Trane Axiom VSHE042 Operating And Maintenance

Category
Split-system air conditioners
Type
Operating And Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Water Source Heat Pump
Axiom™ Variable Speed - VSH/VSV
24 to 60 MBtuh - 60 Hz
Installation, Operation,
and Maintenance
Model Numbers
VSHE024 VSVE024
VSHE033 VSVE033
VSHE042 VSVE042
VSHE050 VSVE050
VSHE060 VSVE060
WSHP-SVX13C-EN
January 2015
© 2015Trane All rights reserved WSHP-SVX13C-EN
Introduction
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earths naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTIONs
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
NOTICE
Indicates a situation that could result in
equipment or property-damage only
accidents.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards.To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
Introduction
WSHP-SVX13C-EN 3
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
WSHP-SVX13C-EN (03 January 2015)
Added the option of a plenum fan allowing the unit to
work at higher external static pressures (ESP)
Added selection of new motor
Added option of insulated water coil and suction line
Condensate drain update
4 WSHP-SVX13C-EN
Table of Contents
Introduction ............................. 2
Warnings, Cautions, and Notices ........ 2
Important Environmental Concerns ..... 2
Important Responsible Refrigerant Practices
2
Copyright ............................. 3
Table of Contents ........................ 4
Model Number Description - VSH/VSV ..... 6
General Information ..................... 7
Unit Inspection ...................... 7
Jobsite Inspection ................... 7
Jobsite Storage ..................... 7
Model Number Description ............ 7
Unit Description ..................... 7
Unit Nameplate ..................... 7
Compressor Nameplate ............... 8
Air-to- Refrigerant Coil ................ 8
Water-to-Refrigerant Coil .............. 8
Controls ............................ 8
System Input Devices and Functions .... 8
Pump Module (field installed accessory) . 8
Unit Dimensions ......................... 9
Clearance Dimensions .................. 9
Unit Fan Performance ................... 26
MERV Filter .......................... 34
General Data ........................... 36
Installation ............................. 39
General Installation Checks ........... 39
Supply-Air Ductwork ................ 39
Return-Air Ductwork ................. 40
Return Air Ducted Panel .............. 40
Ducted Filter Rack ................... 40
Sound Attenuation Pad .............. 41
Hanging the Horizontal Unit .......... 41
Condensate Drain Connection ......... 41
Supply/Return Pipe Connections ...... 41
Cleaning and Flushing the Water Loop . 42
Field Installed Power Wiring .......... 43
Main Unit Power Wiring ..............43
Control Power Transformer ...........43
Sensor Location .....................43
Installation of the Axiom model VS .....44
Electrical Data ...........................45
Variable-Speed WSHP Tracer™ UC400 Control-
ler
......................................47
I/O Definitions .......................47
UC400 Setpoints and Setup Parameters ..48
Sequence of Operation ...................49
Random Start Timer ...................49
Maintenance Timer ....................49
Setpoint Arbitration ....................49
Sensor Arbitration .....................49
Occupancy Determination ..............49
Occupied mode .....................49
Unoccupied mode ...................50
Occupied Standby mode ..............50
Occupied Bypass mode ...............50
Timed override operation .............50
Supply fan mode operation ...........50
Supply fan mode: Cycling .............50
Supply fan mode: ON ................50
Zone sensor fan switch ...............50
Unit Mode Arbitration ................51
Manual mode determination ..........51
Auto-Changeover ....................51
Isolation Valve Operation .............51
Isolation Valve “ON” Control ..........51
Entering water temperature (EWT) sampling
52
Isolation Valve “OFF” Control .........52
Reversing Valve Operation ............52
Cooling and Heating Operation ........52
Unoccupied Cooling and Heating Operation
52
Demand Limit Operation ..............52
Pre-Start Checklist .......................53
Start-Up ................................54
Table of Contents
WSHP-SVX13C-EN 5
Operating Pressures .................. 54
Water Pressure Drop .................. 58
Water Volume ...................... 58
Maintenance ........................... 59
Preventive Maintenance ............. 59
Condensate Trap ................... 59
Troubleshooting ........................ 60
General Unit Troubleshooting .......... 60
Compressor Drive Troubleshooting ..... 61
Pressure transducer/controller ......... 62
Control Wiring ......................... 63
6 WSHP-SVX13C-EN
Digits 1-3 Unit Configuration
VSH = Variable Speed Vertical
VSV = Variable Speed Horizontal
Digit4—Development
Sequence
E = R-410A Refrigerant
Digit 5-7 Nominal Capacity
024 = 24 MBtuh
033 = 33 MBtuh
042 = 42 MBtuh
050 = 50 MBtuh
060 = 60 MBtuh
Digit 8 Voltage (Volts/Hz/
Phase)
1 = 208/60/1
2 = 230/60/1
4 = 460/60/3
Digit 9 Heat Exchanger
1 = Copper Water Coil
2 = Cupro-Nickel Water Coil
7 = Insulated Copper Water Coil and
Suction Lines
8 = Insulated Cupro-Nickel Water Coil and
Suction Lines
Digit 10-11 Current Design
Sequence
Digit 12 Control Type
F = UC400
Digit 13 Freeze Protection
A = 20°F (low temperature/geothermal)
B = 35°F
Digit 14 Sales Order Special
0 = None
S = Sales Order Special
Digit 15 Supply Air
Arrangement
B = Back Supply Air
L = Left Supply Air
R = Right Supply Air
T = Top Supply Air
Digit 16 Return Air
Arrangement
L = Left Return Air
R = Right Return Air
Digit 17 Disconnect
0 = None
Digit 18 Filter Type
1 = 1 inch Throwaway Filter
2 = 2 inch Throwaway Filter
4 = 2 inch MERV 8
5 = 2 inch MERV 13
VSV E 042 3 2 **
123 4 567 8 9 1011
Digit 19 Motor Type
A = ECM
B = Plenum Fan
Model Number Description - VSH/VSV
WSHP-SVX13C-EN 7
General Information
Unit Inspection
Unpack all components of the kit.
Check carefully for any shipping damage. If any
damage is found it must be reported immediately and
a claim made against the transportation company.
Visually inspect the components for shipping damage
as soon as possible after delivery, before it is stored.
Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the
shipment.
Do not remove damaged material from the receiving
location.Take photos of the damage, if possible.The
owner must provide reasonable evidence that the
damage did not occur after delivery.
Notify the carriers terminal of damage immediately by
phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.
Do not attempt to repair any damaged parts until the
parts are inspected by the carriers representative.
Jobsite Inspection
Always perform the following checks before
accepting a unit:
Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit
nameplate specifications.
Visually inspect the exterior of the unit, for signs of
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once the bill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLDTO party and future freight claims MAY NOT be
accepted by the freight company.
Jobsite Storage
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources from growing, the unit should be
stored indoors. If indoor storage is not possible, the
following provisions for outdoor storage must be met:
Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.
Cover the unit(s) with a water proof tarp to protect
them from the elements.
Make provisions for continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces. Wet interior unit insulation can become an
amplification site for microbial growth (mold) which
has been determined to be a cause of odors and
serious health related indoor air quality problems.
Store units in the normal UP orientation to maintain oil
in the compressor.
Do not stack vertical units. Horizontal units may be
stacked two high.
Model Number Description
All products are identified by a multiple-character model
number that precisely identifies a particular type of unit. Its
use will enable the owner/operator, installing contractors,
and service engineers to define the operation, specific
components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial
number printed on the unit nameplate.
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and run tested for proper control
operation.
Unit Nameplate
The unit nameplate is located on the outside of the control
box access panel at the front of the unit. It includes the unit
model number, serial number, electrical characteristics,
refrigerant charge, and other pertinent unit data.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers may also cause
respiratory, skin or eye irritation.
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification
site for microbial growth (mold), which may cause odors
and serious health related indoor air quality problems. If
there is evidence of microbial growth (mold) on the
interior insulation, remove or replace the insulation prior
to operating the system. Failure to remove microbial
growth could result in serious health problems.
General Information
8 WSHP-SVX13C-EN
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Air-to- Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak
tested to assure there is no cross leakage between the
water tube (copper/cupro-nickel) and refrigerant gas (steel
tube).
.
Controls
The control system offered to control the unit is the
Tracer™ UC400 programmable BACnet™ unit controller.
The UC400 controller is standard for all unit sizes.
All power wiring to the equipment is made at the unit
power block. VSH/V 460V units require a neutral wire.
System Input Devices and Functions
A zone sensor or building automation system is required
to operate the water-source heat pump.The flexibility of
having several mode capabilities depends upon the type
of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the UC400
control systems may be located in the back of this manual.
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual
1/6 HP bronze pump and a brass 3-way shut-off valve. Cast
iron pumps are also acceptable.The pump module kits
shall contain the necessary components for the
installation, operation and maintenance of the water
circuit of a closed-loop distributed pumping application.
Table 1. High/Low pressure switch
Trip Recover Unit
LP 40 +/-4 56 +/-4 psig
HP 650 +/-10 550 +/-10 psig
Table 2. Refrigerant charge
VSV R-410A (ounces)
VSV024 72
VSV033 72
VSV042 129
VSV050 129
VSV060 139
VSH024 72
VSH033 72
VSH042 138
VSH050 138
VSH060 150
WSHP-SVX13C-EN 9
Unit Dimensions
Clearance Dimensions
Access to the unit for service purposes should be provided
at installation. All configurations require clearance (see
Figure 2, p. 9 and Figure 1, p. 9) from other mechanical
and electrical equipment (as shown) to enable panel
removal from the unit for service/maintenance ability.
Some local and/or NEC codes require a greater service
clearance than listed below. Check all code requirements
prior to unit installations. The installer is responsible for
compliance with local and NEC code requirements.
Note: *Units in a free return application will
require more than a 1 inch clearance to
provide proper air flow to the units air-to-
refrigerant coil.
Figure 1. Clearance dimensions* VSH
20"
36"
20"
20"
20"
20"
UNIT FRONT
LEFT RETURN RIGHT SUPPLY
UNIT FRONT
LEFT RETURN BACK SUPPLY
36"
20"
20"
20"
20"
20"
UNIT FRONT UNIT FRONT
RIGHT RETURN LEFT SUPPLY RIGHT RETURN BACK SUPPLY
36" 36"
20"
20"
Figure 2. Clearance dimensions* VSV
1"
36"
1"
24"
UNIT FRONT
RIGHT RETURN
TOP/BACK SUPPLY
1"
36"
1"
24"
UNIT FRONT
LEFT RETURN
TOP/BACK SUPPLY
Unit Dimensions
10 WSHP-SVX13C-EN
Figure 3. Left return/top supply - VSV with ECM
D
L
K
D
E
JM
F
B
H
A
HI VOLT
LO VOLT
W.O.
DRAIN
W.I.
C
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT RIGHT SIDE
8 3/4”
3 5/8”
12”
9 1/2”
G
3 5/8”
Table 3. Dimensional data - left return/top supply - VSV with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 20 23 10-1/2 13-1/2 3/16 3/4 3/4 3/4
042–050 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 24-1/4 27-7/8 13-7/8 11-3/8 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
WSHP-SVX13C-EN 11
Figure 4. Left return/top supply - VSV 5 tons with ECM
D
E
L
K
J
H
4-5/8
10-5/8
A
B
C
2 1/2"
8 1/4"
19
G
F
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
W.I.
DRAIN
Table 4. Dimensional data - left return/top supply - VSV060 with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
060 26 62 30-1/2 13-1/4 13-5/8 5 13 39-3/4 30-3/8 13 8-5/8 N/A 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
12 WSHP-SVX13C-EN
Figure 5. Left return/back supply - VSV 5 tons with ECM
D
E
JM
D
F
B
H
8 3/4"
3 5/8"
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
A
12"
3 5/8"
C
BLOWER
ACCESS
COMP/CONTROL
ACCESS
9 1/2"
G
LEFT SIDE
FRONT RIGHT SIDE
TOP
Table 5. Dimensional data - left return/back supply - VSV060 with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 20 23 10-1/2 13-1/2 3/16 3/4 3/4 3/4
042–050 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 24-1/4 27-7/8 13-7/8 11-3/8 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
WSHP-SVX13C-EN 13
Figure 6. Left return/back supply - VSV 5 tons with ECM
H
4-5/8
10-5/8
A
B
C
2 1/2"
8 1/4"
19
E
G
L
J
D
K
F
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
W.I.
DRAIN
Table 6. Dimensional data - left return/back supply - VSV060 with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
060 26 62 30-1/2 13-1/4 13-5/8 5 6-1/2 39-3/4 30-3/8 13 8-5/8 N/A 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
14 WSHP-SVX13C-EN
Figure 7. Right return/top supply - VSV with ECM
C
A
3 5/8"
8 3/4"
LO VOLT
HI VOLT
DRAIN
W.O.
3 5/8"
12"
H
B
D
L
F
J M
E
D
K
9 1/2"
G
FRONT RIGHT SIDE
TOP
LEFT SIDE
BLOWER
ACCESS
COMP/CONTROL
ACCESS
W.I.
Table 7. Dimensional data - right return/top supply - VSV with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 20 23 10-1/2 13-1/2 3/16 3/4 3/4 3/4
042–050 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 24-1/4 27-7/8 13-7/8 11-3/8 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
WSHP-SVX13C-EN 15
Figure 8. Right return/top supply - VSV 5 tons with ECM
H
4-5/8
10-5/8
A
B
C
2 1/2"
8 1/4"
19
J
L
K
F
D
G
E
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
W.I.
DRAIN
Table 8. Dimensional data - right return/top supply - VSV060 with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
060 26 62 30-1/2 13-1/4 13-5/8 5 7-7/8 39-3/4 30-3/8 13 8-5/8 N/A 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
16 WSHP-SVX13C-EN
Figure 9. Right return/back supply VSV with ECM
LO VOLT
HI VOLT
8 3/4"
3 5/8"
C
DRAIN
W.I.
W.O.
12"
3 5/8"
A
H
D
E
J M
D
F
B
9 1/2"
G
BLOWER
ACCESS
COMP/CONTROL
ACCESS
LEFT SIDE
FRONT RIGHT SIDE
TOP
Table 9. Dimensional data - right return/back supply - VSV with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 41-7/8
26-1/2
(673)
18 3-1/4 1-7/8 9-1/2 20 23 10-1/2 13-1/2 3/16 3/4 3/4 3/4
042–050 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 24-1/4 27-7/8 13-7/8 11-3/8 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
WSHP-SVX13C-EN 17
Figure 10. Right return/back supply - VSV 5 tons with ECM
H
4-5/8
10-5/8
A
B
C
2 1/2"
8 1/4"
19
J
D
F
E
G
K
L
BLOWER
ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
W.I.
DRAIN
Table 10. Dimensional data - right return/back supply - VSV060 with ECM
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
060 26 62 30-1/2 13-1/4 13-5/8 4 1-1/2 39-3/4 30-3/8 13 8-5/8 N/A 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
18 WSHP-SVX13C-EN
Figure 11. Left return/top supply VSV with plenum fan
B
H
D
JM
FD
A
C
3-5/8
9-1/2
G
12
3.56
9-3/4
E
BLOWER
ACCESS
FRONT
LEFT SIDE
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
DRAIN
W.I.
TOP
Table 11. Dimensional data—left return/top supply with plenum fan
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024-033 24-1/2 66-3/32 26-1/2 18 3-1/4 7-23/32 9-1/2 20 23 N/A N/A 1/4 3/4 3/4 3/4
042-050 26-1/2 71-3/32 30-1/2 18 4-1/4 5-23/32 9-1/2 24-1/4 27-7/8 N/A N/A 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
WSHP-SVX13C-EN 19
Figure 12. Left return/top supply — VSV060 with plenum fan
B
J
D
D G
F
H
10-5/8
4-5/8
2-1/2
8-1/4
19
A C
26.0780
BLOWER
ACCESS
FRONT
TOP
LEFT SIDE
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
DRAIN
W.I.
Table 12. Dimensional data—left return/top supply - VSV060 with plenum fan
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
060 26 86-1/4 30-1/2 18 N/A 4 7-3/4 39-3/4 30-3/8 N/A N/A N/A 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
Unit Dimensions
20 WSHP-SVX13C-EN
Figure 13. Right return/top supply with plenum fan
B
H
A
C
3-5/8
9-1/2
G
12
3.56
9-3/4
MJ
E
D
F D
BLOWER
ACCESS
FRONT
LEFT SIDE
RIGHT SIDE
HI VOLT
LO VOLT
W.O.
DRAIN
W.I.
TOP
Table 13. Dimensional data - right return/top supply with plenum fan
Units A B C D E F G H J K L M
W.I.
NPTI
W.O.
NPTI
Drain
FPT
024–033 24-1/2 66-3/32 26-1/2 18 3-1/4 7-23/32 9-1/2 20 23 N/A N/A 1-3/4 3/4 3/4 3/4
042–050 26-1/2 71-3/32 30-1/2 18 4-1/4 5-23/32 9-1/2 24-1/4 27-7/8 N/A N/A 1/2 1 1 3/4
Note: Access to the unit for service purposes should be provided at installation. Local and/or NEC codes may require greater service clearance. Check all
code requirements prior to the unit installation. Installer is responsible for following all local and NEC code requirements.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Trane Axiom VSHE042 Operating And Maintenance

Category
Split-system air conditioners
Type
Operating And Maintenance