Danfoss Case Story - Medical Centers Keep Cool User guide

Type
User guide
www.danfoss.us
<3
years payback
When combined with
air-to-air heat exchangers,
Danfoss VSH variable-
speed compressors are
helping Annexairs
rooftop makeup air units
use less energy and are
expected to have less than
a 3-year payback.
Medical Centers Keep Cool
With Variable Speed Compressors
As the oldest inland city in South Carolina dating back to King George III,
Camden is proud of its stately homes, steeplechase racing and southern
resort hospitality. It’s also proudly celebrating the 100-year anniversary of
its hospital -- today known as KershawHealth Medical Center. This modern,
multi-story, 215-bed facility provides general medical and surgical care for
65,000 residents in Kershaw County and surrounding communities. It’s also
keeping up with the times by using energy-ecient, dedicated outdoor air
systems employing Danfoss VSH variable-speed compressors.
Today’s hospitals are built to comply with ASHRAE Standard 62-2007,
which sets the minimum ventilation requirements for acceptable indoor air
quality,” notes Anthony Palucci, director of sales for Annexair, the system
manufacturer. “Our goal was to provide a product that could not only meet
the outside air requirements, but also provide energy savings.
The ASHRAE standard requires operating rooms to have 25 air changes per
hour. At least ve of those air changes must use 100 percent outside air to
maintain positive pressure to keep unhealthy air from leaking into the
surgical suite. Other hospital areas require two changes per hour to control
odors and provide ventilation for comfort. But using a traditional
mechanical cooling for that amount of outside air is extremely expensive.
Annexair’s solution was to use a recuperative dehumidication design in
the makeup air-handling systems. Each unit employed a Danfoss VSH
variable-speed compressor to supply a cooling coil used in conjunction
with a xed plate heat exchanger to recycle thermal energy.
There are several ways to meet requirements for 100 percent outdoor air
without paying a high price for electricity,” says Palucci. “Typically, a unit
like this will use a xed-speed compressor and slow fan speed to increase
time through the cooling section to pull more moisture from the supply air.
But that makes the air too cold. Then you’ve got to use hot gas reheat to
raise the sensible temperature, which is extremely inecient.
Palucci proposed a dedicated outdoor unit package that takes advantage
of a xed plate heat exchanger to provide free pre-cooling and free-reheat
functions to handle dehumidication at full load. The variable-speed
compressor provides the balance of cooling needed at part loads.
This design takes advantage of Camden’s maritime climate,” says Palucci.
“In the summer, humidity is high and temperatures average 78 degrees
Fahrenheit, peaking in the 90s in July. The heat exchanger does double
Case Story
MAKING MODERN LIVING POSSIBLE
USCO.EA .014. A1.22 ©Danfoss USCO/mk, 02.2013
duty by providing cooling and reheating to
dehumidify, using the compressor and cooling
coil section as needed during part-load
conditions.”
Controlling airborne moisture in the fresh air
supplied to the facility is important to control
fungus and microbe growth inside. Proper
dehumidication control is also important to
minimize moisture in the airhandling unit itself.
If ambient air is not properly pre-cooled and
reheated, condensation can occur.
Palucci explains that in an air-to-air recuperative
unit, the outdoor air passes through the xed
plate heat exchangers twice (2-pass). The heat
exchange occurs between the incoming fresh
warm air and the cool air leaving the cooling
coil. On the rst pass, the xed plate pre-
conditions the air reaching the cooling coil by
reducing the sensible temperature, thereby
requiring less mechanical cooling.
At part-load conditions, the VSH compressor
supplies the DX coil with exactly the required
cooling capacity to drop the sensible
temperature even further as needed. The
cooling coil maintains a constant leaving air
dewpoint with the help of the VSH compressor,
without the use of energy wasting hot gas
by-pass. Then in the second pass, the cooled air
is reheated by absorbing heat from the
incoming air stream. Again as needed, a hot gas
reheat coil will raise the sensible temperature to
maintain a neutral dry supply air. But because
the heat exchanger is about 65 percent eective
in handling both precooling and reheating
functions simply through thermal transfer,
electric consumption for additional cooling and
reheats is minimized.
Annexair provided two rooftop makeup air units
(MAU), each using one 22-ton Danfoss VSH
compressor and each delivering 3,800 cfm.
Another MAU employs a 12-ton compressor and
provides 1,700 cfm. The compressors supply the
mechanical cooling section to enable the MAU
to deliver dry air when dry bulb energy air
temperatures range from 95 degrees to 55
degrees and wet bulb temperatures range from
78 degrees to 53 degrees.
We prefer VSH series compressors for our
dedicated MAU systems because they are a
variable-speed scroll designed specically for air
conditioning and heat pumps,” says Palucci.
They come with all the features completely
packaged to make it easy to integrate a
variable-speed compressor into our systems.”
With a 3:1 turndown ratio, the VSH compressors
are ideal for dehumidication. “We take
advantage of the variable-speed control to
deliver only the required cooling capacity,”
notes Palucci. “Even in South Carolina, over 90
percent of operating hours occur at part-load
conditions. The turndown ratio allows
compressor speed to be reduced to match lower
capacity requirements. Between the two MAU
designs, we can go from 22 to 7.5 tons and 12 to
4.”
Anytime the compressor can reduce capacity, it
makes the size of the cooling coils
thermodynamically larger,” explains Palucci.
And when the airstream is exposed to more coil
surface area, more water vapor is pulled out of
the air.”
The speed control allows each unit to operate
within +0.2 degrees of setpoint. Fixed-speed
compressors run at full speed and have to be
cycled on/o or use someother capacity-
reduction method that wastes energy -- and
creates more noise.
Noise reduction is a major benet in a hospital
setting. In the evenings, when sound is critical
and loads are typically low, the VSH compressors
operate at their slowest and quietest -- unlike
xed-speed compressors that frequently cycle
on and o. The VSH drive controller also
provides a soft start that ramps up the inrush
current slowly. Avoiding a huge amperage surge
makes it easier on the motor winding, thus
extending the life of the motor.
Reliability of the Annexair MAU design is also
enhanced because the air-to-air design’s heat
exchangers involve no moving parts, use no
external connections to water or glycol loops,
and do not use a heat-transfer uid that could
be subject to freezing.
“We prefer VSH series compressors
for our dedicated MAU systems
because they are avariable-speed
scroll designed specifically for air
conditioning and heat pumps. They
come with all the features completely
packaged to make it easy to integrate
a variablespeed compressor into our
systems.”
Anthony Palucci, director of sales
for Annexair
www.danfoss.us
The facility went through some scorching
summer heat with these units,” says Palucci. “But
a 100 percent dedicated air-to-air MAU design is
ideal for this application. The units can hit
temperature and humidity setpoints exactly.
And compared to the old, generic units they
replaced, they’re using a lot less electricity. In
fact, with the continuous energy savings from
the air-to-air heat exchangers and VSH
compressors, the expected payback is less than
three years. Conventional units have no
payback. Recuperative air-to-air
dehumidication technology is obviously a
great t for KershawHealth Medical Center.
  • Page 1 1
  • Page 2 2

Danfoss Case Story - Medical Centers Keep Cool User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI