DSPPA ADR6435 Operation Instructions Manual

Type
Operation Instructions Manual
Ø
ADR6435
Addressable PA Amplifier
Operation Instructions
Welcome to DSPPA public broadcast system. For better use of the equipment, please read the manual
carefully before operation.
Guangzhou DSPPA Audio Co., Ltd.
http//www.DSPPA.com
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
2
1. Product Description
1.1 About Simple Addressable System
The simple addressable broadcast host is a type of simple addressable public broadcast system that
integrates addressable control host, pre-amplifying function and final stage power amplifier, and also
combines terminal decoder or addressable speaker.
ADR6435 is the control host of the system, which is capable of controlling 100 zones. The host
employs BUS wiring pattern, and a pair of power wire is connected to every zone. The wiring is very
simple and the zone arrangement and adjustment require no change of line. The zone paging has
options for individual zone, all zones and partial zone, and the paging is provided with
pre-conversation ringing alert.
The simple addressable system composed by the equipment can be controlled by PC, which can
carry out timing programming control for this system.
The equipment is provided with four line input ports used for linking audio facilities of external
equipment to broadcast music programs for zones. In addition, the equipment is also provided with
remote paging extension interface for connection with remote pager.
The system composed by the equipment meets the requirements of the broadcast of schools,
factories, gardens, office buildings, shopping malls, stations and docks.
1.2 Function Features
l Simple addressable public broadcast system
l Addressable control host can control 100 zones
l System composed by the equipment adopts BUS wiring, and zone arrangement and adjustment
requires no change of line.
l Built-in pre-amplifying function, and provided with one microphone interface for convenient
paging.
l Pager has pre-conversation ringing alert, with ringing volume adjustable.
l Built-in power amplification function, provided with 100V constant voltage output interface.
l The equipment is also provided with four line input port, one line output port and one paging
extension port.
l Provided with PC extension port, the system can be controlled by PC.
l Provided with PC control software, providing timing control for zones
l The system uses high reliable control protocol from host to terminal, and supports
plug-and-play of the terminal.
l Energy-saving terminal is powered by the host and requires no local-power.
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
3
2. Brief Description of Product
2.1 Description of Front Panel
1 Power switch 2 power indicator 3 Resume
4 All On 5 All Off 6 Aux volume
7 MIC Volume 8 MIC in 9 Output level
10 Range select 11 Indirect select 12 Chime
2.2 Description of Rear Panel
1 Chime volume 2 Aux. Audio input 3 Aux. Audio output
4 Paging input 5 PC input jack 6 AC220V Power jack
7 AC220V fuse 8 cooling blower fan 9 Control output COM
10 Control output 100V jack
1
9
10
11
12
2
3
5
6
7
8
1
2
3
4 5
7
6
8
10
9
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
4
3 Example of System Connection
TAPE
The acoustic band decoder
TUNER
RECORDER
CDPLAY
Paging
Selector
TAPE
TUNER
RECORDER
CDPLAY
Paging
Selector
DEC
DEC
Speaker
Speaker
DEC
Speaker
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
5
4. Operation Descriptions
4.1 Zone Control Operations
The simple addressable system composed by this equipment is provided with 100 zones, and the
system controls the zones via control keys for the zones on the panel.
Under default status after power-on, the status indicator lamp of selection key of 120zones is on,
and the system is under status of the last shutdown. In this case, the first zone to 20
th
zone can be
directly controlled by key +1+20 (gently press the zone key once, if the indicator lamp is on, it
indicates the zone is switched-on; gently press the zone key when the indicator lamp is on can
make the indicator lamp go off, and it indicates the shutdown of the zone) .For control of zones
whose number is above 20, please press zone selection key first, and then the key for +1+20.
Control scope for the selection key of the five zones are as follows:
l Zone scope selection key 120 is used for controlling the first to 20th zones.
l Zone scope selection key " 2140 " is used for controlling the 21st to 40th zones.
l Zone scope selection key " 4160 " is used for controlling the 41st to 60th zones.
l Zone scope selection key " 6180 " is used for controlling the 61st to 80th zones.
l Zone scope selection key " 81100" is used for controlling the 81st to 100th zones.
Key ALL ON is used for switching on all the zones (100 zones). After switching on all the zones,
in case of a need to switch off a particular or certain zones, please select the related scope of the
zone with zone scope selection key, and then shut off all zones not required with zone control key.
Key ALL ON is used for switching off all the zones (100 zones).Similarly, after switching off all
the zones, in case of a need to switch on certain zones, the above procedures also apply.
Pressing key RESUME makes the system in "resuming" status, and the system reads and executes
the zone status stored in the memory. Under normal operation status of the equipment, prolonged
ON status of the indicator lamp relative to RESUME is called resuming status. Under resuming
status, the present status of all zones can be automatically stored to the memory of the equipment.
4.2 Playing Background Music for Zones
Connect audio facilities for any of the four sound input interfaces of the equipment and power on the
audio facility, then the system will allocate the audio automatically to the 100 terminals. (Note: the
10 zones only uses one audio). Among the four audio input interfaces, AUX1 has priority function. If
there are simultaneous signal input for AUX1 and any one among AUX2, AUX3 and AUX4, then
the input signal of AUX1 interface can automatically suppress the input signal of other lines.
4.3 Volume Control
Knobs AUX1 VOL, AUX2 VOL, AUX3 VOL and AUX4 VOL on the panel of the equipment are
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
6
used to control the volume of the input channels respectively. Knob MIC VOL is used to control
the volume of microphone. Clockwise turning represents volume increase, while anticlockwise
turning represents volume decrease.
Volume of the 100 zones is integratedly controlled by the knob on the panel of the equipment, i.e..
the equipment is not provided with separate control for simultaneous volume increase or decrease for
the 100 zones.
4.4 Paging and Priority Functions
Paging includes remote paging and paging of microphone connected to the equipment. The control
of zones by the remote pager enjoys priority over addressable host and PC control software. When
the zones are switched upon on the remote pager for paging, the five zone scope selection keys on
the panel of the equipment can be used to view the operation status of zones during the paging. Any
operation over the zones by addressable host and PC control software other than the operation by
remote pager will be invalid.
When the remote pager is conducting paging operation for a particular zone, if the zone is switched
on on the remote pager, then all the zones for background music will be switched off, then the paged
zone will be switched on. After the paging, use key ALL OFF on the pager to switch off all the
zones or the power of remote pager, and all the zones will resumed to the pre-paging operation status.
When the pager is conducting paging for all the zones, gently press ALL ON key on the remote
pager to switch on all the zones. In this case, the equipment will switch off the zone playing
background music first, then switch on all the zones. After the paging, gently press key ALL OFF
on the pager to resume the status of playing background music of the zones.
The system can also perform paging over the zones by the microphone connected to the equipment.
Prior to the paging, gently press the key for ringing alert on the panel to obtain the ringing tone.
Ringing volume can be adjusted by the ringing volume adjustment knob (1) on the panel of the
equipment. Adjust the microphone volume to the optimal position (until no howl is available for the
microphone), and then carry out paging for the zones.
When the system is playing the audio input by AUX1 interface, paging over zones can also be
performed by microphone. Input signal of AUX1 interface and ringing signal are the same priority
signal, and the output terminal can transmit three signals, any of which can cover the audio signal
input by AUX2, AUX3 and AUX4.
Note for Operation:
1. When the host is off, at least 10 minutes is required for re-energization.
2. When withdrawing from the remote paging (by pressing key ALL OFF of the remote pager),
please power off the microphone of remote pager at the same time, otherwise, the surrounding
sounds can still reach the zones switched on after the resuming via the microphone of pager.
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
7
4. Precautions for Operation
4.1 Precautions for Safety Operation
l Please do not insert the power supply plug of the equipment into the power network before
connecting properly the system circuitry.
l It should be ensured that the voltage supplied to the equipment be completely meeting the
voltage requirements of the equipment, otherwise, there may exist the risk of burning the
equipment.
l Danger voltage is inside the equipment, and the voltage is high enough to result in the
personnel electric shock. Please do not open the housing without authorization to prevent the
risk of electric shock.
l When the power switch of the equipment is at "OFF" status, the machine is not disconnected
completely with the power network. For your safety, please pull out the power cord from the
socket when the equipment is not to be used.
l Please do not place the equipment at a location too cold or too hot.
l Ensure a good ventilation and a good working condition for the equipment to prevent heating
in the working hours, otherwise, the machine may be damaged due to too high a temperature.
l The master power switch should be turned off at a cloudy day and damp weather or when the
equipment is not to be used for a long time.
l It is required to pull out the power plug to ensure that the equipment is completely
disengaged from the power network when it is to dis-assemble or re-assemble any part of the
equipment or to disconnect or connect plug of any electric apparatus of equipment or making
other connection.
l When the equipment has a failure, it is not allowed for the non-professional personnel to
open the housing to undertake the repair without authorization to prevent accident or
aggravating the damaged condition of the equipment.
l Do not place any chemical subject with corrosivity near the equipment or on the top of
equipment.
4.2 Precautions for After-sales Service
l The company will provide free of charge guarantee service (including provision of
replacement part free of charge) for one year dating from the day of purchase for any quality
problem in the normal range of application, provided that the installation and application are
in conformity to the stipulations given in the Operation Manual.
l At any time for the repair guarantee, the consumer should present the Card of Guarantee and
the sales invoice as a proof.
l The following conditions do not belong to the scope for free of charge service:
(1) Product damage due to mistaken installation, application or handling;
(2) Product damage due to abnormal condition (such as over power voltage or ambient
humidity, etc. );
(3) Product damage due to force majeure such as calamity or accident;
(4) The number on product body has been converted, altered or removed;
* Fire Fighting/Public Broadcast System Simple Addressable Broadcast System
* Addressable Control Host
8
(5) The product has once been repaired or modified by personnel not authorized by our
company;
l Please keep the Operation Manual and Card of Guarantee carefully.
l As to the subjects or precautions not mentioned in the manual, please contact the distributor
or visit the web page of our company: //www. dsppa. com when necessary.
l Please contact the service personnel of the company (or the distributor) if there is any failure
phenomena during the period of grantee, and the company shall not take the responsibility to
repair free of charge if the damage is due to dis-assembling by yourself or from the repair by
the technical personnel not from the company.
6. Performance Specifications
1 Speaker output
100V
2 Rated output 350W
3 Frequency response 50Hz-16KHz-3dB
4 Total harmonic distortion 0.5%
5 S/N ratio (A weighted) 80dB
Minimum power emfAUX 200mV
6
Minimum power emfMIC 3mV
7 Line output 1V
8 Muting function MICCHIMEAUX 1 overrides other input signals.
9 Protection AC fuse × 1, overloadshort circuit, temperature
10
Power Supply Requirements AC 220 V / 50 Hz
11
Net Weight 15.25kg
12
Gross Weight 17.3kg
13
Dimensions 430×320×125mm
Specifications are subject to change without notice.
Guangzhou DSPPA Audio Co., Ltd.