Danfoss ECL Comfort 210/296/310, A214/A314 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210/296/310, A214/A314 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA214/A314
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................25
2.3Mounting...........................................................56
2.4Placingthetemperaturesensors................................59
2.5Electricalconnections.............................................61
2.6InsertingtheECLApplicationKey..............................79
2.7Checklist............................................................85
2.8Navigation,ECLApplicationKeyA214/A314................86
3.0Dailyuse.......................................................104
3.1Howtonavigate.................................................104
3.2Understandingthecontrollerdisplay........................105
3.3Ageneraloverview:Whatdothesymbols
mean?..............................................................108
3.4Monitoringtemperaturesandsystem
components......................................................109
3.5Influenceoverview..............................................110
3.6Manualcontrol...................................................111
3.7Schedule..........................................................113
4.0Settingsoverview..........................................114
5.0Settings.........................................................117
5.1IntroductiontoSettings........................................117
5.2Flowtemperature/Inlettemperature.......................118
5.3DuctTlimit/Roomlimit........................................120
5.4Returnlimit.......................................................122
5.5LimitTsafety.....................................................124
5.6Compensation1.................................................125
5.7Compensation2.................................................127
5.8Controlparameters..............................................129
5.9Fan/acc.control(fan/accessorycontrol)..................138
5.10Application.......................................................145
5.11Alarm..............................................................159
6.0Commoncontrollersettings............................165
6.1IntroductiontoCommoncontrollersettings’..............165
6.2Time&Date.......................................................166
6.3Holiday............................................................167
6.4Inputoverview...................................................169
6.5Log.................................................................170
6.6Outputoverride..................................................171
6.7Keyfunctions.....................................................172
6.8System.............................................................174
7.0Miscellaneous................................................181
7.1ECA30/31setupprocedures.................................181
7.2Severalcontrollersinthesamesystem......................189
7.3Frequentlyaskedquestions....................................192
7.4Definitions........................................................194
7.5Type(ID6001),overview.......................................197
7.6ParameterIDoverview..........................................198
©Danfoss|2018.08VI.GU.A4.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA214
(ordercodeno.087H3811).
TheECLApplicationKeyA214containsthesubtypes:
A214.1A214.6(applicableinECLComfort210,296and310)
A314.1A314.7(applicableinECLComfort310)
A314.9(applicableinECLComfort310)
A214.1iscoolingrelatedapplication
A214.2,A214.3andA214.6areheatingrelatedapplications
A214.4andA214.5arebasicheating/coolingapplications
A314.1andA314.2arebasicheating/coolingapplications
A314.3isaspecialheatingapplication
A314.4andA314.5areadvancedheatingapplications
A314.6andA314.7areadvancedheating/coolingapplications
A314.9isanadvancedheatingapplication
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,e.g.
M-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA214complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin‘Commoncontrollersettings
in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand
thebuilt-inroomtemperaturesensorcanbeutilized.
TheapplicationsA314.1A314.7andA314.9workwiththe
InternalI/OmoduleECA32(ordercodeno.087H3202).
ECA32isplacedinthebasepartforECLComfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volta.c.(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com/.
2|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
VI.GU.A4.02
©Danfoss|2018.08|3
OperatingGuideECLComfort210/296/310,applicationA214/A314
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.0Installation
2.1Beforeyoustart
TheApplicationKeyA214containsseveralapplications,mainly
relatedtoventilationsystemswithheatingorcoolingora
combinationofthese.TheapplicationsintheA214keyofferawide
rangeofpossibilities(seetheexamples).
TheapplicationA214.1isveryflexible.Thesearethebasic
principles:
Coolingwithroomtemperaturecontrol:
Typically,theairducttemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM2(controllingthecoolingtransfer)is
openedgraduallywhentheducttemperatureishigherthanthe
desiredducttemperatureandviceversa.
Roomtemperature:
Ifthemeasuredroomtemperature(S4orECA30)doesnotequal
thedesiredroomtemperature,thedesiredtemperatureatS3can
beadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
coolingcircuitcanbein‘Comfortor‘Saving’mode(twodifferent
temperaturevaluesfordesiredroomtemperature).
Thedesiredroomtemperaturedeterminesacorrectionofthe
desiredtemperatureatS3.
Iftheroomtemperatureisnotmeasured,thedesiredroom
temperatureequals(willbe)thedesiredtemperatureatS3.Inthis
case,thesettingofthe'Balancetemperature'isnotconsidered(or:
hasnoinfluence).
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand
coolingdemand.Thedamper(P2)isON/OFFcontrolledaccording
toschedule.Thecirculationpump(X3)isON/OFFcontrolled
accordingtocoolingdemand.
Returntemperature(optional):
Ifthemeasuredreturntemperature(S5)doesnotequalthe
limitationvalue(typically,thereturntemperaturebecomeslower
thanthelimitationvalue),thedesiredtemperatureatS3canbe
adjusted(typicallytoahighervalue).Thisresultsinagradual
closingofthemotorizedcontrolvalve.
Asimplefrostprotection(viaS5)canbeestablished.Furthermore,
itisexpectedthatthecoolingexchanger(fancoil)circuitcontains
brine.
Foradescriptionofalarmsandcompensationtemperature,please
readthesectionA214andA314ingeneral’ .
TypicalA214.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
(Optional)Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M2
Motorizedcontrolvalve,cooling(3-point
controlled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|5
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationsA214.2andA214.3areveryflexibleandalmost
identical.Thesearethebasicprinciples:
A214.2:Heatingwithducttemperaturecontrol
A214.3:Heatingwithroomtemperaturecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.ThetemperaturesensorS3isthemostimportant
sensor.ThedesiredtemperatureatS3issetintheECLComfort
controllerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheatingsupply
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
S4temperature:
IfthemeasuredS4temperaturedoesnotequalthedesiredS4
temperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredS4temperature).ThedesiredS4
temperaturedeterminesacorrectionofthedesiredtemperature
atS3.
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand
heatingdemand.Thedamper(P2)isON/OFFcontrolledaccording
toschedule.Thecirculationpump(X3)isON/OFFcontrolled
accordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
6|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TypicalA214.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|7
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.4isveryflexible.Thesearethebasic
principles:
Heating/coolingwithairducttemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.
TheflowtemperaturesensorS3intheheatingcircuitisthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheflowtemperatureis
lowerthanthedesiredbalancetemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM2controlsthecooling
temperatureatS4.
Airducttemperature:
AtoolowairducttemperatureS4willactivatetheheatingcircuit
M1,whereasatoohighairducttemperaturewillactivatethe
coolingcircuitM2.
Atheatingdemand,theairducttemperatureS4canadjustthe
desiredtemperatureatS3.Atcoolingdemand,theairduct
temperatureS4iscontrolledaccordingtothedesiredairduct
temperature.A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3
Heatingtemperaturesensor
S4
Airducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-point
controlled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
8|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.5isveryflexible.Thesearethebasic
principles:
Heating/coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.
ThetemperaturesensorS3intheairductisthemostimportant
sensor.ThedesiredtemperatureatS3issetintheECLComfort
controllerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperatureis
lowerthanthedesiredbalancetemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM2controlsthecooling
temperature.
Roomtemperature:
AtoolowroomtemperatureS4willactivatetheheatingcircuitM1,
whereasatoohighroomtemperaturewillactivatethecooling
circuitM2.A"Deadzone"(=numberofdegrees)canbesetinorder
toavoidunstableshiftsbetweenheatingandcoolingoperation.
Atheating/coolingdemand,theroomtemperatureS4canadjust
thedesiredtemperatureatS3.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|9
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.6isveryflexible.Thesearethebasic
principles:
Heatingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Roomtemperature:
Ifthemeasuredroomtemperature(S4orECA30)doesnotequal
thedesiredroomtemperature,thedesiredtemperatureatS3can
beadjusted.
Bymeansofaweekschedule(upto3Comfortperiods/day),
theheatingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).The
desiredroomtemperaturedeterminesacorrectionofthedesired
temperatureatS3.
Thecirculationpump(F1)isON/OFFcontrolledaccordingtothe
Schedule1.Theaccessory(P2)isON/OFFcontrolledaccording
toSchedule1or2.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5),frostprotection(S6andS7)andfire
alarmpleasereadthesectionA214andA314ingeneral’ .
TypicalA214.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3
Flowtemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor(notillustrated)
S7
(Optional)Frostthermostat(notillustrated)
S8
(Optional)Firethermostat(notillustrated)
F1
Circulationpump(ON/OFF)
P2
Accessoryoutput(ON/OFF)
X3
Optionaloutput(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
10|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.1isveryflexible.Thesearethebasic
principles:
Heatingand(passive)coolingwithairducttemperature
control
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheflowtemperatureis
lowerthanthedesiredtemperatureandviceversa.Atcooling,
themotorizeddamperM2controlsthecoolingtemperature.The
coolingsectioncanbepassive(re-circulation)oractive.
Airducttemperature:
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighducttemperaturewillactivatethecooling
circuit(M2).
Atheatingdemand,thetemperatureatS4canadjustthedesired
temperatureatS3.Atcoolingdemand,theS4temperatureis
controlledaccordingtothedesiredS4temperature.A"Deadzone"
(=numberofdegrees)canbesetinordertoavoidunstableshifts
betweenheatingandcoolingoperation.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
A1
Alarm
VI.GU.A4.02
©Danfoss|2018.08|11
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.2isveryflexible.Thesearethebasic
principles:
Heatingand(passive)coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.TheairducttemperaturesensorS3isthe
mostimportantsensor.ThedesiredtemperatureatS3issetinthe
ECLComfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperature
islowerthanthedesiredtemperatureandviceversa.Atcooling,
themotorizeddamperM2controlsthecoolingtemperature.The
coolingsectioncanbepassive(re-circulation)oractive.
Roomtemperature:
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighducttemperaturewillactivatethecooling
circuit(M2).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Atheating/coolingdemand,thetemperatureatS4canadjust
thedesiredtemperatureatS3.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
12|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.3isveryflexible.Thesearethebasic
principles:
Heatingwithroomtemperaturecontrol
Typically,theairducttemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairductemperatureis
lowerthanthedesiredairducttemperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heatingdemand.ThedamperP2isON/OFFcontrolledaccording
toschedule.ThecirculationpumpX3isON/OFFcontrolled
accordingtoheatingdemand.
Variablefanspeed(optional):
ThefanV1canbespeedcontrolledinrelationtothemeasured
windspeedS10.Thefanspeedcontrolsignalisa0–10voltsignal,
generatedbytheinternalinput/outputmoduleECA32.Amenu
intheECLComfort310containssettingsforrelationshipbetween
actualwindspeedanddesiredfanspeed.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S10
Windspeedsignal(0-10volt)
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
V1
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|13
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.4isveryflexible.These
arethebasicprinciples:
Heatingwithroomtemperatureandairpressurecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit,controlledbyM1,isthe
supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airpressurecontrol:
ThefansV2andV3arespeedcontrolledindividuallyinrelationto
desiredpressures(Pascal)atS11andS12.ThesignalsatS11and
S12aremeasuredas0-10voltandconvertedintoPascalintheECL
Comfort310.Furthermore,thespeedofthefanscanbeloweredat
loweroutdoortemperaturesinordertoreducecoldairinlet.
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecooling(settingthefansON)canbe
arranged,mainlyunderthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
14|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairpressurecontrol
(continued)
Ventilationduringsavingperiod:
Adesiredreducedpressurecanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out:
Whenoutdoortemperatureexceedsaselectablevalue,theheating
systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|15
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.5isveryflexible.These
arethebasicprinciples:
Heatingwithroomtemperatureandairqualitycontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit,controlledbyM1,isthe
supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airqualitycontrol(CO
2
measuredin"ppm"):
ThefansV2andV3areincreasedinspeedwhentheppmvalue(0-
10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed
relationbetweenV2andV3canbeset.Asanalternative,theS11
signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Airquality(CO
2
)signal(ppm).Alternative:Relative
Humiditysignal.
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
16|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairqualitycontrol
(continued)
Ventilationduringsavingperiod:
Adesiredfanspeedcanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out:
Whenoutdoortemperatureexceedsaselectablevalue,theheating
systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|17
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.6isveryflexible.These
arethebasicprinciples:
Heating/coolingwithroomtemperatureandairpressure
control
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit(controlledbyM1)andthe
coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperatureis
lowerthanthedesiredinlettemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM3controlsthecooling
temperature.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighairducttemperaturewillactivatethecooling
circuit(M3).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredinlettemperatureandtwo
differenttemperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airpressurecontrol:
ThefansV2andV3arespeedcontrolledindividuallyinrelationto
desiredpressures(Pascal)atS11andS12.ThesignalsatS11and
S12aremeasuredas0-10voltandconvertedintoPascalinthe
ECLComfort310.
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
18|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heating/coolingwithroomtemperatureandairpressure
control(continued)
M1andM3are3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|19
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.7isveryflexible.These
arethebasicprinciples:
Heating/coolingwithroomtemperatureandairquality
control
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit(controlledbyM1)andthe
coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Atcooling,themotorizedcontrolvalveM3controlsthecooling
temperature.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighairducttemperaturewillactivatethecooling
circuit(M3).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airqualitycontrol(CO
2
measuredin"ppm"):
ThefansV2andV3areincreasedinspeedwhentheppmvalue(0-
10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed
relationbetweenV2andV3canbeset.Asanalternative,theS11
signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.7application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Airquality(CO
2
)signal(ppm).Alternative:Relative
Humiditysignal
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
RecoverycircuitpumpON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
20|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
/