Danfoss ECL Comfort 210/296/310, A214/A314 Operating instructions

Category
Thermostats
Type
Operating instructions
OperatingGuide
ECLComfort210/296/310,applicationA214/A314
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................25
2.3Mounting...........................................................56
2.4Placingthetemperaturesensors................................59
2.5Electricalconnections.............................................61
2.6InsertingtheECLApplicationKey..............................79
2.7Checklist............................................................85
2.8Navigation,ECLApplicationKeyA214/A314................86
3.0Dailyuse.......................................................104
3.1Howtonavigate.................................................104
3.2Understandingthecontrollerdisplay........................105
3.3Ageneraloverview:Whatdothesymbols
mean?..............................................................108
3.4Monitoringtemperaturesandsystem
components......................................................109
3.5Influenceoverview..............................................110
3.6Manualcontrol...................................................111
3.7Schedule..........................................................113
4.0Settingsoverview..........................................114
5.0Settings.........................................................117
5.1IntroductiontoSettings........................................117
5.2Flowtemperature/Inlettemperature.......................118
5.3DuctTlimit/Roomlimit........................................120
5.4Returnlimit.......................................................122
5.5LimitTsafety.....................................................124
5.6Compensation1.................................................125
5.7Compensation2.................................................127
5.8Controlparameters..............................................129
5.9Fan/acc.control(fan/accessorycontrol)..................138
5.10Application.......................................................145
5.11Alarm..............................................................159
6.0Commoncontrollersettings............................165
6.1IntroductiontoCommoncontrollersettings’..............165
6.2Time&Date.......................................................166
6.3Holiday............................................................167
6.4Inputoverview...................................................169
6.5Log.................................................................170
6.6Outputoverride..................................................171
6.7Keyfunctions.....................................................172
6.8System.............................................................174
7.0Miscellaneous................................................181
7.1ECA30/31setupprocedures.................................181
7.2Severalcontrollersinthesamesystem......................189
7.3Frequentlyaskedquestions....................................192
7.4Definitions........................................................194
7.5Type(ID6001),overview.......................................197
7.6ParameterIDoverview..........................................198
©Danfoss|2018.08VI.GU.A4.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA214
(ordercodeno.087H3811).
TheECLApplicationKeyA214containsthesubtypes:
A214.1A214.6(applicableinECLComfort210,296and310)
A314.1A314.7(applicableinECLComfort310)
A314.9(applicableinECLComfort310)
A214.1iscoolingrelatedapplication
A214.2,A214.3andA214.6areheatingrelatedapplications
A214.4andA214.5arebasicheating/coolingapplications
A314.1andA314.2arebasicheating/coolingapplications
A314.3isaspecialheatingapplication
A314.4andA314.5areadvancedheatingapplications
A314.6andA314.7areadvancedheating/coolingapplications
A314.9isanadvancedheatingapplication
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,e.g.
M-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA214complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin‘Commoncontrollersettings
in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand
thebuilt-inroomtemperaturesensorcanbeutilized.
TheapplicationsA314.1A314.7andA314.9workwiththe
InternalI/OmoduleECA32(ordercodeno.087H3202).
ECA32isplacedinthebasepartforECLComfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volta.c.(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com/.
2|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
VI.GU.A4.02
©Danfoss|2018.08|3
OperatingGuideECLComfort210/296/310,applicationA214/A314
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
2.0Installation
2.1Beforeyoustart
TheApplicationKeyA214containsseveralapplications,mainly
relatedtoventilationsystemswithheatingorcoolingora
combinationofthese.TheapplicationsintheA214keyofferawide
rangeofpossibilities(seetheexamples).
TheapplicationA214.1isveryflexible.Thesearethebasic
principles:
Coolingwithroomtemperaturecontrol:
Typically,theairducttemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM2(controllingthecoolingtransfer)is
openedgraduallywhentheducttemperatureishigherthanthe
desiredducttemperatureandviceversa.
Roomtemperature:
Ifthemeasuredroomtemperature(S4orECA30)doesnotequal
thedesiredroomtemperature,thedesiredtemperatureatS3can
beadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
coolingcircuitcanbein‘Comfortor‘Saving’mode(twodifferent
temperaturevaluesfordesiredroomtemperature).
Thedesiredroomtemperaturedeterminesacorrectionofthe
desiredtemperatureatS3.
Iftheroomtemperatureisnotmeasured,thedesiredroom
temperatureequals(willbe)thedesiredtemperatureatS3.Inthis
case,thesettingofthe'Balancetemperature'isnotconsidered(or:
hasnoinfluence).
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand
coolingdemand.Thedamper(P2)isON/OFFcontrolledaccording
toschedule.Thecirculationpump(X3)isON/OFFcontrolled
accordingtocoolingdemand.
Returntemperature(optional):
Ifthemeasuredreturntemperature(S5)doesnotequalthe
limitationvalue(typically,thereturntemperaturebecomeslower
thanthelimitationvalue),thedesiredtemperatureatS3canbe
adjusted(typicallytoahighervalue).Thisresultsinagradual
closingofthemotorizedcontrolvalve.
Asimplefrostprotection(viaS5)canbeestablished.Furthermore,
itisexpectedthatthecoolingexchanger(fancoil)circuitcontains
brine.
Foradescriptionofalarmsandcompensationtemperature,please
readthesectionA214andA314ingeneral’ .
TypicalA214.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
(Optional)Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M2
Motorizedcontrolvalve,cooling(3-point
controlled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|5
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationsA214.2andA214.3areveryflexibleandalmost
identical.Thesearethebasicprinciples:
A214.2:Heatingwithducttemperaturecontrol
A214.3:Heatingwithroomtemperaturecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.ThetemperaturesensorS3isthemostimportant
sensor.ThedesiredtemperatureatS3issetintheECLComfort
controllerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheatingsupply
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
S4temperature:
IfthemeasuredS4temperaturedoesnotequalthedesiredS4
temperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredS4temperature).ThedesiredS4
temperaturedeterminesacorrectionofthedesiredtemperature
atS3.
Thefan(F1)isON/OFFcontrolledaccordingtothescheduleand
heatingdemand.Thedamper(P2)isON/OFFcontrolledaccording
toschedule.Thecirculationpump(X3)isON/OFFcontrolled
accordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
6|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TypicalA214.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|7
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.4isveryflexible.Thesearethebasic
principles:
Heating/coolingwithairducttemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.
TheflowtemperaturesensorS3intheheatingcircuitisthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheflowtemperatureis
lowerthanthedesiredbalancetemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM2controlsthecooling
temperatureatS4.
Airducttemperature:
AtoolowairducttemperatureS4willactivatetheheatingcircuit
M1,whereasatoohighairducttemperaturewillactivatethe
coolingcircuitM2.
Atheatingdemand,theairducttemperatureS4canadjustthe
desiredtemperatureatS3.Atcoolingdemand,theairduct
temperatureS4iscontrolledaccordingtothedesiredairduct
temperature.A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3
Heatingtemperaturesensor
S4
Airducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-point
controlled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
8|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.5isveryflexible.Thesearethebasic
principles:
Heating/coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.
ThetemperaturesensorS3intheairductisthemostimportant
sensor.ThedesiredtemperatureatS3issetintheECLComfort
controllerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperatureis
lowerthanthedesiredbalancetemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM2controlsthecooling
temperature.
Roomtemperature:
AtoolowroomtemperatureS4willactivatetheheatingcircuitM1,
whereasatoohighroomtemperaturewillactivatethecooling
circuitM2.A"Deadzone"(=numberofdegrees)canbesetinorder
toavoidunstableshiftsbetweenheatingandcoolingoperation.
Atheating/coolingdemand,theroomtemperatureS4canadjust
thedesiredtemperatureatS3.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA214.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor(not
illustrated)
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|9
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA214.6isveryflexible.Thesearethebasic
principles:
Heatingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Roomtemperature:
Ifthemeasuredroomtemperature(S4orECA30)doesnotequal
thedesiredroomtemperature,thedesiredtemperatureatS3can
beadjusted.
Bymeansofaweekschedule(upto3Comfortperiods/day),
theheatingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).The
desiredroomtemperaturedeterminesacorrectionofthedesired
temperatureatS3.
Thecirculationpump(F1)isON/OFFcontrolledaccordingtothe
Schedule1.Theaccessory(P2)isON/OFFcontrolledaccording
toSchedule1or2.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5),frostprotection(S6andS7)andfire
alarmpleasereadthesectionA214andA314ingeneral’ .
TypicalA214.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/310
ElectroniccontrollerECLComfort210or310
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3
Flowtemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor(notillustrated)
S7
(Optional)Frostthermostat(notillustrated)
S8
(Optional)Firethermostat(notillustrated)
F1
Circulationpump(ON/OFF)
P2
Accessoryoutput(ON/OFF)
X3
Optionaloutput(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
A1
Alarm
*Alternative:ECA30
10|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.1isveryflexible.Thesearethebasic
principles:
Heatingand(passive)coolingwithairducttemperature
control
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheflowtemperatureis
lowerthanthedesiredtemperatureandviceversa.Atcooling,
themotorizeddamperM2controlsthecoolingtemperature.The
coolingsectioncanbepassive(re-circulation)oractive.
Airducttemperature:
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighducttemperaturewillactivatethecooling
circuit(M2).
Atheatingdemand,thetemperatureatS4canadjustthedesired
temperatureatS3.Atcoolingdemand,theS4temperatureis
controlledaccordingtothedesiredS4temperature.A"Deadzone"
(=numberofdegrees)canbesetinordertoavoidunstableshifts
betweenheatingandcoolingoperation.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredairducttemperature).
In'Saving'modethedesiredairducttemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3
Flowtemperaturesensor
S4Ducttemperaturesensor
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
A1
Alarm
VI.GU.A4.02
©Danfoss|2018.08|11
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.2isveryflexible.Thesearethebasic
principles:
Heatingand(passive)coolingwithroomtemperaturecontrol
Typically,theheating/coolingtemperatureisadjustedaccording
toyourrequirements.TheairducttemperaturesensorS3isthe
mostimportantsensor.ThedesiredtemperatureatS3issetinthe
ECLComfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperature
islowerthanthedesiredtemperatureandviceversa.Atcooling,
themotorizeddamperM2controlsthecoolingtemperature.The
coolingsectioncanbepassive(re-circulation)oractive.
Roomtemperature:
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighducttemperaturewillactivatethecooling
circuit(M2).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Atheating/coolingdemand,thetemperatureatS4canadjust
thedesiredtemperatureatS3.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3inheatingmode.In
coolingmodethecoolingisOFFduring'Saving'.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heating/coolingdemand.ThedamperP2isON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
12|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheapplicationA314.3isveryflexible.Thesearethebasic
principles:
Heatingwithroomtemperaturecontrol
Typically,theairducttemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredbalancetemperature'.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairductemperatureis
lowerthanthedesiredairducttemperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredroomtemperature).
In'Saving'modethedesiredroomtemperaturedeterminesa
correctionofthedesiredtemperatureatS3.
ThefanF1isON/OFFcontrolledaccordingtothescheduleand
heatingdemand.ThedamperP2isON/OFFcontrolledaccording
toschedule.ThecirculationpumpX3isON/OFFcontrolled
accordingtoheatingdemand.
Variablefanspeed(optional):
ThefanV1canbespeedcontrolledinrelationtothemeasured
windspeedS10.Thefanspeedcontrolsignalisa0–10voltsignal,
generatedbytheinternalinput/outputmoduleECA32.Amenu
intheECLComfort310containssettingsforrelationshipbetween
actualwindspeedanddesiredfanspeed.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
TypicalA314.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S10
Windspeedsignal(0-10volt)
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizeddamper(0-10voltcontrolled)
V1
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
VI.GU.A4.02
©Danfoss|2018.08|13
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.4isveryflexible.These
arethebasicprinciples:
Heatingwithroomtemperatureandairpressurecontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit,controlledbyM1,isthe
supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airpressurecontrol:
ThefansV2andV3arespeedcontrolledindividuallyinrelationto
desiredpressures(Pascal)atS11andS12.ThesignalsatS11and
S12aremeasuredas0-10voltandconvertedintoPascalintheECL
Comfort310.Furthermore,thespeedofthefanscanbeloweredat
loweroutdoortemperaturesinordertoreducecoldairinlet.
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecooling(settingthefansON)canbe
arranged,mainlyunderthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
14|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairpressurecontrol
(continued)
Ventilationduringsavingperiod:
Adesiredreducedpressurecanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out:
Whenoutdoortemperatureexceedsaselectablevalue,theheating
systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|15
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.5isveryflexible.These
arethebasicprinciples:
Heatingwithroomtemperatureandairqualitycontrol
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit,controlledbyM1,isthe
supplementarycircuit.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airqualitycontrol(CO
2
measuredin"ppm"):
ThefansV2andV3areincreasedinspeedwhentheppmvalue(0-
10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed
relationbetweenV2andV3canbeset.Asanalternative,theS11
signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
TypicalA314.5application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Airquality(CO
2
)signal(ppm).Alternative:Relative
Humiditysignal.
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
P8
Nightdamper,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
16|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heatingwithroomtemperatureandairqualitycontrol
(continued)
Ventilationduringsavingperiod:
Adesiredfanspeedcanbeset.
Roomtemperaturesignalmustbepresent
ThenightdamperP8willopen
ThefanV2willoperateatreducedspeed
ThefanV3isOFF
P2isOFF
M2isOFF
Summercut-out:
Whenoutdoortemperatureexceedsaselectablevalue,theheating
systemclosestotally.
M1is3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|17
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.6isveryflexible.These
arethebasicprinciples:
Heating/coolingwithroomtemperatureandairpressure
control
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit(controlledbyM1)andthe
coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheairducttemperatureis
lowerthanthedesiredinlettemperatureandviceversa.
Atcooling,themotorizedcontrolvalveM3controlsthecooling
temperature.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighairducttemperaturewillactivatethecooling
circuit(M3).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heating/coolingcircuitcanbeinComfortor‘Savingmode(two
differenttemperaturevaluesfordesiredinlettemperatureandtwo
differenttemperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airpressurecontrol:
ThefansV2andV3arespeedcontrolledindividuallyinrelationto
desiredpressures(Pascal)atS11andS12.ThesignalsatS11and
S12aremeasuredas0-10voltandconvertedintoPascalinthe
ECLComfort310.
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.6application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Inletpressuresensor
S12
Outletpressuresensor
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
Recoverycircuitpump,ON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
18|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
Heating/coolingwithroomtemperatureandairpressure
control(continued)
M1andM3are3-pointcontrolled,whereasM2is0-10Vcontrolled.
Foradescriptionofalarms,compensationtemperature,return
temperaturelimitation(S5)andfrostprotection(S6andS7),please
readthesectionA214andA314ingeneral’ .
VI.GU.A4.02
©Danfoss|2018.08|19
OperatingGuideECLComfort210/296/310,applicationA214/A314
TheadvancedheatingapplicationA314.7isveryflexible.These
arethebasicprinciples:
Heating/coolingwithroomtemperatureandairquality
control
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit(controlledbyM1)andthe
coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Atcooling,themotorizedcontrolvalveM3controlsthecooling
temperature.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighairducttemperaturewillactivatethecooling
circuit(M3).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airqualitycontrol(CO
2
measuredin"ppm"):
ThefansV2andV3areincreasedinspeedwhentheppmvalue(0-
10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed
relationbetweenV2andV3canbeset.Asanalternative,theS11
signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
roomtemperatureishigherthandesiredsavingroom
temperature
outdoortemperatureislowerthantheroomtemperature
schedule3isinComfortmode
TypicalA314.7application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3Ducttemperaturesensor
S4
Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Airquality(CO
2
)signal(ppm).Alternative:Relative
Humiditysignal
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
RecoverycircuitpumpON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
20|©Danfoss|2018.08
VI.GU.A4.02
OperatingGuideECLComfort210/296/310,applicationA214/A314
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204