do not use shims to level the unit as
this compromises the load bearing surface.
Use the mounting holes of 13/16 in. diameter at the base
of the basin section, in the side panel anges, for securing
each unit to the support structure using 3/4 in. diameter
bolts. Refer to the Frick unit certied drawing for the bolt
hole locations.
The installing contractor, the building contractor, or some
other relevant party must provide all support beams and
anchoring bolts, which you must select in accordance with
sound structural engineering standards. When select-
ing the support beams, calculate deection by using 55%
of the unit’s operating weight as a uniform load on each
beam.
NOTICE
The support beams must be level at the top and meet
industry acceptable tolerance related to the overall
length of the unit installed. Do not level any unit with
shims.
Table 8: IDSC2 steel support dimensions, single cell
arrangements
Model A1 B1
IDSC2 0812... 8 ft, 5 1/2 in. 11 ft, 11 3/4 in.
IDSC2 1012... 9 ft, 9 3/4 in. 11 ft, 11 3/4 in.
IDSC2 1018... 9 ft, 9 3/4 in. 18 ft, 4 in.
IDSC2 1212... 11 ft, 10 in. 11 ft, 11 3/4 in
IDSC2 1218... 11 ft, 10 in. 18 ft, 4 in.
Table 9: IDSC2 steel support dimensions, dual cell
arrangements (end-to-end)
Model A1 B1
IDSC2 0812... — —
IDSC2 1024... 9 ft, 9 3/4 in. 24 ft, 1 1/2 in.
IDSC2 1036... 9 ft, 9 3/4 in. 36 ft, 10 in.
IDSC2 1224... 11 ft, 10 in. 24 ft, 1 1/2 in.
IDSC2 1226... 11 ft, 10 in. 36 ft, 10 in.
C7 C7
C7 C7
C7C7
C4 C4
C3
C3
C8
C8 C8
140.020-IOM (OCT 2020)
Page 11
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Table 10: IDSC2 steel support dimensions, dual cell
arrangements (side-to-side)
Model A1 B1
IDSC2 0812... — —
IDSC2 2412... 23 ft, 10 in. 11 ft, 11 3/4 in.
IDSC2 2418... 23 ft, 10 in. 18 ft, 4 in.
Table 11: IDSC2 steel support dimensions, quad cell
arrangements
Model A1 B1
IDSC2 2424... 23 ft, 10 in. 24 ft, 1 1/2 in.
IDSC2 2436... 23 ft, 10 in. 36 ft, 10 in.
Figure 12: End view dimension, in. (mm)
Receiving and inspection
All units are packaged so that you can remove them from
a truck using a crane.
All units are factory-tested to ensure safe operation and
quality assembly. Units are packaged and shipped in two
pieces or more, depending on options ordered, for easy
handling and storage at the job site, if necessary.
NOTICE
Record any unit damage or shortages on the Bill of
Lading and report to the carrier and factory im-
mediately. Shipping and handling damages are not
warranty items.
Take photos of all damaged equipment if possible. Dam-
aged equipment is the responsibility of the designated
carrier. Do not return to the manufacturer unless prior
approval is given to do so. Conrm that you have received
all items listed on bill of lading.
C/L of unit load
Mounting hole
1 5/8 (41)
13/16 (21)
Unit
NOTICE
Refer to the submittal package for specic unit infor-
mation.
NOTICE
When lifting the unit use only the designated lifting
lugs as detailed on the rigging drawing attached to
the unit at the time of shipping. Always ensure that
the lifting points are balanced so that the unit is level
during lifting.
Rigging and hardware
Figure 13: Rigging and hardware parts
C
D
B
A
Callout Description
A Lifting lugs
BScrew pin shackles. A minimum
capacity of 3 tons
CSpreader bars. A minimum capacity of
10 tons
DStraps or chains. A minimum capacity
of 3 tons
140.020-IOM (OCT 2020)
Page 12
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 14: Upper casing section rigged
Figure 15: Basin section rigged
Figure 16: Rigging connections
Rigging the basin section
1. Remove the nuts from the shipping support so that
when lifting the units the shipping support detaches,
allowing you to remove the basin section.
2. Dispose of shipping support after lifting the basin
section.
Figure 17: Nuts on shipping support
3. Secure four screw pin shackles through each of the 4
lifting lugs.
Figure 18: Basin shipping support nut removal
Figure 19: Pin shackles at the lifting lugs
Lifting
lugs
WARNING
Do not use hooks to lift the unit.
4. Use the straps or chains to attach the spreader bar to
the basin section of the unit.
140.020-IOM (OCT 2020)
Page 13
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 21: Lower section of the unit - lifting guidelines
8.5' WIDE UNITS
43°
120.0"
10'-0"
94.9"
7'-10.9"
12' LONG UNITS
120.0"
10'-0"
44°
99.4"
8'-3.4"
10' WIDE UNITS
120"
10'-0"
49°
111.1"
9'-3.1"
12' WIDE UNITS
58°
135.4"
11'-3.4"
120"
10'-0"
18' LONG UNITS
120"
10'-0"
117.5"
9'-9.5"
52°
FRONT VIEW SIDE VIEW
8.5' WIDE UNITS
4
120.0"
10'-0"
94.9"
7'-10.9"
12' LONG UNITS
120.0"
10'-0"
4
99.4"
8'-3.4"
10' WIDE UNITS
120"
10'-0"
4
111.1"
9'-3.1"
12' WIDE UNITS
5
135.4"
11'-3.4"
120"
10'-0"
18' LONG UNITS
120"
10'-0"
117.5"
9'-9.5"
5
FRONT VIEW SIDE VIEW
8.5' WIDE UNITS
4
120.0"
10'-0"
94.9"
7'-10.9"
12' LONG UNITS
120.0"
10'-0"
4
99.4"
8'-3.4"
10' WIDE UNITS
120"
10'-0"
4
111.1"
9'-3.1"
12' WIDE UNITS
5
135.4"
11'-3.4"
120"
10'-0"
18' LONG UNITS
120"
10'-0"
117.5"
9'-9.5"
5
FRONT VIEW SIDE VIEW
8.5' WIDE UNITS
4
120.0"
10'-0"
94.9"
7'-10.9"
12' LONG UNITS
120.0"
10'-0"
4
99.4"
8'-3.4"
10' WIDE UNITS
120"
10'-0"
4
111.1"
9'-3.1"
12' WIDE UNITS
5
135.4"
11'-3.4"
120"
10'-0"
18' LONG UNITS
120"
10'-0"
117.5"
9'-9.5"
5
FRONT VIEW SIDE VIEW
NOTICE
Spreader bar must traverse the full width of the unit,
not the length. Incorrect size and use of the spreader
bar may result in equipment damage.
Figure 20: Lifting basin section with spreader bar
94.9 in.
(7 ft, 10.9 in.)
120 in.
(10 ft)
120 in.
(10 ft)
120 in.
(10 ft)
120 in.
(10 ft)
120 in.
(10 ft)
8.5 ft wide units
10 ft wide units
12 ft wide units
18 ft long units 12 ft long units
43°
49°
58°
52°
44°
135.4 in
(11 ft, 3.4 in.) 111.1 in
(9 ft, 3.1 in.)
117.5 in
(9 ft, 9.5 in.)
99.4 in
(8 ft, 3.4 in.)
140.020-IOM (OCT 2020)
Page 14
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
10' WIDE UNITS
12' WIDE UNITS
18' LONG UNITS
12' LONG UNITS
60° 120.0
( 10' )
48°
106.3
(8' - 10.3")
138.2
(11' - 6.2")
120.0
( 10' )
113.9
( 9' - 5.9")
51°
109.0
(9' - 1")
120.0
( 10' )
120.0
( 10' )
49°
Figure 22: Upper section of the unit - lifting guidelines
120 in.
(10 ft)
120 in.
(10 ft)
120 in.
(10 ft)
120 in.
(10 ft)
18 ft long units
10 ft wide units
12 ft wide units 12 ft long units
51°
60° 48°
49°
113.9 in
(9 ft, 5.9 in.)
138.2 in
(11 ft, 6.2 in.) 106.3 in
(8 ft, 10.3 in.)
109 in
(9 ft, 1 in.)
140.020-IOM (OCT 2020)
Page 15
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Rigging the upper casing section
1. Remove all four screws from each plate that holds the
shipping support structure to the unit. This way, when
lifting the unit off the truck it also lifts off the shipping
support structure.
Figure 23: Upper casing shipping support screw removal
Remove
2. Secure four screw pin shackles through each of the
4 lifting lugs.
Figure 24: Screw pin shackle attachment
WARNING
Do not use hooks to lift the unit.
Figure 25: Lifting upper casing with spreader bar
3. Use the straps or chains to attach the spreader bar to
the upper section of the unit.
Figure 26: Screw pin shackle attachment
140.020-IOM (OCT 2020)
Page 16
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
See Figure 27 to Figure 31 for vertical dimension require-
ments for lifting the top section of the unit with two
spreader bars.
NOTICE
Compromising the vertical dimensions indicated be-
low may result in equipment damage.
Figure 27: 12 ft long unit
Figure 28: 18 ft long unit
NOTICE
Refer to the submittal package for specic installation
instructions.
46°
Ref.
106.3 in.
(8 ft, 10.3 in.)
Spreader
bars
Minimum recommended
sling length 10 ft long
Minimum recommended
sling length 10 ft long
Spreader bar
drop leg
20 in.
minimum
Spreader
bars
109 in.
(9 ft, 1 in.)
49°
Ref.
Minimum recommended sling
length 10 ft long
Minimum recommended sling
length 10 ft long
Spreader bar
drop leg
20 in.
minimum
140.020-IOM (OCT 2020)
Page 17
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 29: 8.5 ft wide unit
Figure 30: 10 ft wide unit
57°
Ref.
114.4 in.
(9 ft, 6.4 in.)
Minimum recommended
sling length 10 ft long
Minimum recommended
sling length 10 ft long
20 in.
minimum
Spreader bars
Spreader bars
drop leg
Figure 31: 12 ft wide unit
57°
Ref.
138.7 in.
(11 ft, 6.7 in.)
Minimum recommended
sling length 10 ft long
Minimum recommended
sling length 10 ft long
20 in.
minimum
Spreader bars
Spreader bars
drop leg
NOTICE
Refer to the submittal package for specic installation
instructions.
48°
Ref.
98.2 in.
(8 ft, 2.2 in.)
Spreader bars
Spreader bars
drop leg
Minimum recommended
sling length 10 ft long
Minimum recommended
sling length 10 ft long
20 in.
minimum
140.020-IOM (OCT 2020)
Page 18
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Ofoading and assembly
Compare the data on the nameplate of the unit with the
submittal information to verify you received the correct
unit. Verify model nomenclature and electrical data with
the original order.
NOTICE
Remove any loose parts which were shipped in the
basin section of the unit before installation, when
applicable.
Installing the basin
1. See Rigging and Hardware for instructions on rigging
the basin.
2. Slowly lift the basin section from the shipping support
structure, move to the installation location, and set on
the support structure.
NOTICE
Take care when lifting the basin section so that it is
lifted level with little or no tilt. This ensures the drain
connection pipe does not come in contact with the
ground or any objects in order to prevent damage.
3. Check the position of the basin on the support struc-
ture to ensure proper positioning and that it conforms
to the information provided in Support Structure.
4. Secure the basin section of unit to the support struc-
ture with suitable 3/4 in. diameter bolts (not provided).
Use all of the bolt holes to secure the unit to the
support structure. For bolt hole locations, refer to
the Frick unit certied drawing.
5. Prevent stresses on the unit:
Check that all mounting bolts are tightened equally
to ensure balanced load distribution.
See Riser Pipe Coupling Installation before rigging the up-
per casing section.
Fitting the upper casing section
1. See Rigging and Hardware for instructions on rigging
the upper section.
2. Slowly lift the upper section and move to the installa-
tion location to t the upper section on top of the basin
section.
Figure 32: Lifting the top section of the unit
3. Align the upper casing section with the basin section.
Figure 33: Aligning top and bottom sections
4. Appropriately guide the upper section safely into the
recess and ensure it is free from pinch points.
Figure 34: Positioning the top section of the unit
140.020-IOM (OCT 2020)
Page 19
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
NOTICE
There is already a clearance “gap” designed between
the polyvinyl chloride (PVC) riser pipe in the basin
section and upper section. Take care when lifting the
upper section such that it is lifted level (with little or
no tilt) to ensure the PVC riser pipe does not come in
contact with the ground, any objects, or the basin sec-
tion in order to prevent damage.
Connection joint
Bolt the upper casing section and the basin section to-
gether using the connection joint.
Installing the riser pipe coupling
1. Align the casing to the basin then proceed with tight-
ening the union nut.
Figure 35: Casing
2. Install the cover with M6 x 20 (10x) screws and wash-
ers.
Figure 36: Casing installed
NOTICE
Refer to the submittal package for specic installation
instructions.
Inlet louvers
The narrower inlet louvers t into the inlet louver
openings on the front and back of the unit.
The wider inlet louvers t into the inlet louver openings
on the sides of the unit.
Position inlet louvers so that the louver pattern points
downward into the basin section. See Figure 37.
Figure 37: Positioning louver
After installing the inlet louvers, the top is held in place
by the inlet louver front supports. See Figure 38.
140.020-IOM (OCT 2020)
Page 20
IDSC2 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 38: Louvers and supports
Installing inlet louvers
1. Pick up the inlet louver by holding the louver pattern.
2. Angle the inlet louver to place the top end into the
inlet louver space and slide it all the way up under the
squared inlet louver front supports.
Figure 39: Angling the louver
3. While the inlet louver is slid as far up as it can go into
the inlet louver opening, put the bottom of the inlet
louver into place.
4. Set the inlet louver down so that it rests in the bottom
of the inlet louver opening.
Figure 40: Setting the louver
Removing inlet louvers
1. Grab the inlet louver pattern.
2. Slide the inlet louver straight up to release the bottom
of the inlet louver from the inlet louver opening.
Figure 41: Detaching the louver
3. Pull the bottom of the inlet louver out to remove it.
4. Slide the inlet louver down to release the top of the
inlet louver from the inlet louver front supports.
Figure 42: Removing the louver
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Frick IDSC2 Evaporative Condenser Installation Operation and Maintenance Guide

Type
Installation Operation and Maintenance Guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI