Table 4. ANSI/AHRI/ASHRAE/ISO13256-1 WLHP, GWHP and GLHP performance - 0.5 to 5 Tons
Model Rated GPM Rated CFM
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Full Cool 77°F Full Heat 32°F
Capacity
BtuhEER
Capacity
Btuh COP
Capacity
Btuh EER
Capacity
Btuh COP
Capacity
Btuh EER
Capacity
Btuh COP
GEVG006 1.50 190 7000 13.7 9300 4.70 8100 21.30 7500 4.10 7400 16.00 5600 3.30
GEVG009 2.25 285 8700 15.5 11200 5.50 9600 23.80 9100 4.70 8900 17.80 6700 3.70
GEVG012 3.00 380 11400 14.9 15300 5.30 13300 24.20 12400 4.60 12100 17.60 9400 3.70
GEVG015 3.75 475 15400 15.4 19300 5.20 17300 23.60 15700 4.40 16100 17.90 12400 3.70
GEVG018 4.50 570 18000 15.7 22800 5.10 20100 24.20 18700 4.50 18800 18.20 14400 3.70
GEVG024 6.00 760 23900 16.1 31100 5.30 26600 24.40 25300 4.60 24800 18.50 19600 3.80
GEVG030 7.50 950 29000 15.4 37900 5.10 32300 23.00 30800 4.50 30200 17.70 23300 3.70
GEVG036 9.00 1140 36000 15.4 45100 5.00 39900 22.60 36900 4.40 37300 17.60 28700 3.60
GEVG042 10.50 1330 40900 14.9 55600 4.70 45500 22.00 45600 4.20 42600 17.10 35300 3.50
GEVG048 12.00 1520 49500 15.1 62600 4.90 55700 22.80 50000 4.20 51800 17.40 37600 3.30
GEVG060 15.00 1900 55200 14.5 75400 4.60 61700 21.30 61200 4.10 57300 16.50 47000 3.50
Notes:
1. Rated in accordance with ANSI/AHRI/ASHRAE/ISO13256-1. Certified conditions are 80.6°F DB/66.2°F WB EAT in cooling and 68F DB/59°F WB EAT in heating.
2. Models with capacities greater than 135,000 Btuh are not included in the ANSI/AHRI/ASHRAE/ISO13256-1 water-to-air and brine-to-air heat pump certification program.
Table 5. Electrical data - ECM motors - 0.5 to 5 tons GEVG
Model No. Unit Volts Blower Motor HP
Minimum Circuit
Ampacity
Maximum Overcurrent
Protective Device
GEVG006 208-230/60/1 1/3 5/5 15/15
GEVG006 265/60/1 1/3 515
GEVG009 208-230/60/1 1/3 6/6 15/15
GEVG009 265/60/1 1/3 515
GEVG012 208-230/60/1 1/3 9/9 15/15
GEVG012 265/60/1 1/3 715
GEVG015 208-230/60/1 1/3 10/10 15/15
GEVG015 265/60/1 1/3 715
GEVG018 208-230/60/1 1/3 12/12 20/20
GEVG018 265/60/1 1/3 10 15
GEVG024 208-230/60/1 1/2 19/19 30/30
GEVG024 265/60/1 1/2 13 20
GEVG024 208-230/60/3 1/2 11/11 15/15
GEVG024 460/60/3 1/2 615
GEVG030 208-230/60/1 3/4 20/20 30/30
GEVG030 208-230/60/3 3/4 13/13 20/20
GEVG030 265/60/1 3/4 16 25
GEVG030 460/60/3 3/4 715
GEVG036 208-230/60/1 3/4 24/24 40/40
GEVG036 265/60/1 3/4 20 30
GEVG036 208-230/60/3 3/4 16/16 25/25
GEVG036 460/60/3 3/4 915
GEVG042 208-230/60/1 3/4 26/26 40/40
GEVG042 208-230/60/3 3/4 21/21 30/30
GEVG042 460/60/3 110 15
GEVG048 208-230/60/1 131/31 50/50
GEVG048 208-230/60/3 123/23 35/35
GEVG048 460/60/3 110 15
GEVG060 208-230/60/1 138/38 60/60
GEVG060 208-230/60/3 125/25 40/40
GEVG060 460/60/3 113 20
3
4 5
Table 5. Electrical data - ECM motors - 0.5 to 5 tons GEVG (continued)
Model No. Unit Volts Blower Motor HP
Minimum Circuit
Ampacity
Maximum Overcurrent
Protective Device