Danfoss ECL Comfort 310, A376 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 310, A376 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort310,applicationA376
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................12
2.3Mounting...........................................................13
2.4Placingthetemperaturesensors................................17
2.5Electricalconnections.............................................19
2.6InsertingtheECLApplicationKey..............................28
2.7Checklist............................................................34
2.8Navigation,ECLApplicationKeyA376.........................35
3.0Dailyuse.........................................................50
3.1Howtonavigate...................................................50
3.2Understandingthecontrollerdisplay..........................51
3.3Ageneraloverview:Whatdothesymbolsmean?...........55
3.4Monitoringtemperaturesandsystem
components........................................................56
3.5Influenceoverview................................................57
3.6Manualcontrol.....................................................58
3.7Schedule............................................................59
4.0Settingsoverview............................................60
5.0Settings...........................................................63
5.1IntroductiontoSettings..........................................63
5.2Flowtemperature..................................................64
5.3Roomlimit..........................................................67
5.4Returnlimit.........................................................69
5.5Flow/powerlimit.................................................75
5.6Optimization........................................................79
5.7Controlparameters................................................86
5.8Application.........................................................93
5.9Heatcut-out......................................................101
5.10Alarm..............................................................104
5.11Alarmoverview..................................................112
5.12Anti-bacteria......................................................113
5.13Watermeter......................................................115
6.0Commoncontrollersettings............................116
6.1Introductionto‘Commoncontrollersettings..............116
6.2Time&Date.......................................................117
6.3Scheduleoutput.................................................118
6.4Holiday............................................................119
6.5Inputoverview...................................................121
6.6Log.................................................................122
6.7Outputoverride..................................................123
6.8Keyfunctions.....................................................125
6.9System.............................................................127
7.0Miscellaneous................................................134
7.1ECA30/31setupprocedures.................................134
7.2Overridefunction................................................142
7.3Severalcontrollersinthesamesystem......................145
7.4Frequentlyaskedquestions....................................148
7.5Definitions........................................................151
7.6Type(ID6001),overview.......................................154
7.7ParameterIDoverview..........................................155
©Danfoss|2017.11VI.GU.B3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA376
(ordercodeno.087H3810).
TheECLApplicationKeyA376contains6subtypes,allapplicablein
ECLComfort310:
A376.1:2xHeatingand1xDHW
A376.2:2xHeatingand1xadvancedDHW
A376.3:2xHeatingand1xDHW;motorizedcontrolvalves
are0-10Voltcontrolled
A376.4:1xHeating,1xDHWand1xadvancedDHW
A376.9:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xDHWinclusivereturntemperaturelimitation/monitoring.
Monitoringofinstallation'ssupplyandreturntemperatures.
A376.10:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xDHWinclusivereturntemperaturelimitation/monitoring.
Monitoringofinstallation'ssupplyandreturnpressures.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310which
includesM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA376complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartforECLComfort310:
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.GU.B3.02
©Danfoss|2017.11|3
OperatingGuideECLComfort310,applicationA376
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.GU.B3.02
©Danfoss|2017.11|5
OperatingGuideECLComfort310,applicationA376
2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheA376applicationkeyarealmost
identical.However,someapplicationshaveextrafunctionswhich
aredescribedseparately.
