Danfoss ECL Comfort 300 - C60 Operating instructions

Type
Operating instructions
How to use this guide
This guide is divided into two parts:
• Daily Use (Turn the guide over)
Yellow sections 01 - 09
• Installation and maintenance:
Grey sections 10 and onwards
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating systems.
The ECL Comfort controller ensures you of the following;
Room and hot water temperatures will be adjusted to
yourpersonal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range
of heating systems with different configurations and
capacities.
If your heating system differs from the diagrams shown in
section 10, you may want to sketch an outline of the
system about to be installed. This makes it easier to use the
Installer’s Guide, which will guide you step-by-step from
installation to final adjustments before the end-user takes
over.
Note! The controller is pre-programmed with factory
settings which are shown in the relevant sections of this
guide.
Before you start
VI.7C.B3.02
Identifying the system type
10
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance to your system and make
your own combinations.
Installation
Alternatives using the same settings:
• Heat exchanger or direct district heating
• 2-, 3-, or 4-way control valve
Heating system type 1
Two parallel connected heating circuits with heat
exchangers.
Set line 17 to OFF
Check line 24 in circuit I and II (gear motor/thermo actuator)
Heating system type 2
Two parallel connected heating circuits.
Set line 17 to OFF
Check line 24 i circuit I and II (gear motor/thermo actuator)
Installation
Note!
System diagrams in this instruction are principal drawings and
do not contain all components which are necessary in heating
systems.
Heating system type 3
Radiator heating circuit and secondary connected floor
heating circuit.
Set line 17 to 4K
Check line 24 in circuit I and II (gear motor/thermo actuator)
Heating system type 4
Boiler with two parallel connected heating circuits with heat
exchangers.
Set line 17 to OFF
Check line 24 in circuit I and II (gear motor/thermo actuator)
Mounting the ECL Comfort
controller
11
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Installation
Installation
Connecting the 230 V a.c. units
12
Electrical connections -
230 V a.c.
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted into each screw
terminal.
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Establish these jumpers:
1 L Supply voltage 230 V a.c.
(Live)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open/cir. I 0.2 A 230 V a.c.
4 M1 Gear motor - close/cir. I
alt.: ABV thermo actuator 0.2 A 230 V a.c.
5 230 V a.c. supply for
M1/cir. I
6 M2 Gear motor - open/cir. II 0.2 A 230 V a.c.
7 M2 Gear motor - close/cir. II 0.2 A 230 V a.c.
8 230 V a.c. supply for
M2/cir. II
9 P1 Circulation pump for 4(2)A 230 V a.c.
heating circuit I
10 230 V a.c. supply for
pump relay R1
11 P2 Circulation pump for
heating circuit II 4(2)A 230 V a.c.
12 230 V a.c. supply for
pump relay R2
Terminal Description Max. load
Installation
Connecting the sensors
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Note! Cable lengths above 100 m may cause noise sensibility
(EMC).
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2)
circuit I ESM-10
19 and 16 Flow sensor (S3)
circuit I ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
21 and 16 Flow sensor (S5)
circuit II ESMU/ESM-11/ESMC
22 and 16 Room sensor (S6)
circuit II ESM-10
Terminal Description Type (recommended)
Establish the jumper from 16 to common terminal.
Installation
Connecting the 24 V a.c. and 230 V a.c. units
13
Electrical connections -
24 V a.c.
Jumper from 1 to 5
Jumper from 5 to 8
Jumper from 8 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal
Establish these jumpers:
1 L Supply voltage 24 V a.c.
2 N Supply voltage 24 V a.c.
3 M1 Gear motor - open/cir. I 1A 24 V a.c.
4 M1 Gear motor - close/cir. I
alt.: ABV thermo actuator 1A 24 V a.c.
5 24 V a.c. supply for
M1/cir. I
6 M2 Gear motor - open/cir. II 1A 24 V a.c.
7 M2 Gear motor - close/cir. II 1A 24 V a.c.
8 24 V a.c. supply for
M2/cir. II
9 K1* Relay for circulation pump
for heating circuit I
10 24 V a.c. supply for
pump relay K1
11 K2* Relay for circulation pump
for heating circuit II
12 24 V a.c. supply for
pump relay K2
Terminal Description Max. load
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted into each screw
terminal.
* K1/K2 auxiliary relay
Coil: 24 V a.c.
Contacts: 4A 230 V a.c.
Installation
Connecting the sensors
Establish the jumper from 16 to common terminal.
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2)
circuit I ESM-10
19 and 16 Flow sensor (S3)
circuit I ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
21 and 16 Flow sensor (S5)
circuit II ESMU/ESM-11/ESMC
22 and 16 Room sensor (S6)
circuit II ESM-10
Terminal Description Type (recommended)
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Note! Cable lengths above 100 m may cause noise sensibility
(EMC).
Installation
Installation
Flow temperature sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean at the area
where the sensor is mounted.
Do not move the sensor after it has been fastened in
order to avoid damage to the sensor element.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the
correct position in your heating system.
Special attention should be paid to the following sensors:
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed max. 15 cm
from the mixing point. It should always be placed on a
pipe in which the water flow never stops.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls or close
to radiators, windows or doors.
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on the north side of
the building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors or
windows.
Installation
Line
Circuit
Time
Outdoor
temperature
Desired room
temperature
C
C99
Y
0
P
C
100
06
11
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
15
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data.
The controller immediately starts to copy the factory
settings and heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display line C.
The controller is now ready to be set to control your
heating system.
Installation
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system differs from
the standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings should
be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the ECL
Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10 min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the heating system
you can write a title on the ECL Card with a permanent
ink pen.
Installation
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and
service
All new settings can be stored on the ECL Card. For
details about copying, see section 34. Insert the ECL
Card with the yellow side facing you.
C
C99
Y
0
P
When the copying is finished display line C will appear
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
You can make other changes in the day plan, set
time and date or change settings
(see User’s Guide).
General principles
When the controller is connected and operating you
can check and adjust all or some of the basic settings
on the grey side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Line
indicator
Settings to
be adjusted
Value in range
indicator
Circuit
2
0904
1
1
ON
2
ON
2
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or
value can be adjusted. Use the shift button to
switch between the possibilities.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Go to line 9 (bottom line)
Accept to copy as indicated. No other keys are
active.
Basic set-up
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12 hours,
the time and the date have to be set again.
All other settings are stored as programmed.
The grey side of the ECL Card.
Go to line A.
09
01
56019
5
A
3
Actual time
Month, day
Year
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See User’s Guide, section 4.
Basic set-up
Monitoring temperatures and
system units - Line B
18
Go to line B.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as “
- -”.
If the sensor is short-circuited, the display will indicate it as
- - - “.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
The grey side of the ECL Card.
5 036
B
1
1
ON
2
ON
2
Controlled units
State indicator
Return temperature
Flow
temperature
Push the shift button to see:
- the calculated flow temperature
- the return temperature set points
Relationship between temperature and ohmic value
-10°C 961 Ohm
0°C 1000 Ohm
10°C 1039 Ohm
20°C 1078 Ohm
30°C 1117 Ohm
40°C 1156 Ohm
50°C 1195 Ohm
60°C 1234 Ohm
70°C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Basic set-up
19
Manual control - Line B
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
The grey side of the ECL Card.
Go to line B.
Shift to manual mode
Select the unit you want to control. The
selected unit symbol will flash.
5 036
B
1
1
ON
2
ON
2
Controlled
units
Controller mode
The circuit selector shifts between circuit I and II.
Valves close or open while the
relevant button is pressed
Pumps are switched off or on
when the relevant button is pressed.
1
ON
1
1
Shift away from manual mode.
Basic set-up
Setting the heat curve - Line C
20
Go to line C.
The symbol for the slope of the heat curve will
flash.
Make your adjustments.
The grey side of the ECL Card.
Circuit Setting range Factory setting
I/II 0.2 ... 3.4 1.8
Slope
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Circuit Setting range Factory setting
l/II -9... +9 0
Parallel displacement
8
C
1
1
1
ON
2
ON
2
0
Slope
Displacement
Basic set-up
-20 -10 0 10 20-30
10
20
30
40
50
60
70
80
90
1,8
1,2
0,6
0,2
2,2
C
C
Circuit Setting range Typical setting
Slope
Circuit Setting range Typical setting
I -9 ... +9 0
Parallel displacement
I 0.2 ... 3.4 1.0
Floor heating systems
This controller is factory set for radiator systems, which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your type of system.
Basic set-up
Heating cut-out - Line 1
21
8
1
1
1
1
ON
2
ON
2
The grey side of the ECL Card.
Set the outdoor temperature limit at which you
want the heating system to stop.
Go to line 1.
Circuit Setting range Factory setting
I/II 10 ... 30 °C 18 °C
1 Limit for heating cut-out
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated Tout symbolises the heat stored in the
building.
18°C
Temp
Actual T
out
Accumulated T
out
Time
Heating Heating off Heating
Basic set-up
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63

Danfoss ECL Comfort 300 - C60 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI