Table 3: Module status
Module status Size Meaning Assignment
Input data status 2 bytes One sum bit per module for
the status of the module
inputs
0 = Error
1 = No error
Bit 0 = Main module
Bit 1 = 1st expansion module
Bit 2 = 2nd expansion module
…
Bit 13 = 1st gateway
Bit 14 = 2nd gateway
Bit 15 = Reserved
Output data status 2 bytes One sum bit per module for
the status of the module
outputs
0 = Error
1 = No error
Location status 2 bytes One sum bit per module for
the status of the module
inputs and outputs (AND
link of input data status
and output data status)
0 = Error
1 = No error
For information on the meaning of the status bits, refer to the operating instructions
titled “Flexi Soft in the Flexi Soft Designer Configuration Software” (SICK part number
8012998).
Input values and output values of the modules
•
Input values for I/O modules:
For each module, one byte is available for data set 1. The input values show the
status of the preliminary evaluation on the I/O module. This corresponds to the
status of the element in the logic of the main module. The level at the associated
terminal is not guaranteed to be identified from this as the data can be set to
0 due to the cross-circuit detection or dual-channel evaluation, regardless of the
level at the input terminal (e.g., I1 to I8).
If dual-channel input elements are configured at an I/O module, then only the
low-order bit represents the status of the preliminary evaluation for the affected
element (e.g., bit 0 for I1 and I2, bit 2 for I3 and I4, bit 4 for I5 and I6, bit 6 for I7
and I8). In this case, the high-order bit (bit 1, 3, 5, and 7) is used as follows:
Table 4: Using the higher-value bits for dual-channel evaluation at FX3-XTIO, FX3-XTDI or
FX3-XTDS I/O modules
Firmware version of FX3-
XTIO, FX3-XTDI or FX3-XTDS
Dual-channel equivalent
switch
Dual-channel complemen‐
tary switch
V1.xx.x Same state as the lower-
order bit
Inverted state of the lower-
order bit
V2.00.0 and above Status of the preliminary evaluation
0 = Error
1 = No error
•
Output values for I/O modules:
For each module with outputs, one byte is available for data set 1. The output
values show the status of the control information from the logic of the main
module for the affected element on the I/O module. The level of the associated
terminal is not guaranteed to be identified from this as the output can be disabled
due to the cross-circuit detection or overload detection.
If dual-channel output elements are configured at an I/O module, then only the
low-order bit is used for the control information (e.g., bit 0 for Q1 and Q2, bit 2 for
Q3 and Q4, bit 4 for Q5 and Q6, bit 6 for Q7 and Q8). In this case, the high-order
bit (bit 1, 3, 5, and 7) is not used, i.e., it has the value 0.
•
Input values for FX3-MOCx modules:
THE PROCESS IMAGE
4
8025562//2020-10-09 | SICK O P E R A T I N G I N S T R U C T I O N S | SIM1000 FXG in Flexi Soft Designer
11