3
Parallel Inverter System Solution User Manual V1.1-2023-02-20
Parts Description
No. Parts Description
1Battery Select the battery model according to the approved battery list matched with the inverter. The models and
capacity of the battery connected to each inverter in the system are decided by the manufacturer.
2Bus Bar (Optional) A bus bar shall be added when multiple battery packs in parallel are connected to the inverters in
the system. For detailed information such as the battery pack quantity in parallel, bus bar and so on, please
refer to the related battery’s user manual.
3PV String PV string is composed of series connected PV panels.
4Battery
Breaker
The breakers shall conform to the requirements of local laws and regulations. 2P AC breakers shall be
prepared by the customers. The recommended specications are:
• For GW3000-ES-20, GW3600M-ES-20, GW5000M-ES-20 and GW6000M-ES-20: the nominal current ≥ 75A
and the nominal voltage ≥ 60V.
• For GW3600-ES-20, GW3500L-ES-BR20, GW3600-ES-BR20: the nominal current ≥ 100A and the nominal
voltage ≥ 60V.
• For GW5000-ES-20: the nominal current ≥ 125A and the nominal voltage ≥ 60V.
• For GW6000-ES-20, GW6000-ES-BR20: the nominal current ≥ 150A and the nominal voltage ≥ 60V.
5Inverter The G2 Version of ES Series Inverters (3.0-6.0kW) are able to be used. The inverters’ model shall be the same
in one parallel system.
6Ezlink Module • In parallel inverter scenarios, the Ezlink module is only allowed for networking.
• In one system, it is available to install only one Ezlink module and one smart meter. The inverter
connecting with the Ezlink module and the smart meter is the master inverter by default, and all
the others are slave inverters. The master inverter issues commands to the slave inverters via the
communication cables.
7AC Circuit
Breaker
When the number of inverters in the system is 3 < N ≤ 16, AC circuit breakers shall be installed on the
external of the AC side. The breakers’ specications for the BACK-UP and ON-GRID loads of one inverter
type shall be the same. AC breakers shall be prepared by the customers. The recommended specications
are:
• For GW3600M-ES-20: the nominal current ≥ 20A and the nominal voltage ≥ 230V.
• For GW3000-ES-20, GW5000M-ES-20, GW6000M-ES-20, GW3600-ES-20 and GW3600-ES-BR20: the nominal
current ≥ 40A and the nominal voltage ≥ 230V
• For GW5000-ES-20, GW6000-ES-20, GW3500L-ES-20-BR20 and GW6000-ES-BR20: the nominal current ≥
63A and the nominal voltage ≥ 230V.
8 Smart Meter When any phase’s current in the grid is no more than 120A, use the delivered smart meter or purchased
from the inverter manufacturer. Recommended model: GM1000.
When any phase’s current in the grid is more than 120A, select industrial and commercial Smart Meter and
CT. For details, please contact the After-Sales service.
9Switchboard • Prepare the switchboard by yourself.
• When there are no more than 3 parallel inverters in the system, prepare built-in AC breakers for BACK-UP
and ON-GRID loads, which are used to connect the AC cables of the inverters, and then get tied to the
grid.
• When the number of inverters in the system is 3 < N ≤ 16, prepare the switchboard with nominal current
≥ 2 x N x Imax (N refers to the parallel inverter quantity; Imax refers to the maximum output current of
the inverter.)
10 Load Breaker Depend on the actual using load.
11 Automatic
Transfer
Switch (ATS)
• When the number of inverters in the system is 3 < N ≤ 16, prepare ATS by yourself.
• ATS function:
1. when BACK-UP load is powered by the grid, to avoid un-even current under bypass mode and the load
current is too big to damage the inverter, install an ATS to ensure the grid current runs through the
ATS to provide the electricity to BACK-UP load.
2. power on all inverters in the system at the same time, to ensure electricity provided to the loads
simultaneously. Otherwise, it will cause overload protection.
• ATS specication:
1. with its normally closed contact connecting with the grid.
2. nominal current ≥ 2 x N x Imax (N refers to the parallel inverter quantity; Imax refers to the maximum
output current of the inverter.)
12 Manual
Bypass Switch
(Optional)
• When there are no more than 3 parallel inverters in the system, to ensure the BACK-UP load is powered
by the grid during the inverter maintenance, install a manual Bypass switch by yourself.
• The specication of the manual Bypass switch and the BACK-UP & ON-GRID load breakers:
• For GW3000-ES-20, GW3600M-ES-20, GW5000M-ES-20, GW6000M-ES-20, GW3600-ES-20 and GW3600-
ES-BR20: the nominal current ≥ 120A and the nominal voltage ≥ 230V.
• For GW5000-ES-20, GW6000-ES-20, GW3500L-ES-20-BR20 and GW6000-ES-BR20: the nominal current ≥
160A and the nominal voltage ≥ 230V.