VMA120012
Detailed Procedures
Investigating Occupant Hot/Cold Complaints
Zone temperature control problems, which are usually reported as
occupant hot/cold complaints, have causes ranging from the building
or mechanical system to the control components. The following guide
helps you locate the cause of zone temperature control problems with
pressure independent VAV terminals.
Table 2: Occupant Hot/Cold Complaints
Symptom Cause Action
Occupant Hot Complaints
Zone setpoint too high Lower the common setpoint, or
calibrate remote setpoint potentiometer.
Controller not in Occupied
mode
Check to see if mode is commanded by
network features.
Setpoint offset Set Occupied setpoint offset to one degree
or less for greatest comfort.
Occupant Hot Complaints
or EWMA Space Less
than -1°C (-2°F)
Insufficient airflow Check terminal box inlet obstructions.
Airflow not in control (Indicated
by nvoEwmaFlow greater than
m
2
Box Area * 200 [l/s] or
sq ft Box Area * 40 [cfm])
Tighten damper shaft coupling, or
increase minimum flow setpoint, or
reconnect duct, or look for a
differential pressure sensing problem.
Reheat and or supplemental
heat stuck on, valve stuck open
or wrong stroke time/range
Verify heating device operation.
Verify reverse or direct acting valves.
VAV box inlet air too warm
With the box at maximum cooling flow, verify
diffuser air temperature is 10 to 15°C
(50 to 60°F). Warmer air temperature may
indicate supply air temperature problem,
stuck reheat valve or box series fan adjusted
to flow higher than maximum cooling.
Zoning problem - VAV box
serves multiple rooms/areas
See the Establish Zones section in the
Variable Air Volume Modular Assembly
(VMA) 1200 Series Overview and
Engineering Guidelines Technical Bulletin
(LIT-1162350).
Zone sensor placement
resulting in non-representative
temperature sensed
See the Room Sensor Placement section in
the Variable Air Volume Modular Assembly
(VMA) 1200 Series Overview and
Engineering Guidelines Technical Bulletin
(LIT-1162350).
Zone sensor wiring crossed Rewire VMA to appropriate sensor.
VAV outlet duct crossed Change duct routing or cross sensor wiring.
Cooling load exceeds design
due to change in use, added
equipment, or people
Investigate possibility of increasing the Max
Cooling Flow setpoint. (How much greater is
present load than design? Is sufficient
supply air available? Is box large enough?)
Continued on next page . . .