Legrand Emergency Shunt Relay Installation guide

Category
Network switches
Type
Installation guide

This manual is also suitable for

Wattstopper
®
Emergency Shunt Relay
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
IS-00726– 04/20 rev. 2
AD-RRU-X-UNV • Les Numéros de Catalogue • Los Números de Catálogo:
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
OVERVIEW
SAFETY INSTRUCTIONS
In the past, all emergency lights were left on 24 hours a day to meet safety codes. The Emergency Shunt Relay converts up to 20A of
normal light fixtures to approved emergency lights. During normal operation, the AD-RRU-X-UNV dims designated emergency lights
with the same control as normal lights. During a utility power interruption, the AD-RRU-X-UNV turns designated emergency lights on, at
ful lbrightness, regardless of dimmer position. An Emergency Shunt Relay requires a dedicated switch/dimmer to control the emergency
lights. In other words, the switch/dimmer must be wired on the emergency power circuit.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! When using electrical equipment, basic safety precautions should always be
followed, including the following:
1. This product can be used with LED, ballast, tungsten, and general use loads.
2. Make sure all connections are in accordance with the National Electrical Code and local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before servicing.
4. This product is intended to be used to control indoor and outdoor located loads.
5. An unswitched AC power source is required (120-240VAC/277VAC).
6. Do not install near gas or electric heaters.
7. Do not attempt to service a sealed Emergency Power Control. When malfunctioning, return to Legrand
8. The use of accessory equipment is not recommended by the manufacturer and may cause unsafe condition.
9. Do not use this product for other than its intended use.
10. Servicing should be performed by qualified service personnel.
11. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized
personnel.
EMERGENCY
POWER
UTILITY
POWER
TEST
SPECIFICATIONS
Mechanical Specifications:
Mounting ........... 4-11/16” Junction box with extension box
Frame ............ Use single gang plaster ring or blank cover
Installation ...............Suitable for installation in the plenum
Plastic Flame Rating ...........UL94-5VA, Tested to UL2043
Shipping Weight .........................................................8 oz.
Color ......................................................................... White
Operating Temperature .............-40° - 149°F (-40° - 65°C)
Flush Mounted Size ...........................4-1/2” x 2-3/4” x 1/4”
Body Size .....................................2-7/8” x 1-3/4” x 1-7/32”
Electrical Specifications:
Sensing Input .....................................................120-277V
Contact ............................... Form C (N.O. + N.C.) Contact
Auxiliary N.O. Contact .......................................1A/30VDC
20 Amp Ballast Load Rating ............................... 120-277V
20 Amp General Use Rating...............................120-277V
1200W Incandescent Load Rating ............................ 120V
1500W Incandescent Load Rating ............................ 277V
UL Listing .................................. UL 924 Listed (usUL/cUL)
FIRE ALARM / REMOTE TEST SWITCH
Some applications demand that emergency lighting be activated upon fire alarm, security alarm, or remote test switch activation. The
AD-RRU-X-UNV is equipped with a low-voltage override input (red jumper).
2
INSTALLATION
INITIAL TESTING, TROUBLESHOOTING, AND MAINTENANCE
Unique enclosure permits flush, fixture, plenum or panel mounting.
In order to install the RRU in accordance with national/local code requirements, a qualified electrician should review and understand
the installation instructions. Check voltage and current requirements. Verify and lock out circuit breakers on both regular (utility) power
and 24 hour emergency generator or inverter circuit. Install a self-adhesive 2” x 3” caution label in each fixture or load controlled by an
AD-RRU-X-UNV cautioning that the load is supplied from 2 different power sources, normal and emergency. Review wiring diagram and
connect wires, one at a time, in accordance with the numeric identification. In order to provide a safe light level, when regular power is
interrupted, it is recommended that a minimum of appproximately 5000 lumen are controlled by a 24 hour emergency circuit and are
spaced no farther than 24’ in any direction from each other in a normal 9’ white ceiling environment.
No maintenance is required to keep the RRU functional. However, regular testing should be performed when the lamps or ballasts have
been replaced or when remodeling has taken place.
In a new installation, where hundreds of devices may be used, each having as many as 14 wires to be correctly connected, it is
important that a fast, convenient method is used to check connections. In order to test that the wires are connected correctly, without
any inconvenience to occupants, do not turn off regular (utility) power off until you have checked each device as follows:
1. Check that regular branch circuit breaker is connected and utility power is available. Green LED should be lit. If green LED is not lit,
check connections and continuity to branch circuit breaker.
2. Check that emergency branch circuit breaker is connected and emergency power is available.
3. Normal Operation Test: Turn dimmer or other control device to the “ON” position. Emergency lights should turn on. Reduce
dimmer to ~50%, emergency lights should dim to ~50%. Turn room switch or control to the “OFF” position. Emergency lights should
turn off.
4. Emergency Operation Test: Press and hold test button, emergency lights should illuminate at full brightness until test button is
released.
5. Maintenance: No maintenance is required to keep the RRU functional. However, regular testing should be performed when the
lamps or ballasts have been replace or when remodeling has taken place.
Recommended Box Size
4-11/16” with extension
(total depth 4” minimum)
Confirm body size will fit in
fixture ballast channel prior
to installation
(2-7/8” x 1-3/4” x 1-7/32”)
Recommended Box Size
4-11/16” with extension
(total depth 4” minimum)
Tested to UL2043,
suitable for installation
in the plenum
FLUSH MOUNT JUNCTION BOX FIXTURE MOUNT
WARNING: TURN BREAKERS OFF
AND CHECK THAT NO POWER IS ON
WHEN WORKING IN THE ENCLOSURE
OR RELATED EQUIPMENT.
3
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
+12VDC 250mA
TX1
TX5
Gnd
RX 1
RTS 1
CTS 1
Gnd
TX 2
Port 2
RS-232
36V
Port 3 Port 4 Port 5 Class 2 Bus 2 Bus 3
RS485-1 RS485-2
Bus 4
Station BusController
Bus
Secondary Enclosures
Port 1
Enclosure
Address
Controller Bus
Termination
10s
RX 2
TX 2
RX 2
RTS 2
CTS 2
Gnd
Gnd
TX 2
RX 2
T/R+
T/R+
T/R-
T/R+
T/R-
Override
Gnd
T/R+
T/R-
Gnd
Gnd
T/R-
T/R+
T/R-
Run 1
Gnd
RX 5
Run 2
Main Enclosure Terminal Board
1s
OFF ON
LINE
NEUTRAL
EMERGENCY
POWER
UTILITY
POWER
TEST
BLACK
WHITE
BROWN
(Cap Off)
YELLOW #5
BLUE #4
NORMAL
PANEL
(20 AMP
BREAKER)
LINE NEUTRAL
High Voltage Barrier
(COM-HV-BARRIER)
NORMAL POWER
LINE HOT
(Unswitched)
LCAP44M ENCLOSURE DIAGRAM
1. Mount AD-RRU-X-UNV using double-sided tape that is installed on the AD-RRU-X-UNV to secure in location shown.
2. Cut yellow and blue wires to an appropriate length, then wire the yellow wire (#5) to far right GND terminal and the blue wire (#4) to
the Override terminal.
3. Black wire (#1) and WHITE wire (#2) should not be terminated .This is for the field to install to unswitched normal power.
4. Terminate the brown wire (#3)
See Main Terminal Board Close-Up Diagram
(Next Page)
4
SECONDARY TERMINAL BOARD WIRING DIAGRAM
Secondary Enclosure
Terminal Board
Enclosure
Select
Serial #
Enclosure
Bus
Termination
A B OFF ON
1 2 3 1 2 3
T/R+
T/RB
GND
T/R+
T/RB
GND
Override
Override
EMERGENCY
POWER
UTILITY
POWER
TEST
BLACK - Regular Line Hot (Unswitched)
WHITE - Regular Line NEUTRAL
BROWN - Cap Off
BLUE #4
YELLOW #5
NORMAL
PANEL
20 AMP
BREAKER
AD-RRU-X-UNV
SECONDARY TERMINAL BOARD (VSUB218)
MAIN TERMINAL BOARD WIRING CLOSE-UP DIAGRAM
+12VDC 250mA
TX1
TX5
Gnd
RX 1
RTS 1
CTS 1
Gnd
TX 2
Port 2
RS-232
36V
Port 3 Port 4 Port 5 Class 2 Bus 2 Bus 3
RS485-1 RS485-2
Bus 4
Station BusController
Bus
Secondary Enclosures
Port 1
Enclosure
Address
Controller Bus
Termination
10s
RX 2
TX 2
RX 2
RTS 2
CTS 2
Gnd
Gnd
TX 2
RX 2
T/R+
T/R+
T/R-
T/R+
T/R-
Override
Gnd
T/R+
T/R-
Gnd
Gnd
T/R-
T/R+
T/R-
Run 1
Gnd
RX 5
Run 2
Main Enclosure Terminal Board
1s
OFF ON
LINE
NEUTRAL
BLACK - Regular Line Hot (Unswitched)
WHITE - Regular Line NEUTRAL
BROWN - Cap Off
YELLOW #5
BLUE #4
NORMAL
PANEL
20 AMP
BREAKER
AD-RRU-X-UNV
MAIN TERMINAL BOARD (VSUB215)
EMERGENCY
POWER
UTILITY
POWER
TEST
1. Cut yellow and blue wires to an appropriate length, then wire the yellow wire (#5) to far right GND terminal and the blue wire (#4) to
the Override terminal.
2. Black wire (#1) and WHITE wire (#2) should not be terminated .This is for the field to install to unswitched normal power.
3. Terminate the brown wire (#3)
5
LVOS-0-10-PWM STATION DIAGRAM
The station supports two Override modes, ON and OFF. When either switch is closed ALL loads are ON or OFF depending on which
override loop is closed. However, the ON override takes precedence over the OFF override if both switches are closed. Exmaple below
is all loads ON.
BLACK - Regular Line Hot
(Unswitched)
WHITE - Regular Line
NEUTRAL
BROWN - Cap Off
120VAC
From Breakers
Breaker feeds can be shared as long as the
maximum breaker amperage is not exceeded
LV POS +
LV NEG -
LINE
AC
1
1 2 3 4
STATUS
LOW VOLTAGE OUTPUT STATION-0-10-PWM-DIN
PWM
LVOS-0-10-PWM-DIN
0-10: 10VDC@100mA MAX
PWM: 12VDC@100mA MAX
INPUT
120-277VAC
50/60 Hz
RELAY: 120-277 VAC/5A MAX. INCANDESCENT
STATION
BUS
CLASS 2
ETHERNET
10/100
SERIAL NUMBER
NEUTRAL
NEUTRAL
LINE
LINE
GND
GND
2 3 4
1 2 3
IR
4
SENS
PWM OUTPUTS 0-10 OUTPUTS
10mA
MAX
CONTACT INPUT OVERRIDE
+12V
+12V
GND
GND
ON
GND
OFF
GND
OUT 1
GND
OUT 2
OUT 3
GND
GND
OUT 4
GND
OUT 1
GND
OUT 2
OUT 3
GND
GND
OUT 4
GND
STATION
BUS
CLASS 2
1 2 3 4
0-10
1 2 3 4
RELAY
12awg Stranded
EMERGENCY
POWER
UTILITY
POWER
TEST
LVOS-0-10-PWM
NORMAL
PANEL
20 AMP
BREAKER
AD-RRU-X-UNV
YELLOW #5
BLUE #4
N/C FIRE ALARM CONTACT DIAGRAM
LVS UL924
CONTROL
Red Fire
Alarm Low
Volt Wires
NOTE: DC Power Supply
may be fed by normal or
emergency power, but
emergency is recommended
DC+
DC– / COM
DC POWER
SUPPLY
N/C FIRE ALARM CONTACT
The fire alarm input can be connected to a N/C fire alarm contact rated 100mA, 24VDC or greater (closed during fire event, open during
normal conditions) and a 10V-30VDC power supply rated 1W or greater.
AD-RRU-X-UNV has a fire alarm input with a low-voltage wire red loop. Red loop can be cut and connected as shown above. Red wires
are polarity independent.
6
WIRING DIAGRAM
SINGLE LINE DRAWINGS
AD-RRU-X-UNV
EMERGENCY
POWER
UTILITY
POWER
TEST
AD-RRU-X-UNV
EMERGENCY
POWER
UTILITY
POWER
TEST
AD-RRU-X-UNV
AD-RRU-X-UNV
AD-RRU-X-UNV
EMERGENCY
20 AMP
BREAKER
TO ADDITIONAL
AD-RRU-X-UNV
CONTROLS
NORMAL
POWER
PANEL
UL 1008
TRANSFER
SWITCH or
EQUIVALENT
Normal/Utility
Power Source
Emergency
Power Source
Neutral Not Shown
EMERGENCY
POWER
UTILITY
POWER
TEST
EMERGENCY
POWER
UTILITY
POWER
TEST
EMERGENCY
POWER
UTILITY
POWER
TEST
On a 20 Amp circuit, one emergency power control
(AD-RRU-X-UNV) can control up to 20 Amp of
emergency lighting, or 20 AD-RRU-X-UNVs can each
control one Amp of emergency lighting load. One
AD-RRU-X-UNV is required per switch leg or zone.
EMERGENCY
POWER
PANEL
LIGHTING
CONTROL
DEVICE
(Switch, Sensor, Power
Pack, Relay Panel)
DESIGNATED
EMERGENCY
LIGHTS
TO ADDITIONAL
UL924 CONTROLS
AD-RRU-X-UNV
EMERGENCY
POWER
UTILITY
POWER
TEST
TYPICAL WIRING DIAGRAM
0-10V
Dimmer
Red Jumper
(Fire alarm tie-in or remote
test - See additional resources
for wiring details)
#5 YELLOW #1 BLACK
#2 WHITE
NORMAL HOT
NORMAL NEUTRAL
20A
20A
NORMAL
PANEL
EMERGENCY
PANEL OR
INVERTER
Emergency
Hot
Switch or
Dimmer
Emergency Light
NOTE: Emergency Light is also called N/E Light or Normal/Emergency Light by specifiers
Emergency
Neutral
#4 BLUE
#3 BROWN
EMERGENCY
POWER
UTILITY
POWER
TEST
Violet (+)
Gray (-)
NEUTRAL IN
LINE
OUT
#5 YELLOW #1 BLACK
#2 WHITE
NORMAL
HOT
NORMAL
NEUTRAL
20A
20A
NORMAL
(UTILITY)
PANEL
EMERGENCY
PANEL OR
INVERTER
GRAY
NEUTRAL OUT
VIOLET
LINE IN
EMERGENCY
NEUTRAL
EMERGENCY
HOT
#4
BLUE
#3 BROWN
EMERGENCY
POWER
UTILITY
POWER
TEST
VIOLET
VIOLET
CONTROL UNIT
EMERGENCY LIGHT(S)
GRAY
VIOLET
NEUTRAL HOT/LINE
800.879.8585
www.legrand.us/wattstopper
IS-00726 – 04/20 rev. 2
© Copyright 2020 Legrand All Rights Reserved.
© Copyright 2020 Tous droits réservés Legrand.
© Copyright 2020 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
MULTI-VIEW LINE DRAWING
EMERGENCY
POWER
UTILITY
POWER
TEST
1.25”
1.6875”
3.5”
2.8125”
1.3125”
FRONT
BACKRIGHT SIDELEFT SIDE
BOTTOM
TOP
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

Legrand Emergency Shunt Relay Installation guide

Category
Network switches
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI