Danfoss ECL Comfort 310, A376 Operating instructions

Type
Operating instructions
OperatingGuide
ECLComfort310,applicationA376
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................12
2.3Mounting...........................................................13
2.4Placingthetemperaturesensors................................17
2.5Electricalconnections.............................................19
2.6InsertingtheECLApplicationKey..............................28
2.7Checklist............................................................34
2.8Navigation,ECLApplicationKeyA376.........................35
3.0Dailyuse.........................................................50
3.1Howtonavigate...................................................50
3.2Understandingthecontrollerdisplay..........................51
3.3Ageneraloverview:Whatdothesymbolsmean?...........55
3.4Monitoringtemperaturesandsystem
components........................................................56
3.5Influenceoverview................................................57
3.6Manualcontrol.....................................................58
3.7Schedule............................................................59
4.0Settingsoverview............................................60
5.0Settings...........................................................63
5.1IntroductiontoSettings..........................................63
5.2Flowtemperature..................................................64
5.3Roomlimit..........................................................67
5.4Returnlimit.........................................................69
5.5Flow/powerlimit.................................................75
5.6Optimization........................................................79
5.7Controlparameters................................................86
5.8Application.........................................................93
5.9Heatcut-out......................................................101
5.10Alarm..............................................................104
5.11Alarmoverview..................................................112
5.12Anti-bacteria......................................................113
5.13Watermeter......................................................115
6.0Commoncontrollersettings............................116
6.1Introductionto‘Commoncontrollersettings..............116
6.2Time&Date.......................................................117
6.3Scheduleoutput.................................................118
6.4Holiday............................................................119
6.5Inputoverview...................................................121
6.6Log.................................................................122
6.7Outputoverride..................................................123
6.8Keyfunctions.....................................................125
6.9System.............................................................127
7.0Miscellaneous................................................134
7.1ECA30/31setupprocedures.................................134
7.2Overridefunction................................................142
7.3Severalcontrollersinthesamesystem......................145
7.4Frequentlyaskedquestions....................................148
7.5Definitions........................................................151
7.6Type(ID6001),overview.......................................154
7.7ParameterIDoverview..........................................155
©Danfoss|2017.11VI.GU.B3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA376
(ordercodeno.087H3810).
TheECLApplicationKeyA376contains6subtypes,allapplicablein
ECLComfort310:
A376.1:2xHeatingand1xDHW
A376.2:2xHeatingand1xadvancedDHW
A376.3:2xHeatingand1xDHW;motorizedcontrolvalves
are0-10Voltcontrolled
A376.4:1xHeating,1xDHWand1xadvancedDHW
A376.9:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xDHWinclusivereturntemperaturelimitation/monitoring.
Monitoringofinstallation'ssupplyandreturntemperatures.
A376.10:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xDHWinclusivereturntemperaturelimitation/monitoring.
Monitoringofinstallation'ssupplyandreturnpressures.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310which
includesM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA376complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartforECLComfort310:
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.GU.B3.02
©Danfoss|2017.11|3
OperatingGuideECLComfort310,applicationA376
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.GU.B3.02
©Danfoss|2017.11|5
OperatingGuideECLComfort310,applicationA376
2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheA376applicationkeyarealmost
identical.However,someapplicationshaveextrafunctionswhich
aredescribedseparately.
Theapplicationsareveryflexible.Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.Bymeansofaweek
schedule,theheatingcircuitcanbein‘Comfort’or‘Savingmode
(twovaluesforthedesiredroomtemperature).InSavingmodethe
heatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
A376.1,A376.2,A376.3,A376.4:
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
TypicalA376application:
Theshowndiagramisafundamentalandsimplifiedexampleand
doesnotcontainallcomponentsthatarenecessaryinasystem.The
numbersincirclesrefertothecircuitnumbers.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:A376ingeneral,sensors
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
A376.1,A376.2,A376.3,A376.4:
Roomtemperaturesensor,circuit1
A376.2:Roomtemperaturesensor,circuits1and2
A376.9:Returntemperaturesensor,monitoring,circuit1
A376.10:Returntemperaturesensor,monitoring,circuit2
S3
Flowtemperaturesensor,circuit1
S4
DHWtemperaturesensor,circuit3
S5
Returntemperaturesensor,circuit1
S6
Returntemperaturesensor,circuit3
S7
A376.1,A376.3:Roomtemperaturesensor,circuit2
A376.2,A376.4:Supplyflowtemperaturesensor
A376.9,A376.10:Pressuresignal
S8
A376.2,A376.4:Flowswitch,DHWdraw-off
A376.9,A376.10:Alarminput
S9
Flowtemperaturesensor,circuit2
S10
A376.1,A376.2,A376.3,A376.4:
Returntemperaturesensor,circuit2
A376.9,A376.10:
Returntemperaturesensor,monitoring,circuit2
(S11)
(A376.9:Supplyflowtemperaturesensor)
A376.10:Supplyflowpressuresignal
(S12)
A376.9:Supplyreturntemperaturesensor
A376.10:Supplyreturnpressuresignal
(S13)
A376.9,A376.10:Returntemperaturesensor,circuit2
(S14)
A376.9,A376.10:Pressuresignal
(S15)
A376.9,A376.10:Alarminput
(S16)
A376.9,A376.10:Alarminput
6|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
Heating(circuit2inA376.1,A376.2,A376.3,A376.9,A376.10)
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS9isthemostimportantsensor.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),
heatingcircuit2canbeinComfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredroomtemperature).Themotorized
controlvalveM3controlsthecircuit.
Thereturntemperature(S10)enableslimitationasdescribed
previously.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
Thecirculationpump(P3)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the
desiredflowtemperatureatS3canbeinfluencedbythedesired
flowtemperatureatS9.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
A376.1,A376.2,A376.3,A376.4:
Ifthemeasuredroomtemperaturedoesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Heatingrelatedcircuits,ingeneral:
Exerciseofcirculationpumpsandcontrolvalvesinperiodswithout
heatingdemandcanbearranged.
Listofcomponents:A376ingeneral,pumpsandactuators
P1
DHWcirculationpump,circuit3
P2
Heatingcirculationpump,circuit1
P3
A376.1,A376.2,A376.3,A376.9,A376.10:
Heatingcirculationpump,circuit2
A376.4:DHWcirculationpump,circuit2
M1
Motorizedcontrolvalve,circuit3
M2
Motorizedcontrolvalve,circuit1
M3
Motorizedcontrolvalve,circuit2
A1
Alarm
A376.1examplea:
A376.1exampleb:
VI.GU.B3.02
©Danfoss|2017.11|7
OperatingGuideECLComfort310,applicationA376
DomesticHotWater(DHW)
A376.1,A376.2,A376.3,A376.9,A376.10:Circuit3
A376.4:Circuit2
IfthemeasuredDHWtemperature(S4/S9)islowerthanthe
desiredDHWtemperature,themotorizedcontrolvalve(M1/M3)is
openedgraduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
Thereturntemperature(S6/S10)canbelimitedtoafixedvalue.
A376.9,A376.10:
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
DomesticHotWater(DHW),advancedtemperaturecontrol
A376.2,A376.4:Circuit3
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
TheDHWtemperatureatS4ismaintainedat‘Comfort’levelata
DHWdraw-off(DHWtapping)(theflowswitchS8isactivated).If
themeasuredDHWtemperatureS4islowerthanthedesiredDHW
temperature,themotorizedcontrolvalve(M1)isopenedgradually
andviceversa.TheDHWtemperaturecontrolisinrelationto
actualsupplytemperatureS7.Inordertocompensateforthe
reactiontime,themotorizedcontrolvalvecanbepre-activatedat
thestartofaDHWdraw-off(DHWtapping).Anidletemperature
(thedesiredsavingtemperature)canbemaintainedateitherS7or
S4whenthereisnodraw-off(DHWtapping).
Thereturntemperature(S6)canbelimitedtoafixedvalue.
DHWcircuits,ingeneral
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Theoutdoortemperature(S1)isusedtoprotectthecirculation
circuit(s)againstfrost.
A376.2examplea:
A376.2exampleb:
A376.3examplea:
8|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ApplicationA376.3ingeneral:
TheapplicationissimilartotheA376.1application,butthe
motorizedcontrolvalvesarecontrolledbymeansof0-10volt
signals(analogsignals).Thetriacoutputsarenotactivefor
activating3-pointcontrolledactuators.TheapplicationA376.3
requirestheinternalI/OmoduleECA32inordertoactivate0-10
voltcontrolledactuators.
ApplicationA376.4,ingeneral
Theheatingcircuit(1)andDHWcircuit(3)aresimilartotheA376.2
application.TheDHWcircuit2issimilartotheDHWcircuitinthe
A376.1application.
ApplicationA376.9ingeneral:
TheapplicationA376.9issimilartotheA376.1,butwithspecial
functions.
TheapplicationA376.9requirestheinternalI/OmoduleECA32.
S11andS12measuresupplyflowandreturntemperaturesfor
monitoring.
S13measuresreturntemperature.
S14measurespressure.
S15andS16arealarminputs.
Schedulein"Commoncontroller"isconnectedtotheoutputO1
andcanbeusedforvariousissues.
Heatingcircuits1and2:
Therearenoroomtemperatureinfluencepossibilities.
Thesecondaryreturntemperatures(S2andS10)areusedfor
monitoringonly.
Thepressuremeasurings,0-10volt(S7andS14,)areusedto
activateanalarmiftheactualpressureishigherorlowerthan
thechosensettings.
DHWcircuit3:
ThereturntemperatureS6canmeasure,formonitoring
purpose,thereturntemperatureonthesecondaryside.An
alternativepositionforS6canbeinthereturnontheprimary
sideinordertolimitthereturntemperaturetoafixedvalue.
A376.3exampleb:
A376.4examplea:
A376.9examplea:
VI.GU.B3.02
©Danfoss|2017.11|9
OperatingGuideECLComfort310,applicationA376
Allcircuits:
Thetemperatures(S11andS12)areusedformonitoringonly.
Theswitchinputs(S8,S15andS16)arerelatedtothecircuits
1,2and3respectively.Typicallyusedasalarmsignalfor
malfunctionofthecirculationpumpinquestion.
ApplicationA376.10
TheapplicationA376.10issimilartotheA376.9.
TheapplicationA376.10requirestheinternalI/OmoduleECA32.
S11andS12measuresupplyflowandreturnpressuresfor
monitoring.
S13measuresreturntemperature.
S14measurespressure.
S15andS16arealarminputs.
Schedulein"Commoncontroller"isconnectedtotheoutputO1
andcanbeusedforvariousissues.
A376.9exampleb:
A376.10examplea:
10|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
ApplicationA376ingeneral:
ThealarmoutputA1ispresentontheseoutputs:
Application:Relay:
A376.1,A376.2,A376.3,A376.4
Relay6
A376.9,A376.10
Relay4
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
ModbuscommunicationtoaSCADAsystemcanbeestablished.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkinmaster-
slavesystem.
Unusedinputscan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving' ,
'Frostprotection'or'Constanttemperature'mode.
Circuit1canactasmasterandtheremainingcircuitscanactas
slaves.
HolidayprogramsarepresentforHeatingandDHWcircuits.
Besides,aholidayprogramispresentfortheentirecontroller.
WhentheA376hasbeenuploadedwiththesubtypesA376.1,
A376.2,A376.3andA376.4,theECLComfortcontrollerstarts
inManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
ThesubtypesA376.9andA376.10start,afterupload,inScheduled
mode.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.GU.B3.02
©Danfoss|2017.11|11
OperatingGuideECLComfort310,applicationA376
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
Advicesforsettings:
Whencircuit1mustbeabletoreceiveaheatdemandfromcircuit
2,circuit3oraslave:
MENU\Settings\Application:'Demandoffset'(ID11017):3K*
WhenaheatingorDHWcircuitmustbeabletosenditsheat
demandtocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):ON
WhenaheatingorDHWcircuitshouldnotsenditsheatdemand
tocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):OFF
*Thisrecommendedvalueisaddedtotheheatdemandvaluefrom
circuit2,circuit3ortheslave;alwaysthehighestdemand.
12|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.GU.B3.02
©Danfoss|2017.11|13
OperatingGuideECLComfort310,applicationA376
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
14|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.GU.B3.02
©Danfoss|2017.11|15
OperatingGuideECLComfort310,applicationA376
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
16|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.GU.B3.02
©Danfoss|2017.11|17
OperatingGuideECLComfort310,applicationA376
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
18|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
VI.GU.B3.02
©Danfoss|2017.11|19
OperatingGuideECLComfort310,applicationA376
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
0,2A/230Va.c.
20|©Danfoss|2017.11
VI.GU.B3.02
OperatingGuideECLComfort310,applicationA376
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163