Skov DOL 61 Display and Alarm Unit Technical User Guide

Type
Technical User Guide
www.dol-sensors.com
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
DOL 61
DISPLAY AND ALARM UNIT
TECHNICAL USER GUIDE
For other language variants of
this document we refer to www.dol-
sensors.com or your local dealer.
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
PRODUCT DESCRIPTION
DOL 61 Display and Alarm Unit can be used
with all sensors with 24VDC supply voltage and
0-10VDC or 0-20mADC outputs. DOL 61
features a relay, that can be programmed to
activate when a specific input criterion is met.
The relays can for example be used to sound
a horn or flash a lamp when the ammonia level
in a house exceeds 50ppm.
DOL 61 is capable of powering a sensor with
24VDC.
POWER SUPPLY
Mains connection.
ELECTRIC CONNECTIONS
USB port
USB port for of USB memory stick.
Mini SD card
Placement of Mini SD card.
Sensor Interface
1: GND
2: Analog input (0-10VDC or 0-20mADC)
3: 24VDC
Jumper selection of 0-10VDC or 0-
20mADC analogue input
ON: 0-20mADC
OFF: 0-10VDC
Relays
C1: Relay COM connection
S1: Relay NO connection
C2, S2, C3, S3, C4 & S4 is not used.
TECHNICAL DATA
100-240VAC
50/60Hz
<110 mA @ 230VAC
24VDC ±5% 40mA
Max current 100mA
0-10VDC or 0-
20mADC, to be
selected by jumper
Com. Make
10A @ 125VAC
5A @ 30VDC
5A @ 250VAC
Data output
Mini SD-card
(included). Stores
data for up to 300
days (continuously
deleted). Data is
stored with one
decimal every 30
seconds.
0 oC to +45 oC
10% to 90% RH
700 hPa to 1300
hPa
-20 oC to +60 oC
Mechanical properties
H x W x D: 152 x
162 x 261 mm
800g
Typical detergents,
disinfectants,
alcohol, surfactants,
peracetic acid, soap
IP 56
CE
Power supply:
L: 230VAC phase
N: 230VAC null
USB port
Switch:
0-10V or 0-20mA
Sensor
connection
Relays
Mini SD card
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
TECHNICAL USER GUIDE
1. FRONT MENU OVERVIEW
1: Status measurement
2: Current measurement
3: Channel (analogue input) 1-1
4: History
5: Configurations
6: Current date/year
7: Current time
2. FRONT MENU
The front view displays the measured values from the sensor.
When Threshold 1 is exceeded, the status changes from green to orange .
When Threshold 2 is exceeded, the status is shown as red .
DOL 61 supports one channel.
There is also access to the history view and the configuration menu .
The current date and time is also shown.
3. HISTORY
The history view shows the measured values during the current week. Switch between
weeks by means of the arrows , .
4. CONFIGURATIONS
In the configurations menu, all settings can be made. Tap a field to be able to make settings.
Settings are stored by means of the save button .
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
4.1 CONFIGURATIONS NUMBER OF CHANNELS
DOL 61 supports one channel/one sensor.
Settings are stored with the save button .
To return to the configuration menu, tap the close button .If you do not save the settings before
returning to the configurations menu, the settings are deleted.
4.2 CONFIGURATIONS SETTING CHANNEL
Make settings for the channel/sensor. Tap the pencil to rename it.
Select the unit of measure (Unit), the upper and lower limit for the sensor measurement range
(Scaling) as well as the thresholds.
If the input is changed from 0-10VDC to 0-20mA, the scaling for 0mA must be set at “Scaling 0V”
and 20mA at “Scaling 10V”.
When Threshold 1 is exceeded, the status changes from green to orange .
When Threshold 2 is exceeded, the status is shown as red .
Both Thresholds are set according to the scaling for the input.
RELAY
When threshold 2 is exceeded, the relay changes.
Value on channel 1 below threshold 2, shorted relay.
Value on channel 1 above threshold 2, open relay.
No power connected to DOL 61, open relay.
4.3 CONFIGURATIONS LANGUAGE
Here you can select the displayed language.
4.4 CONFIGURATIONS SYSTEM DATE
Here you can set the date and time (DD/MM/YYYY).
4.5 CONFIGURATIONS SYSTEM TIME
Here you can set the system time (hh/mm).
4.6 CONFIGURATIONS DATA ON USB
In this menu, the measured values which are saved on the Mini SD card can be copied to a
USB stick. This is done to avoid losing data, when the Mini SD card is removed.
4.7 CONFIGURATIONS RESTART
Tapping Restart resets the unit to default.TECHNICAL USER GUIDE
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
4.8 CONFIGURATIONS UPDATE SOFTWARE
In this menu, the software can be updated from a USB stick.
The files must be stored on a stick in a folder named “bin” (Stick:/bin/).
The update function lists the firmware-files (.bin) when starting it.
If more than five files are stored, you can navigate between them using the arrow buttons. Pushing
the up button while placed at the top of the list, scans the folder again.
If no stick is detected, the stick must be removed and connected again, push the up button to re-
scan the folder.
When a file is selected, it can be installed by pushing the button .
The text „Install…“ shows that the installation is active. The selection is displayed again after a
successful installation.
Push the play button to make the application start.
4.9 CONFIGURATIONS DECIMAL SEPARATOR
Here the decimal separator can be set for the data logged on the SD-card/USB stick, the
decimal separator on the screen is always a dot.
4.10 CONFIGURATIONS ABOUT
Here the current unit version is displayed.
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
TECHNICAL USER GUIDE
dol sensors Hedelund 4, Glyngøre 7870 Roslev Denmark Tlf. +45 72 17 58 88 Fax +45 72 17 59 59 www.dol-sensors.com
f
2018.06.14 • 604307 • 16.20 • EN • Made in Denmark
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Skov DOL 61 Display and Alarm Unit Technical User Guide

Type
Technical User Guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI