Johnson Controls VMA18 Series Installation guide

Type
Installation guide

This manual is also suitable for

VMA1826/1832 VAV Controller Installation Guide
Applications
The VMA18 Series programmable VAV box
controllers are intended for use as functional
replacements for the VMA1410, VMA1415, VMA1420,
and the VMA1440 controllers.
VMA1826 controllers are well-suited for commercial
zoning applications and can be used for pressure
dependent VAV box applications where no
differential pressure tranduser (DPT) is required.
Note: At Controller Configuration Tool (CCT)
13.0 or later, using Release Mode 10.1, VMA18
Series controllers can be configured as either
N2 devices or as standard BACnet
®
MS/TP
devices. This ability provides a potential cost-
effective protocol upgrade path for existing
customers and should be considered when you
install the controller.
Important: When you receive a VMA18 Series
controller from the factory or upgrade the
firmware or main code, the controller defaults
to using the MS/TP communications protocol.
The Load Summary screen of CCT shows the
connection as Wired Field Bus, indicating that
the MS/TP protocol is in use. If you have an N2
application, the Load Summary screen indicates
that you need to switch the communications
protocol to N2.
These VMA controllers feature an integral digital
pressure sensor, a damper actuator, and a 32-bit
microprocessor. The controller's small package size
facilitates quick field installation and efficient use
of space for field replacements, while still enabling
precision control performance.
Note: Connecting an IOM to the VMA via the SA
Bus connection is not supported.
For information about sensor compatibility and
replacement, see Sensor replacement and reuse
scenarios.
North American emissions
compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment
is operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Observe these guidelines when installing a VMA18
Series controller:
Transport the VMA controller in the original
container to minimize vibration and shock
damage to the VMA controller.
Do not drop the VMA controller or subject it to
physical shock.
Parts included
One VMA18 Series controller with removable N2/
FC bus terminal block
One installation instructions sheet
Two 6.35 mm x 6.35 mm (1/4 in. x 1/4 in. ) brass
fittings
*2410143373K*
Part No. 24-10143-373 Rev. K
2019-10-18
(barcode for factory use only)
MS-VMA1826-x, MS-VMA1832-x
One self-drilling No. 10 x 25 mm (1 in.) screw
Two 12-in. (30.48 cm.) pieces of flexible tubing
One controller/sensor Y cable adapter
One 8-pin to 6-pin single-socket cable adapter
Note: Remove the cap plug from the TSTAT port
of the controller and save for future use. The
cap plug is used on existing sensor ports that
are no longer used.
Materials and special tools needed
Note: You may not require all the materials
listed for your controller installation.
Several 6 mm (1/4 in.) female spade terminals
for input and output wiring and crimping tool or
spade mounted terminal blocks
Small straight-blade screwdriver for securing
wires in the terminal blocks
8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point
socket to tighten the square coupler bolt
Several shims or washers to mount the VMA
Power screwdriver, 100 mm (4 in.) extension
socket, punch, drill, and 3.5 mm (9/64 in.) drill bits
to mount the VMA
Pliers to open and close the damper
Required length of 3.97 mm (5/32 in.) ID
pneumatic tubing and barbed fittings
Physical features
Figure 1: VMA18 Series Controller Wiring Terminations and Physical Features
Table 1: VMA18 Series Controller feature callout numbers and descriptions
Physical features: description and references
1 24 VAC, Class 2 Supply Power Spade Terminals (see Supply power spade terminals)
2 Device Address DIP Switch Block (see Setting the device address)
VMA1826/1832 VAV Controller Installation Guide2
Table 1: VMA18 Series Controller feature callout numbers and descriptions
Physical features: description and references
3 Binary Outputs, 24 VAC Triacs (see Table 4)
4 Configurable Outputs: Voltage Analog Output (0–10 VDC) and Binary Output (24 VAC Triac) (see Table 4)
5
Dual Port Fitting (see Figure 1)
Not included in the VMA1826 model.
6 Manual Override Switch (see Mounting)
7 Controller Coupler (see Mounting)
8 Coupler Bolt (see Mounting)
9
Universal Input: Voltage Analog Input (0–10 VDC)
Resistive Analog Inputs (0–600k ohm) (see Table 4):
0–2k Potentiometer
RTD: 1k Nickel, 1k Platinum, or A99B SI
NTC: 10K Type L (10K JCI Type II is equivalent to Type L) or 2.252K Type II
Dry Contact Binary Input
10 N2/FC Bus Pluggable Screw Terminal Block (see N2/FC bus terminal block)
11 EOL (End-of-Line) Switch (see Setting the EOL switch)
12 SA Bus Spade Terminals (see SA bus spade lugs)
13 TSTAT Modular Port: RJ-45 8-Pin Modular Jack (see Modular port)
14 Captive Spacer and Screw (see Figure 1)
15 LED Status Indicators (see Table 8)
Mounting
Observe these guidelines when mounting a VMA:
Important: When the air supply to the VAV
box is below 10°C (50°F), make sure that any
condensation on the VAV box, particularly on
the damper shaft, does not enter the VMA
electronics. Mount the VMA vertically above the
damper shaft to allow any shaft condensation
to fall away from the VMA. Additional measures
may be required in some installations.
Ensure the mounting surface can support the
VMA and any user-supplied enclosure.
Mount the VMA on a hard, even surface whenever
possible.
Use shims or washers to mount the VMA securely
and evenly on the mounting surface.
Mount the VMA in an area free of corrosive
vapors that matches the ambient conditions
specified in the VMA1832 Technical Specifications
section.
Provide sufficient space around the VMA for cable
and wire connections and adequate ventilation
through the controller (50 mm [2 in.] minimum
on the top, bottom, sides, and front of the
controllers).
Do not mount the VMA in areas where
electromagnetic emissions from other
devices or wiring can interfere with controller
communication.
Avoid mounting the VMA on surfaces with
excessive vibration.
Because the VMA controller is smaller than the
VMA1410, VMA1415, VMA1420, and the VMA1440
controllers, we recommend plugging the unused
open hole with the screw from the original VMA14
mounting when using the VMA18 to replace a
VMA14 Series controller.
On panel or enclosure mount applications, observe
these additional guidelines:
Do not install the VMA in an airtight enclosure.
Mount the VMA so that the enclosure walls do not
obstruct cover removal or ventilation through the
controller.
Mount the VMA so that the power transformer
and other devices do not radiate excessive heat to
the controller.
VMA1826/1832 VAV Controller Installation Guide 3
To mount the VMA18 Series controller, complete the
following steps:
1. Place the VMA18 Series controller in the proper
mounting position on the damper shaft so that
the wiring connections are easily accessible.
Note: The line from the captive spacer and
screw through the center of the damper
shaft must be either horizontal or vertical,
and the wall plate must be wall-mounted
to comply with UL requirements. See the
following figure for possible mounting
positions.
Figure 2: Possible VMA18 Series Controller
Mounting Positions
Make sure the VMA controller base is parallel
to the VAV box (perpendicular to the damper
shaft). If needed, use a spacer to offset tipping
of the VMA controller caused by the shaft
bushings.
Note: Using the alignment marks to center
the captive spacer ensures sufficient
VMA18 controller movement in either
direction.
2. Secure the self-drilling No. 10 screw through
the shoulder washer (Figure 1) with a power
screwdriver and 100 mm (4 in.) extension
socket. Otherwise, use a punch to mark the
position of the shoulder washer, and then drill a
hole into the VAV box using a 3.5 mm (9/64 in.)
drill bit. Insert the mounting screw and tighten
against the washer.
Note: The mounting screw for the VMA
controller does not use the same hole
as the screw for the VMA1410, VMA1415,
VMA1420, and the VMA1440 controller.
We recommend plugging the unused
open hole with the screw from the original
VMA14 mounting when using the VMA18
to replace a VMA14 Series controller.
Important: Do not overtighten the screws,
or the threads may strip. If mounting to
the VAV box, make sure the screws do not
interfere with damper blade movement.
3. Locate the damper position using the typical
marking on the end of the damper shaft. See
the following figure.
Figure 3: Typical damper end shaft icons
4. Note the direction, clockwise (CW) or
counterclockwise (CCW), required to close the
damper. Grasp the damper shaft firmly with
pliers, and either manually close the damper
(for 90° boxes) or manually open the damper
(for 45° or 60° boxes).
5. Push down and hold the Manual Override
button (Figure 1) and turn the VMA controller
coupler until it contacts the mechanical end-
stop at either the fully closed (90° boxes) or
fully open (45° and 60° boxes) position.
6. If the damper for a 90° box closes CCW, rotate
the coupler to the CCW mechanical limit. If the
damper for a 90° box closes CW, rotate the
coupler to the CW mechanical limit. The open
end-stop is automatically set for 90° boxes. For
45° and 60° boxes, hard stops must be provided
at both fully closed and fully open damper
positions. By installing the VMA controller at the
fully open position, the VMA controller provides
the open stop for 45° and 60° boxes. The closed
damper seal provides the fully closed stop.
Important: The integrated actuator has
a stroke time of 60 seconds for 90° of
travel. The stroke time is the amount of
time (in seconds) that it takes the actuator
to move from the fully closed to fully
opened position or from fully open to fully
closed position. For proper operation, the
actuator stroke time must be configured
in the CCT application based on the actual
time it takes the actuator to drive the
damper. The default setting is 60 seconds
VMA1826/1832 VAV Controller Installation Guide4
(for 90° VAV boxes). For 45° and 60° VAV
boxes, the actuator stroke time must be
adjusted. Refer to the Controller Tool Help
(LIT-12011147) for instructions on setting
the actuator stroke time in the application.
7. Tighten the square coupler bolt to the shaft
using an 8 mm (5/16 in.) wrench or 10 mm (3/8
in.) 12-point socket. Tighten to 10.5 to 11.5 N·m
(95 to 105 lb·in).
8. Loop the pneumatic tubing to include a trap for
condensation. If needed, use the included brass
fittings and attach the included pieces of tubing
to the tubing of the VMA controller. Attach the
tubing from the VMA controller to the dual port
fitting on the VMA controller and the other ends
of the tubing to the pressure transducer in the
VAV box application (Figure 1). The VMA1826
does not come with the tubing pieces.
Note: The VMA uses a digital non-flow
pressure sensor with bidirectional flow
operation, which allows the high- and
low-pressure DP tube connections to
be made to either barbed fitting on the
VMA controller. You do not need to make
a specific high- or low-side connection
when you attach the tubing to the barbed
fittings on the VMA.
9. Push the manual release button, and turn the
actuator coupling manually to ensure that the
actuator can rotate from full-closed to full-open
positions without binding.
10. Complete the mounting by rotating the damper
to the full-open position.
CAUTION
Risk of Property Damage
Rotate the damper to the full-open position before
starting the air handler. Failure to rotate the damper to
the full-open position may result in damage to the VAV
box or ductwork when the air handler is started.
ATTENTION
Mise En Garde: Risque de dégâts matériels
Faire pivoter le registre pour le placer en position
d'ouverture complète avant de démarrer l'unité de
traitement d'air. Le non-respect de cette directive
risque d'endommager le caisson de l'unité à volume
d'air variable (VAV) ou le réseau de conduites au dé-
marrage de l'unité de traitement d'air.
Wiring
WARNING
Risk of Electric Shock
Disconnect the power supply before making electrical
connections to avoid electric shock.
AVERTISSEMENT
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation avant de réaliser tout rac-
cordement électrique afin d'éviter tout risque de
décharge
Important: Do not connect supply power
to the controller before finishing wiring and
checking all wiring connections. Short circuits
or improperly connected wires can result
in damage to the controller and void any
warranty.
Important: Do not exceed the controller
electrical ratings. Exceeding controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
Important: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
VMA1826/1832 VAV Controller Installation Guide 5
For detailed information on configuring and wiring
an N2 Bus, refer to the N2 Communications Bus
Technical Bulletin (LIT-636018).
VMA terminals and bus ports
See Figure 1 for input and output terminal and bus
port locations on the VMA18 Series controllers.
Observe the following guidelines when wiring a
VMA18 controller.
Input and Output terminals
The input spade terminals are located on the side
of the VMA near the N2/FC Bus terminal block. The
output spade terminals are located on the opposite
side of the controller near the power supply spade
terminals. See Table 4 for more information.
N2/FC bus terminal block
The N2/FC Bus terminal block is a blue, removable,
4-terminal plug that fits into a board-mounted jack.
Wire the removable N2/FC Bus terminal block plugs
on the VMA and other field controllers in a daisy-
chain configuration using 3-wire twisted, shielded
cable as shown in Figure 4. See Table 5 and Table 6
for more information.
Figure 4: N2/FC bus terminal block wiring
Note: The Shield terminal (SHLD) on the N2/FC
Bus terminal block is isolated and can be used
to connect the cable shields on the bus (Figure
4).
SA bus spade lugs
Wire the SA Bus spade lugs on the VMA and other
SA Bus devices in a daisy-chain configuration using
4-wire twisted, shielded cable as shown in Figure 5.
See Table 6 for more information.
Figure 5: SA bus spade lug wiring
Note: Connecting an IOM to the VMA by using
the SA Bus connection is not supported.
Modular port
The modular (TSTAT) port on the face of the VMA
(Figure 1) is an RJ-45, 8-position modular jack used
to connect your new or existing sensor to the VMA
using one of the two included adapters. Refer to
the Sensor Replacement section in the N2 VMA
Application Note (LIT-12011829).
Figure 6: Pin number assignments for the
modular port on VMA18 Controllers
Supply power spade terminals
Wire the 24 VAC supply power wires from the
transformer to the HOT and COM terminals on the
VMA1826/1832 VAV Controller Installation Guide6
spade terminal as shown in Figure 7. See Table 6 for
more information.
Figure 7: 24 VAC Supply Power Spade Terminal
Wiring
Important:
The supply power terminal block on the
VMA18 is a two-position spade lug (Figure
7). Exercise caution while rewiring the power
plug when replacing an existing controller.
Stray wire strands may make contact and
cause a short circuit across the 24 VAC power
supply.
To maintain proper phasing when replacing
the existing VMA14xx controller with the
VMA18 controller, connect the power wire
from 24 VAC: 1 terminal on the existing
controller to the HOT power terminal on
the VMA18. Also connect the power wire
from the 24 VAC: 2 terminal on the existing
controller to the COM power terminal on the
VMA18 controller.
The supply power wire colors may be different on
transformers from other manufacturers. Refer to
the transformer manufacturer’s instructions and
the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to
the VMA and all other network devices so that
transformer phasing is uniform across the
network devices. Powering network devices
with uniform 24 VAC supply power phasing
reduces noise, interference, and ground loop
problems. The VMA does not require an earth
ground connection. However, when grounding
the secondary of the 24 VAC transformer
is required, only one connection to ground
should be made near the transformer.
Figure 8: Transformer Grounding
CAUTION
Risk of Personal Injury and Property Damage
Improper wiring of this terminal may cause a short cir-
cuit across the 24 VAC power supply on -1 models.
ATTENTION
Risque de blessure et dégâts matériels
Improper wiring of this terminal may cause a short cir-
cuit across the 24 VAC power supply on -1 models.
To wire the VMA18 Series controller, complete the
following steps:
1. Terminate wiring per engineering drawings.
2. Wire network sensors and other devices to the
VMA's SA Bus.
3. Wire the N2/FC Bus in a daisy chain (see Table
6).
4. Ensure that the VMA’s device address DIP
switches are set to the appropriate device
address. (See Setting the device address.)
5. Connect the VMA controller to 24 VAC, Class 2
power.
Refer to the N2 VMA Application Note (LIT-12011829)
for more information about replacing an existing
controller with an VMA18 controller.
VMA1826/1832 VAV Controller Installation Guide 7
VMA terminal functions, ratings,
requirements, and wiring guidelines
Input and Output wiring guidelines
Table 4 provides information about the functions,
ratings, and requirements for the VMA input and
output terminals, and Table 5 provides guidelines
for wire sizes and cable lengths.
In addition to the wiring guidelines in Table 4,
observe these guidelines when wiring VMA inputs
and outputs:
Run all low-voltage wiring and cables separate
from high-voltage wiring.
All input and output cables, regardless of wire
size or number of wires, should consist of twisted,
insulated, and stranded copper wires.
Shielded cable is not required for input or output
cables.
Shielded is recommended for input and output
cables that are exposed to high electromagnetic
or radio frequency noise.
Cable runs of less than 30 m (100 ft) typically do
not require an offset in the input/output software
setup. Cable runs over 30 m (100 ft) may require
an offset in the input/output software setup.
Maximum cable length versus load
current
Use Figure 13 to estimate the maximum cable
length relative to the wire size and the load current
(in mA) when wiring inputs and outputs.
N2/FC and SA bus and supply power
wiring guidelines
Table 6 provides information about terminal block
functions, ratings, and requirements.
Table 6 also provides wire size, cable type, and
cable length guidelines for wiring the VMA
communication buses and supply power.
In addition to the guidelines in Table 6, observe
these guidelines when wiring the SA and N2/FC
Buses and supply power:
Run all low-voltage wiring and cables separate
from high-voltage wiring.
All N2/FC and SA Bus cables, regardless of wire
size, should be twisted, insulated, stranded
copper wire.
Shielded cable is strongly recommended for all
N2/FC and SA Bus cables.
Refer to the N2 Communications Bus Technical
Bulletin (LIT-636018) for detailed information
regarding wire size and cable length
requirements for the N2/FC and SA buses.
Termination diagrams
A set of Johnson Controls
®
termination diagrams
provides details for wiring inputs and outputs to
the VMA18 Series controllers. See the figures in this
section for the applicable termination diagrams.
Table 2: Termination details
Type of field device
Type of Input/
Output
Termination diagrams
Voltage Input -
External Source
UI
VMA1826/1832 VAV Controller Installation Guide8
Table 2: Termination details
Type of field device
Type of Input/
Output
Termination diagrams
Voltage Input - Internal
Source
UI
Voltage Input (Self-
Powered)
UI
Temperature Sensor UI
Dry Contact UI
0–10 VDC Output to
Actuator (Internal
Source)
CO
0–10 VDC Output to
Actuator (External
Source)
CO
VMA1826/1832 VAV Controller Installation Guide 9
Table 2: Termination details
Type of field device
Type of Input/
Output
Termination diagrams
24 VAC Triac Output
(Switch Low, External
Source)
CO
Note: Only applies to CO4 and CO5.
Incremental Control to
Actuator (Switch Low,
External Source)
CO
Note: Applies to CO4 and CO5.
Analog Output
(Voltage)
CO
24 VAC Binary Output
(Switch Low, Internally
Sourced)
BO
Note: Applies to BO1, BO2, and BO3.
Incremental Control to
Actuator (Switch Low,
Internally Sourced)
BO
Note: Only applies to BO1, BO2, and BO3.
Temperature Sensor
with Modular Jack
SA Bus
Note: The bottom jack (J2) on the TE-700 and TE-6x00 Series Sensors are not usable as a
zone bus or an SAB connection.
VMA1826/1832 VAV Controller Installation Guide10
Table 2: Termination details
Type of field device
Type of Input/
Output
Termination diagrams
Network Stat with
Terminals Addressable
SA Bus
Network Stat with
Terminals (Fixed
Address = 199)
SA Bus
VMA replacement wiring diagram
Consider the following information when replacing
a VMA1410, VMA1415, VMA1420, and the VMA1440
controller with a VMA18 controller.
The VMA142x controller has five binary outputs
(BOs) and internally supplies 24 VAC. The VMA18
controller has three binary outputs (BOs) and
supplies 24 VAC to these BOs. The VMA18 controller
has two configurable outputs (COs) and these two
COs require an external low voltage power source.
Refer to Variable Air Volume Modular Assembly (VMA)
1400 Series (LIT-635058) for the Input/Output (I/
O) point differences between the VMA1410 and
VMA1420.
See the following figure for wiring instructions.
VMA1826/1832 VAV Controller Installation Guide 11
Figure 9: VMA Replacement Wiring Diagram
Sensor replacement and reuse
scenarios
This section describes sensor replacement and
reuse scenarios for replacing a VMA1410, VMA1415,
VMA1420, or the VMA controller with VMA18
controllers.
See Table 3 for a description of the most popular
sensor models used with the VMA1410, VMA1415,
VMA1420, and the VMA controllers, the sensor
replacement and reuse scenarios for that sensor
model, and sensor replacement and reuse
instructions.
Important: Complete all the steps in the
Mounting section before following the
instructions in this section.
VMA1826/1832 VAV Controller Installation Guide12
Sensor replacement and reuse
scenarios table
Table 3: Sensor replacement and reuse scenarios
Sensor used with VMA1410, VMA1415,
VMA1420, VMA1440 Controller
Sensor replacement and reuse scenarios Instructions
Replace a sensor with an NS Series Sensor
Note: Replacing a TE-6xxx Series
Sensor is recommended over reusing
the sensor because it provides a
usable port at the sensor location for
commissioning.
Replacing a TE-6xxx series sensor
TE-6xxx Series (see TE-6xxx series sensor
connected to VMA Controller)
Note: The VMA1832 does not support
the Dual Setpoint model TE-67xP-3x00
Reuse a sensor, installing an adapter at a
VMA controller location
Reusing a TE-6xxx series sensor
AP-TMZ1600-0 (see Replacing an AP-
TMZ1600-0 sensor connected to a VMA
Controller)
Replace a sensor with an NS Series Sensor
Replacing an AP-TMZ1600-0 sensor
connected to a VMA Controller
TE-7710-0 Series Wireless Transmitter and
TE-7720-0 Wireless Receiver (see Replacing
a TE-7710-0 Series Wireless Transmitter and
TE-7720-0 Wireless Receiver connected to a
VMA Controller)
Replace with a WRZ Series Wireless Sensor
and aWRZ7860 Series One-to-One Receiver
Replacing a TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless Receiver
connected to a VMA Controller
Replace a sensor with a TE-730 Series Sensor
Replacing a TE-700 Series sensor
TE-700 Series (see TE-700 Series Sensor
connected to a VMA Controller)
Reuse a sensor
Reusing a TE-700 Series sensor
Sensor Replacement Scenario
Descriptions
TE-6xxx series sensor connected to
VMA Controller
To replace a TE-6xxx Series Sensor with a
functionally equivalent NS Series Network Sensor,
follow the instructions in the Replacing a TE-6xxx
series sensor section.
To reuse a TE-6xxx Series Sensor connected to
a VMA controller, follow the instructions in the
Reusing a TE-6xxx series sensor section.
Replacing the sensor with an NS Series Network
Sensor is preferred to reusing the TE-6xxx Series
Sensor because the NS sensor allows for easier
controller commissioning. Be sure to use an NS
sensor with similar dimensions as the existing
sensor in order to match the original sensor
installation.
Note: If temporary occupancy is required for
the application on the TE-67xx and TE-68xx
Series Sensors, set the sensor's LED mode to
LED ON (the DIP switch positions on the back
of the sensor are down, up, and down). This
setting only applies to single and no setpoint
controller models (not dual setpoint controller
models). The VMA1832 does not support the
LED OFF mode and the pushbutton will not
function in that configuration.
Refer to the NS Series Network Sensors Product
Bulletin (LIT-12011574) for a complete list of available
NS Series Network Sensors.
Note: In each of the following procedures
that include the use of the Commissioning
Converter (BTCVT), note the following: The
Mobile Access Portal (MAP) Gateway serves
as a replacement for the BTCVT, which is no
longer available for purchase, but continues to
be supported on select controllers. CCT auto-
detects when BTCVT can be used or not, based
on the controller model and the corresponding
CCT Release mode.
BTCVT can be used with controllers that
contain CCT Release mode 10.2 or earlier
firmware.
Metasys
®
controllers from Release 9.0 or
earlier support BTCVT.
BTCVT cannot be used with controllers that
contain CCT Release mode 10.4.
VMA1826/1832 VAV Controller Installation Guide 13
Metasys Release 10.0 controllers use CCT
Release mode 10.4, therefore BTCVT is not
supported with these controllers.
Replacing a TE-6xxx series sensor
To replace a TE-6xxx Series Sensor with a
functionally equivalent NS Series Network Sensor,
complete the following instructions.
Note:
Replacing a TE-6xxx Series Sensor is
recommended over reusing the sensor.
When replacing a TE-6xxx Series sensor with
an NS Series sensor and dissimilar paint or wall
covering is visible outside of the new sensor,
consider using the NS-WALLPLATE-0 for the new
NS sensor. See Table 9 for more information.
1. Remove the TE-6xxx Series Sensor from the wall
and disconnect the 8-pin male jack from the
back of the sensor.
2. Plug the 8-pin male jack that was plugged into
the back of the sensor into the 8-pin female
socket on the single-socket adapter (Figure 10)
provided with the VMA18 controller.
3. Plug the 6-pin male jack on the single socket
adapter into the modular jack connection on
the NS Series Network Sensor.
4. Mount the NS Series Network Sensor in the
same location the TE-6xxx Series Sensor was
previously mounted, concealing the adapter
assembly in the existing wall opening behind
the sensor. Refer to the installation instructions
for the applicable NS Series Sensor model.
5. Plug the BTCVT into the 6-pin socket on the NS
Series Network Sensor.
Note: When using an NS Series Network
Sensor with screw terminal block terminations,
see the wiring diagram in the installation
instructions for the applicable NS Series Sensor
model.
Figure 10: Single-Socket Adapter
Reusing a TE-6xxx series sensor
To reuse a TE-6xxx Series Sensor with the VMA
controller, complete the instructions in this section.
The Y adapter provided in the VMA18 accessory pack
is required for this procedure.
CAUTION: The adapter must be installed at the
VMA controller location. Damage to the SA Bus
may occur if you do not use the Y adapter.
To install the adapter at the VMA controller location,
see Installing the adapter at the VMA Controller
location.
Figure 11: Y Adapter
Installing the adapter at the VMA
Controller location
To install the adapter at the VMA location, complete
the following instructions:
1. Disconnect the 8-pin male jack that is plugged
into the VMA1410, VMA1415, VMA1420, or
VMA1440 controller.
2. Plug the 8-pin male jack that was plugged into
the VMA controller into the 8-pin female socket
on the Y adapter (Figure 12).
VMA1826/1832 VAV Controller Installation Guide14
3. Plug the 8-pin male jack on the Y adapter into
the VMA18 controller socket labeled TSTAT
(Figure 12).
4. Plug the BTCVT into the 6-pin socket on the Y
adapter. When commissioning is complete,
allow the 6-pin socket to remain unconnected
(Figure 12).
Replacing an AP-TMZ1600-0 sensor
connected to a VMA Controller
To replace an AP-TMZ1600-0 sensor connected to a
VMA controller, complete the following instructions.
Note: The AP-TMZ1600-0 sensor is not
supported for use with the VMA18 controller
and must be replaced with an NS Series
Network Sensor. Refer to the NS Series Network
Sensors Product Bulletin (LIT-12011574) for a
complete list of available NS Series Network
Sensors.
1. Remove the AP-TMZ1600-0 sensor and
disconnect the 8-pin male jack from the back of
the sensor.
2. Plug the 8-pin male jack from the VMA
controller into the 8-pin female socket on the
single-socket adapter (Figure 10) included with
the VMA18 controller.
3. Plug the 6-pin male jack on the single socket
adapter into the modular jack connection on
the back of the NS Series Network Sensor.
4. Mount the NS Series Network Sensor in the
same location the AP-TMZ1600-0 Sensor was
previously mounted, concealing the adapter
assembly in the existing wall opening behind
the sensor. Refer to the installation instructions
for the applicable NS Series Sensor model.
5. Plug the BTCVT into the 6-pin socket on the NS
Series Network Sensor.
Note: When using an NS Series Network
Sensor with screw terminal block terminations,
see the wiring diagram in the installation
instructions for the applicable NS Series Sensor
model.
Replacing a TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless
Receiver connected to a VMA Controller
To replace a TE-7710-0 Series Wireless Transmitter
and TE-7720-0 Wireless Receiver connected to a VMA
controller, or to convert the wired sensors used
with the VMA18 controller to wireless, complete the
following instructions.
Note: The TE-7710-0 Series Wireless
Transmitter and TE-7720-0 Wireless Receiver
must both be replaced with a WRZ Series
Wireless Sensor and a WRZ7860-0 Series
One-to-One Receiver. Refer to the WRZ
Series Wireless Room Sensors Product Bulletin
(LIT-12011653) for a complete list of available
WRZ Series Wireless Room Sensors.
1. Disconnect the 6-foot interface cable
connecting the VMA controller and the
TE-7720-0 Wireless Receiver.
2. Plug one end of the 6-foot interface cable into
the VMA18 socket labeled TSTAT.
3. Plug the other end of the 6-foot interface cable
into the 8-pin female socket of the single-socket
adapter.
4. Plug the male end of the single-socket adapter
directly into the BTCVT.
5. Complete commissioning of the VMA18
controller and disconnect the BTCVT.
Note: Sensor point information such as
temperature, setpoint, and occupancy is
not available during commissioning.
6. Install the WRZ Series Wireless Sensor and
a WRZ7860-0 Series One-to-One Receiver in
the same locations as the previous sensor
and receiver. Refer to the WRZ Series Wireless
Room Sensors Installation Instructions (Part No.
24-10332-2) and the WRZ-7860-0 Installation
Instructions (Part No. 24-10563-47).
7. Plug the 6-pin male jack on the adapter into the
WRZ7860-0 receiver.
Note: When using an WRZ Series Sensor with
screw terminal block terminations, refer to the
wiring diagram in the installation instructions
for the applicable WRZ Series Sensor model.
VMA1826/1832 VAV Controller Installation Guide 15
TE-700 Series Sensor connected to a
VMA Controller
To replace a TE-700 Series Sensor with a TE-730
Series Sensor, follow the instructions in Replacing a
TE-700 Series sensor.
To reuse a TE-700 Series Sensor connected to a
VMA controller, follow the instructions in Reusing a
TE-700 Series sensor.
Replacing a TE-700 Series sensor
Replace a TE-700 Series Sensor with a TE-730 Series
Sensor. No cable adapters are required for this
scenario.
Note: Refer to the TE-730 Series Sensor
Installation Instructions (Part No. 24-10674-0) to
install the TE-730 Series Sensor.
Reusing a TE-700 Series sensor
See the instructions in this section to reuse a
TE-700 Series Sensor when connected to a VMA18
controller.
1. Disconnect the 8-pin male jack plugged into the
VMA controller.
2. Plug the 8-pin male jack on the Y adapter
(Figure 10) provided with the VMA controller
into the 8-pin female socket labeled TSTAT on
the VMA18 controller.
3. Plug the 8-pin male jack that was plugged into
the VMA controller into the 8-pin female socket
of the Y adapter.
Note: The 6-pin connection is not used
for this scenario and it should remain
unconnected.
4. Refer to the TE-730 Series Sensor Installation
Instructions (Part No. 24-10674-0) to install the
TE-730 Series Sensor.
Figure 12: Y Adapter at Controller Location
VMA1826/1832 VAV Controller Installation Guide16
Input and Output wiring guidelines tables
Table 4: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal block label Terminal labels Function, ratings, and requirements
To determine wire size and
maximum cable length
+15 V
15 VDC Power Source for active (3-wire) input
devices connected to the Universal INn terminals.
Provides 35 mA total current.
Same as (Universal) INn.
Note: Use 3-wire cable for
devices that source power
from the +15 V terminal.
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 75k ohm Pulldown
See Guideline A in Table 5.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V, 15k ohm pull up
Qualified Sensors: 0–2k potentiometer,
RTD (1k Nickel [ Johnson Controls sensor],
1k Platinum, and A99B Silicon Temperature Sensor)
Negative Temperature Coefficient (NTC) Sensor
10K Type L (10K JCI Type II is equivalent to Type L) or
2.252K Type II
See Guideline A in Table 5.INn
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V, 15k ohm pull up
See Guideline A in Table 5.
UNIVERSAL
(Inputs)
ICOMn
Universal Input Common for all Universal INn
terminals
Note: All Universal ICOMn terminals are
isolated from all other commons on the -0
models. The -1 model ICOMn terminals are
isolated from FC BUS COM terminals only.
Same as (Universal) INn.
OUTn
Binary Output - 24 VAC Triac (Internal Power)
Sources internal 24 VAC power (24~ HOT)
See Guideline C in Table 5.
BINARY
(Outputs)
OCOMn
Binary Output - 24 VAC Triac (Internal Power)
Connects OCOMn to 24~ COM when activated.
Internal Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
See Guideline C in Table 5.
VMA1826/1832 VAV Controller Installation Guide 17
Table 4: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal block label Terminal labels Function, ratings, and requirements
To determine wire size and
maximum cable length
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
External 1k to 50K ohm load required
See Guideline A in Table 5.
OUTn
Binary Output 24 VAC Triac
Connects OUT to OCOM when activated.
External Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
See Guideline C in Table 5.
Analog Output Signal Common: All Configurable
Outputs defined as Analog Outputs share a
common, which is isolated from all other commons
except the Binary Input common.
CONFIGURABLE
(Outputs)
OCOMn
Binary Output Signal Common: All Configurable
Outputs defined as Binary Outputs are isolated from
all other commons, including other Configurable
Output commons.
Same as (Configurable) OUTn.
Note: Table 5 defines cable length guidelines
for the various wire sizes that may be used for
input and output wiring.
Table 5: Cable length guidelines for recommended wire sizes
Guideline Wire size/Gauge and type Maximum cable length and type Assumptions
1.0 mm (18 AWG) stranded copper 457 m (1,500 ft) twisted wire
0.8 mm (20 AWG) stranded copper 297 m
(975 ft) twisted wire
297 m (975 ft) twisted wire
0.6 mm (22 AWG) stranded copper 183 m
(600 ft) twisted wire
183 m (600 ft) twisted wire
A
24 AWG stranded copper 107 m (350 ft)
twisted wire
107 m (350 ft) twisted wire
100 mV maximum voltage drop
Depending on the cable length
and the connected input or output
device, you may have to define an
offset in the setup software for the
input or output point.
1.0 mm (18 AWG) stranded copper 229 m (750 ft) twisted wire
0.8 mm (20 AWG) stranded copper 297 m
(975 ft) twisted wire
137 m (450 ft) twisted wire
0.6 mm (22 AWG) stranded copper 183 m
(600 ft) twisted wire
91 m (300 ft) twisted wire
B
24 AWG stranded copper 107 m (350 ft)
twisted wire
61 m (200 ft) twisted wire
100 mV maximum voltage drop
Depending on the cable length
and the connected input or output
device, you may have to define an
offset in the setup software for the
input or output point.
C
See Figure 13 to select wire size/gauge.
Use stranded copper wire.
See Figure 13 to determine cable
length.
Use twisted wire cable.
N/A
Figure 13: Maximum wire length by current and
wire size
VMA1826/1832 VAV Controller Installation Guide18
Communication bus and supply
power table
Table 6: Communication bus and supply power terminal blocks, functions, ratings, requirements, and
cables
Terminal block/Port label Terminal labels
Function, electrical ratings/
Requirements
Recommended cable type
1
+
-
N2/FC Bus Communications
COM
Signal Reference (Common) for bus
communications
N2/FC BUS
2
2
SHLD
Isolated terminal (optional shield drain
connection)
Use existing cable or 18 AWG
+
-
SA Bus Communications
COM
SA Bus Signal Reference and 15 VDC
Common
SA BUS
SA PWR
15 VDC Supply Power for Devices on
the SA Bus
0.6 mm (22 AWG) stranded, 4-wire
(2 twisted-pairs), shielded cable
recommended
Note: The + and - wires are one
twisted pair, and the COM and
SA PWR are the second twisted
pair.
TSTAT TSTAT
RJ-45 8-Position Modular Connector
provides +15 VDC Power for:
BTCVT
33
MAP Gateway
VAV Balancing Tool
One-to-One Wireless Receiver
24 AWG 3-pair CAT 3 Cable <30.5 m
(100 ft)
HOT
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)
24~
COM
24 VAC Power Supply Common The
-0 models isolate this terminal from all
other commons.
The -1 models only isolate this terminal
from the FC bus common.
0.8 mm to 1.0 mm²
(20 to 18 AWG) 2-wire
1 To determine wire size and cable lengths for cables other than the recommended cables, see Table 5.
2 The N2/FC Bus wiring recommendations in this table are for N2 bus communications at 9,600 baud. For more information, refer to
the N2 Communications Bus Technical Bulletin (LIT-636018).
3 The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported
on select controllers.
Setup and adjustments
Important: Electrostatic discharge can
damage controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.
Setting the device address
Metasys field controllers are subordinate devices on
N2 buses. Before operating field controllers on a
bus, you must set a valid and unique device address
for each controller on the bus.
You set a field controller’s device address by setting
the positions of the switches on the Device Address
VMA1826/1832 VAV Controller Installation Guide 19
DIP switch block at the top of the controller (Figure
1). Device addresses 1 through 253 are the valid N2
addresses for these N2 controllers.
Valid MS/TP addresses for wired controllers are
4 through 127. For wireless controllers, valid
addresses are 132 through 254 (132 [132-128=4]
through 254 [254-128=126]).
For wireless controllers, the address 120 through
127 are used by the ZigBee
®
Coordinator. This may
cause a smaller field device range.
If the VMA18 Series controller may eventually be
converted to MS/TP, use addresses 4 through
127 for a wired VMA controller or addresses 132
through 253 for a future wireless VMA controller, if
possible. Using these addresses simplifies the MS/
TP conversion process.
Note: Metasys field controllers ship with
Switch 128 ON and the remaining address
switches OFF rendering the controllers wired
subordinate devices, which do not operate
on MS/TP buses, but do not interfere with
bus operation. Set a valid and unique device
address on the field controller before applying
power to the controller on the bus.
The DIP switch block (Figure 14) has eight switches
numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 128
through 1 are device address switches.
Figure 14: Device address switches set to 21
To set the device addresses on a Metasys field
controller:
1. Set all of the switches on the field controller’s
device address DIP switch block (128 through 1)
to OFF.
2. Set one or more of the eight address switches
(128 through 1) to ON, so that the sum of the
switch numbers set to ON equals the intended
device address. Set the highest number switch
that is less than or equal to the intended device
address to ON. Then continue setting lower
numbered switches until the total equals the
intended address. For example, if the intended
device address is 21, set Switch 16 to ON first,
then set Switch 4 to ON, followed by Switch 1
(16+4+1=21). See Figure 14.
3. Set a unique and sequential device address
for each of the field controllers connected on
the N2 bus, starting with device address 1.
To ensure the best bus performance (if the
protocol is changed to BACnet MS/TP), set
sequential device addresses with no gaps in
the device address range (4, 5, 6, 7, 8, 9, and
so on). The field controllers do not need to
be physically connected on the bus in their
numerical device address order.
4. Write each field controller’s device address on
the white label below the DIP switch block on
the controller’s cover.
Refer to the N2 Communications Bus Technical Bulletin
(LIT-636018) for more information on field controller
device addresses and how to set them on N2 buses.
Setting the EOL switch
Each field controller has an EOL (End of Line) switch,
which, when set to ON (up), sets the field controller
as a terminating device on the bus. See Figure 1 for
the EOL switch location on the field controller. The
default EOL switch position is OFF (down).
Figure 15: EOL switch positions
To set the EOL switch on a field controller:
1. Determine the physical location of the field
controller on the N2 or FC Bus.
2. Determine if the field controller must be set as
a terminating device on the bus.
VMA1826/1832 VAV Controller Installation Guide20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

Johnson Controls VMA18 Series Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI