I SECTION 2: SECURING HEATER TO THE WALL
SEE DIAGRAM 2
I
4
0
I
I SECTION 3: SAUNA ROCKS
SECTION 5: TEMPERATURE SENSOR
SEE DIAGRAM 3 & 4
I
pMEREC
INSTALLATION AND SERVICE INSTRUCTIONS
page 3
The sauna heater comes completely assembled.
After removing heater from the carton.
7emove
the heater from its mounting bracket. Attach the
bracket supplied to the wall so that the bottom of
the heater is 12 inches from the floor and the too
of the heater is a least 40 inches belowthe interior
This heater must not be operated unless the rock
compartment in thetop of the heater is filled with
the igneous rocks that are furnished with the
heater. They should be put an the heater so that
the air is free to travel around them. Do not pack
too tightly.
All wiring must be accomplished by a licensed
electrical contractor. Referto the Heater Specifi-
cation Chartto determine the wire size and circuit
protection required. The sauna system MUST BE
SUPPLIED WITH A NEUTRALAND A GROUND as
440
ler NEC, oras required by local codes. Grounding
Feed the 25 foot single pin RCA cable from the
control to the sensor location ( plus 24' of slack).
It will be necessary to drill 1/2" holes to string the
cable through the studs or ceiling joist. Then,
using the sensor template supplied with the
heater packet, locate and drill the 1/2' hole and
the 1/8' holes as shown on the template into the
finished wall. It is required that the sensor be
mounted to the wall above the heater 2' down
ceiling and not less than 4 inches from adjacent
wood surfaces as indicated on the Heater Spec-
ification Chart. Do not install benches overtop of
heater. ( See Diagram 2 for attaching bracket and
heater to wall.)
During the first operation, the rocks should be
heated for two hours at maximum temperature
with no one in the sauna room. This will allow any
concealed moisture to be evaporated. If not, the
moisture could cause the rocks to crack and
possibly project fragments.
and neutral terminals are provided in the wiring
compartment of each heater for power supply
and room light circuit. Complete the wiring
through the knockouts provided and according
to the proper wiring diagram 5 or 6.
from the ceiling. Screwthe 3/4' screws provided
into the 1/8' pilot holes until all but 3/8' of the
screw is in the wall. The sensor housing should
fit snug to the wall when slipped on. After plug-
ging the sensor to the sensor cable, tape the
connection tightly together and slip any excess
cable and the connection into the wail cavity.
Attach the sensor to the wall using the keyhoie
slots in the back of the sensor housing. See
Diagrams 3 and 4.
WARNING
Do not locate benches over heater.
Minimum height of ceiling above
heater 40".
Do not construct sauna
roam
so as
to restrict airflow through the
bottom of the heater.
Minimum clearance from heaterto
wooden surfaces (benches, side
walls, heater fence etc.) 4 inches.
Mounting brackets supplied.
Provides properciearance from
wall behind heater.
Rock preheat required. Although
the rocks are specially selected for
use with this sauna heater,
concealed moisture could cause
the rock to crack and project
fragments causing potential injury
hazard when the rocks are heated.
The rocks must be preheated on
the sauna heater for two hours at
maximum temperature with no one
in the sauna room.
Packing the rocks too tightly may
cause the heater limit switch to
trip.
Use only capper wire of the size
and type indicated in the wiring
diagrams and the
temperature rating indicated on the
heater junction box.
All heaters, controls and contactors
must be grounded per NEC to
prevent electrical shock in case of
unit failure.
Do not cut mutilate or place undue
tension on control cables. Doing so
will void warranty and may cause
damage to the control system.
•
SECTION 4: ELECTRICAL WIRING
SEE DIAGRAM 5 & 5
4211-22 12/97