1119 WIRELESS DOOR SOUNDER
Installation Guide
DESCRIPTION
The Model1119Wireless Door
Sounder is a single‑zone
transmitter equipped with a
battery‑powered sounder that
provides100‑110decibels of
annunciation.
The1119provides a cover tamper,
sounder cuto, survey LED, and two
batteries. Thetransmitter’szone
input can be connected to a
standard door contact, typically
attached to an emergency exit
door for local annunciation during
the day and burglary alarm
annunciation at night. The sounder
always automatically turns on when
the door opens and can be silenced
depending on system configuration.
Compatibility
• All DMP1100Series Wireless
Receivers
• All DMP Burglary Panels
What is Included?
• One1119Wireless Door Sounder
• Two3.0V Lithium CR123A
batteries
• Hardware pack with a470k EOL
resistor and serial number labels
1PROGRAM THE PANEL
To allow the1119sounder to be turned on or silenced by the panel,
the transmitter serial number must be programmed as an output in
OUTPUT INFORMATION and assigned to the ALARM ACTION output
in ZONE INFORMATION. Refer to “Silence the Sounder” for more
information.
Note: When programming both the output and zone, ensure the
Supervision Time is set to the same value.
To enter panel programming, reset the panel and enter 6653 (PROG)
at a keypad. After completing each of the following steps, press CMD
to advance to the next prompt. After you finish programming, go to
STOP and press CMD to save and exit the Programmer menu. For more
information, refer to the appropriate panel programming guide.
PANEL MODEL SLOW RESPONSE FAST RESPONSE
XR Series 450‑474 480‑499
XT Series 31‑34 41‑44
XTL Series 51‑54 61‑64
Table 1: Valid Output Numbers by Panel Model
Program the Output
1. Go to OUTPUT INFO (XR
Series) or OUTPUT SETUP
(XT and XTL Series).
2. At OUTPUT NO, enter the
output number.
Refer to Table 1.
3. At OUTPUT NAME, enter
a descriptive name for the
output.
4. At SERIAL#, enter the
8‑digit device serial number that
starts with 15. Refer to Figure 1.
5. At SUPRVSN TIME, enter the supervision time in minutes.
Program the Zone
1. In ZONE INFORMATION, enter the wireless zone number.
2. At *UNUSED*, enter the zone name.
3. At ZONE TYPE, press any select key or area and select the zone
type.
a. If the sounder should be the only source of annunciation
during a disarmed state, select NT (Night).
b. If the system requires local annunciation at the keypad
when the panel is disarmed, select DY (Day).
4. At AREA NO, select the area where you want the zone assigned.
5. At the NEXT ZONE prompt, select NO.
6. At WIRELESS?, select YES.
7. Enter the eight‑digit SERIAL# that starts with 02. Refer to
Figure 1.
8. At SUPRVSN TIME, enter a supervision time. Default is 240.
9. To allow the panel to control the sounder, select NO at the
NEXT ZONE prompt. The menu advances to ALARM ACTION.
10. At OUTPUT NO, enter the output number that you assigned to
the sounder in the previous section.
Figure 1: Zone and Output
Serial Number Location
ZONE
SN02999999
V112233440
SN15199999
V112233440
OUT
Zone Serial
Number
Output Serial
Number