Theapplicationsareveryflexible.Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.Bymeansofaweek
schedule,theheatingcircuitcanbein‘Comfort’or‘Savingmode
(twovaluesforthedesiredroomtemperature).InSavingmodethe
heatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
A376.1,A376.2,A376.3,A376.4:
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
TypicalA376application:
Theshowndiagramisafundamentalandsimplifiedexampleand
doesnotcontainallcomponentsthatarenecessaryinasystem.The
numbersincirclesrefertothecircuitnumbers.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:A376ingeneral,sensors
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
A376.1,A376.2,A376.3,A376.4:
Roomtemperaturesensor,circuit1
A376.2:Roomtemperaturesensor,circuits1and2
A376.9:Returntemperaturesensor,monitoring,circuit1
A376.10:Returntemperaturesensor,monitoring,circuit2
S3
Flowtemperaturesensor,circuit1
S4
DHWtemperaturesensor,circuit3
S5
Returntemperaturesensor,circuit1
S6
Returntemperaturesensor,circuit3
S7
A376.1,A376.3:Roomtemperaturesensor,circuit2
A376.2,A376.4:Supplyflowtemperaturesensor
A376.9,A376.10:Pressuresignal
S8
A376.2,A376.4:Flowswitch,DHWdraw-off
A376.9,A376.10:Alarminput
S9
Flowtemperaturesensor,circuit2
S10
A376.1,A376.2,A376.3,A376.4:
Returntemperaturesensor,circuit2
A376.9,A376.10:
Returntemperaturesensor,monitoring,circuit2
(S11)
(A376.9:Supplyflowtemperaturesensor)
A376.10:Supplyflowpressuresignal
(S12)
A376.9:Supplyreturntemperaturesensor
A376.10:Supplyreturnpressuresignal
(S13)
A376.9,A376.10:Returntemperaturesensor,circuit2
(S14)
A376.9,A376.10:Pressuresignal
(S15)
A376.9,A376.10:Alarminput
(S16)
A376.9,A376.10:Alarminput
6|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
Heating(circuit2inA376.1,A376.2,A376.3,A376.9,A376.10)
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS9isthemostimportantsensor.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),
heatingcircuit2canbeinComfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredroomtemperature).Themotorized
controlvalveM3controlsthecircuit.
Thereturntemperature(S10)enableslimitationasdescribed
previously.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
Thecirculationpump(P3)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the
desiredflowtemperatureatS3canbeinfluencedbythedesired
flowtemperatureatS9.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
A376.1,A376.2,A376.3,A376.4:
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Heatingrelatedcircuits,ingeneral:
Exerciseofcirculationpumpsandcontrolvalvesinperiodswithout
heatingdemandcanbearranged.
Listofcomponents:A376ingeneral,pumpsandactuators
P1
DHWcirculationpump,circuit3
P2
Heatingcirculationpump,circuit1
P3
A376.1,A376.2,A376.3,A376.9,A376.10:
Heatingcirculationpump,circuit2
A376.4:DHWcirculationpump,circuit2
M1
Motorizedcontrolvalve,circuit3
M2
Motorizedcontrolvalve,circuit1
M3
Motorizedcontrolvalve,circuit2
A1
Alarm
A376.1examplea:
A376.1exampleb:
VI.GU.B3.02
©Danfoss|2017.11|7
OperatingGuideECLComfort310,applicationA376
DomesticHotWater(DHW)
A376.1,A376.2,A376.3,A376.9,A376.10:Circuit3
A376.4:Circuit2
IfthemeasuredDHWtemperature(S4/S9)islowerthanthe
desiredDHWtemperature,themotorizedcontrolvalve(M1/M3)is
openedgraduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
Thereturntemperature(S6/S10)canbelimitedtoafixedvalue.
A376.9,A376.10:
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
DomesticHotWater(DHW),advancedtemperaturecontrol
A376.2,A376.4:Circuit3
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TheDHWtemperatureatS4ismaintainedat‘Comfort’levelata
DHWdraw-off(DHWtapping)(theflowswitchS8isactivated).If
themeasuredDHWtemperatureS4islowerthanthedesiredDHW
temperature,themotorizedcontrolvalve(M1)isopenedgradually
andviceversa.TheDHWtemperaturecontrolisinrelationto
actualsupplytemperatureS7.Inordertocompensateforthe
reactiontime,themotorizedcontrolvalvecanbepre-activatedat
thestartofaDHWdraw-off(DHWtapping).Anidletemperature
(thedesiredsavingtemperature)canbemaintainedateitherS7or
S4whenthereisnodraw-off(DHWtapping).
Thereturntemperature(S6)canbelimitedtoafixedvalue.
DHWcircuits,ingeneral
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Theoutdoortemperature(S1)isusedtoprotectthecirculation
circuit(s)againstfrost.
A376.2examplea:
A376.2exampleb:
A376.3examplea:
8|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ApplicationA376.3ingeneral:
TheapplicationissimilartotheA376.1application,butthe
motorizedcontrolvalvesarecontrolledbymeansof0-10volt
signals(analogsignals).Thetriacoutputsarenotactivefor
activating3-pointcontrolledactuators.TheapplicationA376.3
requirestheinternalI/OmoduleECA32inordertoactivate0-10
voltcontrolledactuators.
ApplicationA376.4,ingeneral
Theheatingcircuit(1)andDHWcircuit(3)aresimilartotheA376.2
application.TheDHWcircuit2issimilartotheDHWcircuitinthe
A376.1application.
ApplicationA376.9ingeneral:
TheapplicationA376.9issimilartotheA376.1,butwithspecial
functions.
TheapplicationA376.9requirestheinternalI/OmoduleECA32.
S11andS12measuresupplyflowandreturntemperaturesfor
monitoring.
S13measuresreturntemperature.
S14measurespressure.
S15andS16arealarminputs.
Schedulein"Commoncontroller"isconnectedtotheoutputO1
andcanbeusedforvariousissues.
Heatingcircuits1and2:
Therearenoroomtemperatureinfluencepossibilities.
Thesecondaryreturntemperatures(S2andS10)areusedfor
monitoringonly.
Thepressuremeasurings,0-10volt(S7andS14,)areusedto
activateanalarmiftheactualpressureishigherorlowerthan
thechosensettings.
DHWcircuit3:
ThereturntemperatureS6canmeasure,formonitoring
purpose,thereturntemperatureonthesecondaryside.An
alternativepositionforS6canbeinthereturnontheprimary
sideinordertolimitthereturntemperaturetoafixedvalue.
A376.3exampleb:
A376.4examplea:
A376.9examplea:
VI.GU.B3.02
©Danfoss|2017.11|9
OperatingGuideECLComfort310,applicationA376
Allcircuits:
Thetemperatures(S11andS12)areusedformonitoringonly.
Theswitchinputs(S8,S15andS16)arerelatedtothecircuits
1,2and3respectively.Typicallyusedasalarmsignalfor
malfunctionofthecirculationpumpinquestion.
ApplicationA376.10
TheapplicationA376.10issimilartotheA376.9.
TheapplicationA376.10requirestheinternalI/OmoduleECA32.
S11andS12measuresupplyflowandreturnpressuresfor
monitoring.
S13measuresreturntemperature.
S14measurespressure.
S15andS16arealarminputs.
Schedulein"Commoncontroller"isconnectedtotheoutputO1
andcanbeusedforvariousissues.
A376.9exampleb:
A376.10examplea:
10|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ApplicationA376ingeneral:
ThealarmoutputA1ispresentontheseoutputs:
Application:Relay:
A376.1,A376.2,A376.3,A376.4
Relay6
A376.9,A376.10
Relay4
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
ModbuscommunicationtoaSCADAsystemcanbeestablished.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkinmaster-
slavesystem.
Unusedinputscan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving' ,
'Frostprotection'or'Constanttemperature'mode.
Circuit1canactasmasterandtheremainingcircuitscanactas
slaves.
HolidayprogramsarepresentforHeatingandDHWcircuits.
Besides,aholidayprogramispresentfortheentirecontroller.
WhentheA376hasbeenuploadedwiththesubtypesA376.1,
A376.2,A376.3andA376.4,theECLComfortcontrollerstarts
inManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
ThesubtypesA376.9andA376.10start,afterupload,inScheduled
mode.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.GU.B3.02
©Danfoss|2017.11|11
OperatingGuideECLComfort310,applicationA376
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
Advicesforsettings:
Whencircuit1mustbeabletoreceiveaheatdemandfromcircuit
2,circuit3oraslave:
MENU\Settings\Application:'Demandoffset'(ID11017):3K*
WhenaheatingorDHWcircuitmustbeabletosenditsheat
demandtocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):ON
WhenaheatingorDHWcircuitshouldnotsenditsheatdemand
tocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):OFF
*Thisrecommendedvalueisaddedtotheheatdemandvaluefrom
circuit2,circuit3ortheslave;alwaysthehighestdemand.
12|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.GU.B3.02
©Danfoss|2017.11|13
OperatingGuideECLComfort310,applicationA376
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
14|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.GU.B3.02
©Danfoss|2017.11|15
OperatingGuideECLComfort310,applicationA376
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
16|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.GU.B3.02
©Danfoss|2017.11|17
OperatingGuideECLComfort310,applicationA376
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
18|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
VI.GU.B3.02
©Danfoss|2017.11|19
OperatingGuideECLComfort310,applicationA376
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
0,2A/230Va.c.
20|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
/