Danfoss ECL Comfort 200 - P20 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 200 - P20 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ECL COMFORT
Table of Contents
Daily Use
Section
1 Choose favourite display
2 Select controller mode
3 Adjust room temperature
4 Setting personal day plan
6 Hot points
7 Definitions
Your personal week plan:
This guide is associated to ECL Card 087B4660
Installer:
By:
Date:
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Table of Contents
Sections of the Installers part of this guide.
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
13 Electrical connections 24 V a.c.
14 Placing the temperature sensors
15 Adapting the ECL Comfort controller
Basic Set-up
16 Adjusting the ECL Card settings
17 Setting the time and date - Line A
18 Monitoring temperatures and system units - Line B
19 Manual control - Line B
20 Setting the heat curve - Line C
21 Heating cut-out - Line 1
22 Flow temperature limits - Line 2
23 Room temperature influence - Line 3
24 Boiler control - Line 4
Check & Overviews
29 Check list
30 ECL Card settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Daily use, turn the guide over sections 01 - 07
1 Choose favourite display
2 Select controller mode
3 Adjust room temperature
4 Set personal day plan
6 Hot points
7 Definitions
ECL Comfort
Users Guide
P20
Boiler Control
P20
VI.7B.D4.02
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Installation and maintenance. Grey sections 10 and
onwards. Turn the guide over.
Heating 03691215182124
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Factory settings are grey.
6-8 16 - 22
823-
3 91
0
A
2
The shown diagram is a fundamental and simplified example
and does not contain all components that are necessary in
heating systems.
If the system you are about to install differs from the shown
diagram of a standard heating system, feel free to sketch
an outline for comparison. Adaptation of heating systems,
see section 10.
List of components:
ECL Comfort 200
S1 Outdoor temperature sensor (ESM-10)
S2 Room temperature sensor (ESM-10)
S3 Boiler temperature sensor (ESM-)
S4 Return temperature sensor (ESM-)
P1 Circulation pump for heating circuit
P2 Burner
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Extended service parameters,
see section 31
The ECL Card: Installers guide
The grey side of the card must face
you when you change settings. For
daily use and during start-up, the
yellow side of the card must face you.
User setting
indicator
User/
service
settings
Shift
button
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switch between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Switch between user settings (yellow
card side) and service settings (grey
card side).
The ECL Card
For daily use and your personal adjustments the yellow side
of the ECL Card must be facing you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switch between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Switch between user settings (yellow card
side) and service settings (grey card
side).
Line indicator
Room temperature
Heating system
information
Todays programme
Day plans
A
B
C
1
2
3
4
5
6
7
6
1
2
3
4
Heating circuit
Service setting
indicator
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
Adjustment Controller
mode
5
1
ON
036
B
ON
6
0 3 6 9 12 15
0
5
0
8
0 3 6 9 12 15 18 21 2
4
0
7
0
Before you start
How to use this guide
This guide is divided into two parts:
Daily Use (turn the guide over)
Yellow sections 1-7
Installation and maintenance:
Grey sections 10 and onwards
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating systems.
The ECL Comfort controller ensures you of the following;
Room temperatures will be adjusted to your personal
settings
.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with different configurations and
capacities.
If your heating system differs from the diagram shown in
section 10, you may want to sketch an outline of the system
about to be installed. This makes it easier to use the
Installers Guide, which guides you step-by-step from
installation to the final adjustments before the end-user
takes over.
Note! The controller is pre-programmed with factory
settings that are shown in the relevant sections of this
guide.
However, you might come across some settings that
are not listed in this instruction. These settings are used in
connection with optional modules, and you can find a
description of the settings and the corresponding
parameters in the instruction for optional module in
question.
Operating the ECL controller and the ECL Card
The ECL Card has a yellow side for the daily use and a
grey side for the installation and maintenance.
Both sides of the card are divided into lines representing
the different options of control and programming.
Select the side of the ECL Card you want to
operate.
The light diode below the inserted ECL Card
indicates the chosen side, ie. left light for daily use
and right light for the installation and maintenance.
(See sections 15 and 16).
VI.7B.D4.02
Identifying the system
type
10
Heating system type 1
Note!
The system diagram in this instruction is a principal drawing
and does not contain all the components for a heating
system.
Installation
Installation
Mounting the ECL Comfort
controller
11a
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Installation
Installation
11b
Connecting the sensors
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Cable type: Copper cable
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Connecting the 230 V a.c. units
12a
Electrical connections -
230 V a.c.
Establish the jumper from 16 to common terminal.
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
Terminal Description Type (recommended)
Establish these jumpers,
Jumper from 1 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal.
1 L Supply voltage 230 V a.c.
2 N Supply voltage 230 V a.c.
9 P1 Circulation pump 4(2)A 230 V a.c.
10 Phase for pump relay
11 P2 Burner 4(2)A 230 V a.c.
12 Phase for burner relay
Terminal Description Max. load
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw terminal.
Installation
Installation
12b
Connecting the sensors
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Cable type: Copper cable
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Connecting the 24 V a.c. and 230 V a.c. units
13a
Electrical connections -
24 V a.c.
Cable cross section for voltage conductor: 0.75 ... 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw terminal.
Establish these jumpers,
Jumper from 1 to 10
Jumper from 10 to 12
Jumper from 2 to common N-terminal.
1 L Supply voltage 24 V a.c.
2 N Supply voltage 24 V a.c.
9 K1* Relay for the circulation
pump P1 (2)A 230 V a.c.
10 24 V supply for relay K1
11 K2* Relay for burner 4(2)A 230 V a.c.
12 24 V supply for relay K2
Terminal Description Max. load
Establish the jumper from 16 to common terminal.
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
Terminal Description Type (recommended)
* K1/K2 auxiliary relay
Coil: 24 V a.c.
Installation
Installation
13b
15
Adapting the ECL Comfort
controller
While the set-up is in operation, the data transfer-display
will appear.
After initialising, the display will return to the standard
display line C of the yellow side of the ECL Card.
The controller is now ready to control the selected
heating system. You can make your own adjustments/
settings for daily use in the basic set-up and change the
extended service settings.
Open the lid and switch on the controller. The display
shows the heating system type.
P
10
02
1
P02
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
Accept to set up the selected system.
Select the heating system type printed on your
ECL Card.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the correct
position in your heating system.
Special attention should be paid to the following sensors.
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows
or air outlets.
Boiler sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor according to the boiler manufacturers
specification.
Do not move the sensor after it has been fastened in
order to avoid damage to the sensor element.
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed in/on a pipe
with return water flow.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls nor
close to radiators, windows or doors.
Insert the ECL Card with the grey side facing you.
See section 16 for general principles of operation and
section 17 for setting the time and date.
Select the grey side of the ECL Card for the
basic set-up and the extended service
parameters.
Installation
Installation
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12
hours, the time and date have to be set again.
All other settings are stored as programmed.
Go to line A.
09
01
5609
5
A
3
1
Actual time
Month, dayYear
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See Users Guide, section 4.
16
Adjusting the ECL Card
settings
If several controllers are installed in the heating
system you can write a title on the ECL Card with a
permanent ink pen.
Changing from one side of the ECL Card to the other
When changing from the grey side of the ECL Card to the
yellow side, you will always enter line C and the standard
display.
Changing from the yellow side to the grey side, you will
always enter line A - Time and date.
See opposite page.
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings
referring to the grey side of the ECL Card. Select the grey
side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Use the minus/plus buttons to adjust the
setting(s).
In some displays more than one setting or
value can be adjusted. Use the shift button to
switch between the options. The chosen value
flashes in the range indicator.
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
Line
indicator
Settings to
be adjusted
Value in
range indicator
094
2
ON
ON
1
0
Basic set-up
Basic set-up
The grey
side of the
ECL Card
19
Manual control - Line B
Go to line B.
Shift to manual mode
Select the unit you want to control. The
selected unit symbol flashes.
Burner and pump start and
stop when the relevant button is pressed.
ON
ON
1
Monitoring temperatures
and system units - Line B
18
When the burner and the circulation pump are operating, it
is indicated as ON below the symbols.
If a sensor is not mounted or is disconnected, the display
will indicate it as
- -.
If the sensor is short-circuited, the display will indicate it as
- - - .
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Go to line B.
5
ON
036
B
ON
1
Controlled units
Return temperature
Flow
temperature
State indicator
Relationship between temperature and ohmic value
-10°C 961 Ohm
0°C 1000 Ohm
10°C 1039 Ohm
20°C 1078 Ohm
30°C 1117 Ohm
40°C 1156 Ohm
50°C 1195 Ohm
60°C 1234 Ohm
70°C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Controlled
units
Controller mode
5
ON
036
B
ON
1
State indicator
Push the shift button to see:
- the calculated flow temperature
- the return temperature set point
Shift away from manual mode
Basic set-up
Basic set-up
Go to line B.
The grey
side of the
ECL Card
The grey
side of the
ECL Card
-20 -10 0 10 20-30
10
20
30
40
50
60
70
80
90
1,4 1,8
1,0
0,6
0,2
2,2
o
C
o
C
Setting the heat curve -
Line C
20a
Go to line C.
The symbol for the slope of the heat curve will
flash.
ON
8
C
1
ON
1
0
Slope
Displacement
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Setting range Factory setting
-9 ... +9 0
Parallel displacement
Make your adjustment
Setting range Factory setting
0.2 ... 3.4 1.8
Slope
Floor heating systems
This controller is factory set for radiator systems which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your system type.
Setting range Typical setting
0.2 ... 3.4 1.0
Setting range Typical setting
-9 ... +9 0
Basic set-up
Basic set-up
Slope
Parallel displacement
20b
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Flow temperature limits -
Line 2
22
Setting range Factory setting
10 ... 110 °C min. 40 °C max. 90 °C
2 Boiler temperature min., max. limits
Go to line 2.
094
2
ON
ON
1
0
Max. flow
temperature
Min. flow
tempera-
ture
Temperature
range for flow
temperature
The left end of the range indicator flashes.
Adjust the min. limit of your heating system.
Select the max. limit. The right end of the range
indicator will flash.
Adjust the max. limit.
Heating cut-out - Line 1
21
Setting range Factory setting
10 ... 30 °C 18 °C
ON
8
1
1
ON
1
1 Limit for heating cut-out
Go to line 1.
Set the outdoor temperature limit at which you
want the heating system to stop.
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated T
out symbolises the heat stored in the
building.
18 ˚C
Temp
Actual T
out
Accumulated T
out
Time
Heating Heating off Heating
Basic set-up
Basic set-up
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Room temperature
influence - Line 3
23a
The room sensor in the reference room
registers the difference between the desired and
the actual room temperature. The flow
temperature reference will be corrected to
eliminate this difference.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
Set a positive value for min. influence and a
negative value for max. influence.
+
_
Influence
Min. limitation
Set
T
ROOM
Max. limitation
This section is only relevant if you have installed a room
sensor. There are two basic principles for control of the
room temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a
max. limitation of the room temperature. The controller will
allow for free heat gains, i.e. solar radiation or heat from a
fire place, etc.
The max. influence determines how much the
room temperature should influence the flow
temperature.
Go to line 3.
Select the max. influence.
The bar below the range indicator flashes in the
right side of the display.
Adjust the max. influence.
+
_
Influence
Max. limitation
T
ROOM
Setting range Factory setting
0 ... 99/-99 ... 0 min. 0 max. -40
3 Room temperature influence
Set
Example
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x
-40 x 0.1 x H = -14.4 degrees.
Example
The actual room temperature is 2 degrees too low.
The influence at max. limitation (right corner of the display) is
set to
20.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x 0.1 x H = 7.2 degrees.
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-35.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x 0.1 x H = -12.6 degrees.
ON
-040
3
ON
1
Min.
influence
Max.
influence
Basic set-up
Basic set-up
23b
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Go to line 4.
The burner is switched on and off to maintain the
desired mean boiler temperature. Set the difference
between cut-in and cut-out temperature.
Boiler control - Line 4
24
Setting range Factory setting
OFF/1 ... 50 OFF
4 Boiler temperature difference
OFF:
1 ... 50:
Basic set-up
Basic set-up
The grey
side of the
ECL Card
The boiler temperature difference is set
automatically according to the
momentary load of the boiler and the
temperature conditions in the heating
system.
The boiler temperature difference is set
manually to a fixed value according to
the boiler manufactorers specification.
Adapting the ECL Comfort controller to the heating
system
29b
Check list
Turn the ECL Card so that the grey side faces
you.
Select basic setup and extended service
settings.
Set the time and the date (Line A)
See section 17.
Check all settings on the grey side of the
ECL Card.
See sections
20 to 24.
If your heating system differs from the diagram
shown on the overleaf of the cover, you should
check and perhaps alter the service parameters.
Please pay special attention to line 35 and 36
.
29a
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12 or 13.
Check that burner and pumps are connected to
the correct terminals.
See section 12 or 13.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and push
, if necessary.
Select manual operation in the controller mode.
See section 2
in the Users Guide.
Check that the temperatures shown in display
A and B match the actual sensors.
See section 1
in the Users Guide.
Control & overviews
Control & overviews
Service parameters
31
10 Choice of time control unit
0 ... 5 0
11 Reduced temperature dependent
on outdoor temperature
OFF/-29... +10
0
C -15
0
C
12 Boost
0 ... 99% 0%
14 Optimising time constant
OFF/10...59 OFF
15 Adaptive function of
room temperature
OFF/1 ... 30 OFF
17 Temperature reference feedback
OFF/1 .. 20 OFF
20 Optimisation based on room /
outdoor temperature
ON / OFF OFF
21 Total stop
ON / OFF OFF
22 Pump motion
ON / OFF ON
25 Pump stop in the boiler circuit
ON / OFF OFF
27 Boiler protection
ON / OFF OFF
30 Limitation of return temperature
10 ... 110
0
C 40
0
C
35 Return temperature influence - max.
+/- 0 ... 9.9 0
36 Return temperature influence - min.
+/- 0 ... 9.9 +2
37 Adaptive function of return limitation
OFF / 1 ... 50 25
71 Minimum ON-time of the burner
0 ... 9 min 1 min
141 Override input selection
OFF/1 ... 4 OFF
196 Service pin LON
ON/OFF OFF
197 LON reset
ON/OFF ON
198 Summer time change
ON/OFF ON
199 Slave address
0 ... 9 15
Grey ECL Card lines 10 - 199
Line Setting range Factory setting Your setting
°C
%
°C
min
ECL Card settings
30
Heat curve - Slope
0.2 ... 3.4 1.8
Set the slope of the heat curve,
see section 20.
Heat curve - Parallel displacement
-9 ... +9 0 K
Set the parallel displacement of the heat
curve,
see section 20.
1
Limit for heating cut-out
10 ... 30 °C 18 °C
Saves energy by stopping the heating
system when the outdoor temperature
gets above a certain limit,
see section 21.
2
Boiler temperature min.-/max. limits
10 ... 110 °C min. 40, max. 90 °C
The limits of min. - and max. flow
temperature,
see section 22.
3
Room temperature influence
0 ... 99/-99 ... 0 min. 0, max. -40
The room temperatures influence on the
flow temperature control,
see section 23.
4
Boiler temperature difference
OFF/1 ... 50 OFF
Set the difference between the cut-in and
cut-out temperature.
Setting range Factory setting Your settings
A Time and date
B System information
C Heat curve
See sections 16 & 17
See sections 18 & 19
See section 20
Control & overviews
Control & overviews
Extended Service
32b
Service parameters
10-11
ECL Comfort controller - day plan circuit I
Room panel ECA 60 or remote control
ECA 61 on address A
Room panel ECA 60 or remote control
ECA 61 on address B
Choose between
0
1
2
-29 to +10 °C
The setting of the reduced temperature
depends on the outdoor temperature, when the
outdoor temperature is higher than the set limit.
The lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set set limit, there is no
temperature reduction.
OFF: The reduced temperature setting will be
constant at all outdoor temperatures.
32a
Adjusting the service
parameters
In addition to the settings in lines 1 to 7 on the grey
side of the ECL Card, there is an extended service
menu from line 10 and onwards.
Push repeatedly to reach the lines numbered
10 and onwards.
Line
number
Value
Range
indicator
01
0
Now you can move to any line of your choice.
Set the parameter value.
When you have entered all your personal settings, turn
the ECL Card over so that the yellow side faces you.
Select daily use settings
Dedicates the unit for the time control of the comfort and
reduced temperature periods
Setting range Factory setting
0 ... 5 0
10 Choice of time control unit
The limit of the outdoor temperature at which the reduced
temperature setting is switched off.
Setting range Factory setting
OFF / -29 ... +10 °C -15 °C
11 Reduced temperature dependent on outdoor
temperature
100%
0%
-20 -10-29 0 10 2015
Reduction
Outdoor
temp.
o
C
Extended service
Extended service
The grey
side of the
ECL Card
The adaptive function will eliminate the difference between
the required and actual room temperature by integrating
the difference and adjusting the reference for the flow
temperature.
32d
Service parameters
14-15
OFF: The adaptive function is cancelled.
1: The desired temperature is adapted
quickly.
30: The desired temperature is adapted
slowly.
In order to shorten the heating-up period after a reduced
temperature period, the flow temperature can be increased
temporarily.
If a room sensor is installed the boost stops, when the
optimisation period is over or the room temperature has
been reached.
32c
Service parameter
12
Set the percentage at which you want the flow
temperature to be changed temporarily.
Shortens the heating-up period by increasing the flow
temperature by the percentage you set.
Setting range Factory setting
0 ... 99% 0%
12 Boost
Optimises the start and stop times for the reduced temperature
period to obtain the best comfort at the lowest energy
consumption.
Setting range Factory setting
OFF / 10 ... 59 OFF
14 Optimising time constant
Controls how fast the room temperature adapts to the
desired temperature.
Setting range Factory setting
OFF / 1 ... 30 OFF
15 Adaptive function of room temperature
No optimisation. The heating starts and stops at
the times set in the week plan.
OFF:
41
25
Dimensioning temperature: The lowest outdoor
temperature at which the heating system can secure
the desired room temperature.
Adjust the optimising time constant. The value
consists of a number of two digits. You can select
the following values:
10, 11, ..... 59.
The two digits have the following meaning:
1. digit (system type and heat accumulation of
the building)
1
2
3
4
5
light
medium
heavy
medium
heavy
1. digit Heat accumulation System type
of the building
Radiator
system
Floor heating
system
2. digit (capacity of the heating system)
2. digit Dimensioning Capacity
temperature
large
.
.
normal
.
.
small
-50 °C
.
.
-25 °C
.
.
-05°C
0
.
.
5
.
.
9
Extended service
Extended service
The grey
side of the
ECL Card
The grey
side of the
ECL Card
32f
Service parameter
21
Select total stop function
ON: Total stop function is ON. At total stop the
flow temperature reference is lowered to
10 °C and the minimum setting of the flow
temperature limit of line 2 (see section
22) is overruled in the reduced
temperature period.
T
ref
T
min
10 °C
Time
OFF: No total stop.
Ref. temp.
T
ref
T
min
10 °C
Time
32e
Service parameters
17-20
Select calculation method:
Calculation based on the room
temperature (only if a room sensor is
used).
Calculation based on the outdoor
temperature. Use this setting if you have
no room sensor.
ON:
OFF:
Setting range Factory setting
ON / OFF OFF
20 Optimisation based on room/outdoor
temperature
The optimised start and stop time calculation can be based
on either the room temperature or on the outdoor temperature.
Ref. temp.
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop of the reduced
temperature period.
21 Total stop
The temperature reference in heating circuit I can be influenced
by another external reference.
OFF: The temperature reference in circuit I is
not influenced by any other controller.
1 - 20: The temperature reference in circuit I will
always at least correspond with the value
of the set number + the highest
temperature reference degree of an
external controller.
T
ref
(l)
T
ref
(ll)
Setting line 17
Time
°C
Setting range Factory setting
OFF / 1 ... 20 OFF
17 Temperature reference feedback
This function is used if circuit I is the main supply for other
mixing circuits.
Extended service
Extended service
The grey
side of the
ECL Card
The grey
side of the
ECL Card
When the boiler is heated up from a temperature below
the set minimum limit, ie. the shift from reduced temperature
to comfort temperature, the heating up period must be as
short as possible to reduce the time of possible
condensation in the furnace.
This prevention is obtained by allowing the smallest
possible removal of heat from the boiler (the circulation
pump is stopped).
When the minimum temperature limit +4 K is reached, the
circulation pump starts again. If the temperature decreases
below the minimum temperature, the pump is stopped
again.
These conditions apply for high thermic capacity boilers.
Service parameter
27
The circulation pump can be stopped to prevent condensation
in the boiler during heating up.
Setting range Factory setting
ON / OFF OFF
27 Boiler protection
32g
Service parameters
22-25
The boiler circuit pump can be stopped at certain
conditions during comfort and reduced temperature
periods.
ON: The circulation pump is controlled
according to extended conditions;
Pump is OFF when Troom. is > Troom.set
+ 1K and Tref. < Tmin. This means that
the room temperature will not be too
high even if Tref. is limited by the
minimum setting of the boiler circuit.
OFF: The circulation pump is controlled
according to normal conditions.
Normally the boiler circuit pump is ON when the boiler
temperature is >20 °C or the outdoor temperature is <2 °C.
Setting range Factory setting
ON / OFF OFF
25 Pump stop in the boiler circuit
Set the anti-blocking function to ON or OFF.
ON:
OFF:
The pump is switched on for 1minute
every third day.
The pump motion is switched off.
Exercises the pump to avoid blocking in periods without heat
demand.
Setting range Factory setting
ON / OFF ON
22 Pump motion
Extended service
Extended service
The pump is stopped until the set
minimum temperature in the boiler is
reached.
ON:
OFF:
The pump is controlled according to the
normal conditions. (Pump is ON when Tref.
is above 20 °C).
0
C
Time
T
min
10
On
Off
32h
The grey
side of the
ECL Card
The grey
side of the
ECL Card
/