Legrand LCAP32M Installation guide

Type
Installation guide
Wattstopper
®
Commercial Power Enclosure Solutions and Main Lug Options
French Description
Spanish Description
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: IS-00706 – rev. 7
LCAP32M/S and LCAP 44M/S • Les Numéros de Catalogue • Los Números de Catálogo:
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
SOLUTION 1 - PARENT-LEVEL ENCLOSURE MODELS
OVERVIEW
The Wattstopper LCAP Series Commercial Enclosures ship with pre-congured modular solutions.
Load dimming and switching use Vantage™ controllers and switching products. The pre-congured
designs save time in Vantage’s Design Center™ software and during the installation process.
The LCAP32/44M/S series offers one of the highest amperage dimming and switching options in
the LCAP enclosure line. Vantage’s own forward and reverse phase dimming, use, patent pending,
individual load linearization curve settings. Each dimmed load’s starting/stopping points can also be
set. This technology is exclusive with Vantage and allows for smooth dimming and consistent lighting
using mixed lighting types and brands. The LCAP32/44M/S enclosures may be connected to other
LCAP enclosures and Vantage enclosures; scalable to virtually any size system. IMPORTANT: See
page 7 for optional Main Lug / circuit breaker models.
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Enclosure Bus
Termination
OFFON
Enclosure
Select
AB
Secondary Enclosure
Terminal Board
T/R+
T/R B
GND
Override
T/R+
T/R B
GND
Override
Main Enclosure Description
LCAP44 44” Architectural Enclosure
LCAP32 32” Architectural Enclosure
LCAP32/44M/S Panel Congurations
LCAP32/44M (contains controller)
LCAP32/44S (contains Secondary Terminal Board)
KIT part numbers / Ordering Key, page 5
Panel Load Section:
LCAP44M/S, up to 4 Modules
LCAP32M/S, up to 2 Modules
Panel Controller Section:
(1) IC-36-II Controller
-OR-
(1) Secondary Terminal Board
Optional Parts Description
COM-HV-BARRIER Low-voltage Barrier
VA-RRU-1-120V Emergency Shunt Relay - 120V
VA-RRU-1-277V Emergency Shunt Relay - 277V
Additional Parts Order Separately Description
VA-EPC-DFS-120V Emergency Lighting Surface Mount Switch 120V
VA-EPC-DFS-277V Emergency Lighting Surface Mount Switch 277V
Part Number
Breakdown
Enclosure and Lid
ONLY
Panel
Type
LCAP32/44/M/S Optional Modules
LCAP32/44M/S With Module Options Module Type Location 1-4
Actual PN
Important See Ordering Key and Kit Part Numbers (pg. 5)
2
IS-00706 – Rev. 7
*InFusion controllers have a micro-SD ash card port for backup. Please see InFusion Controller Instruction Sheet for more details.
For module and emergency switch install sheet information, visit the Vantage Dealer Site.
LCAP M/S SERIES SPECIFICATIONS
LCAP ENCLOSURE DESIGNS
Specications LCAP32M / LCAP32S LCAP44M / LCAP44S
Cabinet Dimensions, HWD 32” x 24” x 4.575”
81cm x 61cm x 11.6cm
44.5” x 24” x 4.575”
113cm x 61cm x 11.6cm
Door Dimensions, HWD 32” x 24” x 0.75”
81cm x 61cm x 2cm
44.5” x 24” x 0.75”
113cm x 61cm x 2cm
Panel Insert, HWD 29.5” x 21” x 4.175”
75cm x 53.3cm x 10.6cm
42” x 21” x 4.175”
106.7cm x 53.3cm x 10.6cm
Weight - Enclosure 30 lbs / 13.61 kg 41 lbs / 18.6 kg
Weight - Door 15.5 lbs / 7.03 kg 20.7 lbs / 9.39 kg
Weight - Panel Insert 18.7 lbs / 8.48 kg 23 lbs / 10.43 kg
Number of Modules Up to 2 Up to 4
Load Capacity Up to 24 Up to 48
Line Feeds (Breakers) Up to 17 Up to 33
*Flash Memory (via controller)
Enclosure Finish Galvanized steel
Door Finish Black - Powder coated
Cover Vented, hinged
Wire Copper wire, MIN. of 176° F/ 80° C insulation
Ventilation Maintain 36” front clearance
Ambient Operating Temperature 32 - 104° F / 0 - 40° C
Ambient Operating Humidity 5 - 95% non-condensing
UL, CUL, and CE Listed Yes
LCAP SERIES ENCLOSURE FACTS
Enclosures must be populated from left to right and top down
- Blank module positions cannot be left between lighting modules in Design Center setup
Enclosures are pre-congured and wired (to the extent possible) using specic combinations of the following
componentsInstalled switching components are dependent on the enclosure design
- Components using high-voltage wiring
• Mixed high voltage wiring
- Components using low voltage control signal wiring
- Components using low voltage communication wiring
- Components using high voltage and low voltage connections made inside the enclosure
• The enclosure uses built-in barriers to separate high and low voltage wiring
• Some designs include the barrier while other designs require the barrier be added by the designer
- High voltage barriers may be installed between 120V/240V/277V load modules
Enclosures may be setup as follows
- Main Enclosures Containing: One Main Enclosure Terminal Board (36V) and one IC-36-II InFusion Controller - OR -
- Secondary Enclosures Containing: One Secondary Enclosure Terminal Board
EULA
In order to enhance the security of our products, Legrand ships its products with all insecure ports closed and insecure protocols
disabled. You are free to congure your device as needed, but in doing so note that you may be decreasing the security of your
device and any information contained in the device. As you modify the device’s default settings, keep in mind how this may impact
the security of the device and your network. In addition, you should use caution in connecting your device to the Internet, especially
if you have altered the default security settings. If you have any questions or concerns about how your modications of the device
may affect its security, please contact the Legrand customer service team at 1-800-879-8585 / https://www.legrand.us/support/
Wattstopper.aspx
3
IS-00706 – Rev. 7
ENCLOSURE FEATURES / PARTS
1. Enclosure can (includes door), order LCAP32/44 for can only, (44” shown)
2. Panel Insert (See Panel Load Section)
a. Ground terminals (terminals for upper and lower sections)
b. Module Panel Boards – 103160-1. Up to 4 modules for 44” and up to 2 Modules for 32”
c. Metal isolation barrier between varying voltages. Should be added in Design Centers project design as part of enclosure
setup, giving it the correct part number via the position (optional)
d. AC Terminal boards installed for module type ordered
e. Terminal board jumpers are installed for lighting control via breakers during construction
NOTE: MDR8CW301 commercial modules do not support either type of terminal jumper boards
3. Panel Insert (controller section)
a. Barrier for IC-36-II controller or secondary terminal board.
b. IC-36-II board or secondary terminal board inside barrier.
c. IC-36-II controller for M models or Secondary Terminal Board for S models.
4. Enclosure cover, with hinged/vented door allowing easy access when servicing and proper ventilation for convection cooling
process
LCAP32/44M/S PANEL BASIC CONSTRUCTION PARTS
4
IS-00706 – Rev. 7
TERMINAL JUMPER BOARDS
MODULE TERMINAL BOARDS
LCAP32/44M PANEL OPTIONAL CONSTRUCTION PARTS
INSTALLATION / ENCLOSURE MOUNTING INSTRUCTIONS
Terminal jumper boards are installed for use
during construction to supply power to loads.
Modules can then be installed when construction
is nished.
NOTE: 8 line feed relay modules do not have a
jumper board option
JUMPER BOARDS: MJTB or QJUMPER
VOLTAGE BARRIER
When adjacent modules use different line voltage
feeds (e.g., 120V and 277V) install a voltage
barrier between the modules
Installation of LCAP products should be performed or supervised by a Wattstopper/Vantage factory representative and a Certied
Wattstopper/Vantage Installer. Installation and maintenance of high-voltage devices should only be performed by qualied and
licensed personnel having appropriate training and experience.
The AD-RRU-X-UNV Switch comes pre-installed in the kit
The AD-EPC-D-F-ATS Switch is installed on site
NOTE: Please see install sheets for emergency switch applications
12 LOAD
TSDM-KIT
8 LOAD
TLM-KIT
8 LOAD
TUDM-KIT
8 LINE FEED
T8LRM-KIT
EMR SWITCH
AD-RRU-X-UNV
EMR SWITCH
AD-EPC-D-F-ATS
Order Separate
EMERGENCY
POWER
UTILITY
POWER
TEST
5
IS-00706 – Rev. 7
Do not use outdoors
Do not mount near gas or electric heaters
Do not mount enclosures in attics, garages, or crawlspaces, unless room is properly conditioned to conform to ambient room
temperature and humidity requirements
Mount enclosure a minimum of 18” from ceiling or oor
National Electrical Code requires a minimum frontal clearance of 36” for the enclosure
Use screws provided for mounting
If any emergency circuits are fed or controlled from this panel, it must be located electrically where fed from a UPS, generator, or
other guaranteed source of power during emergency and power outage situations
LISTED AS EMERGENCY LIGHTING EQUIPMENT – using an appropriate label
CAUTION: To avoid electrical overload, total external connected load should not exceed output rating
SAVE THESE INSTRUCTIONS
IMPORTANT SAFEGUARDS
CAUTION: TURN BREAKERS OFF AND CHECK THAT NO POWER IS ON AT THE AC TERMINAL
BOARDS WHEN WORKING IN THE ENCLOSURE OR WORKING ON LIGHTING FIXTURES
CONNECTED TO THE MODULE’S LOADS, ETC. DO NOT ALLOW TRIMMED WIRE CUTTINGS
TO FALL INTO ENCLOSURE COMPONENTS AS THEY MAY CAUSE DAMAGE WHEN
POWER IS RESTORED. DAMAGE FROM THIS TYPE OF SHORT WILL VOID THE WARRANTY.
EMERGENCY CIRCUITS
Drill proper size holes in can for running wires in and out of the enclosure. Separate high and low-voltage wire run
channels. All wire runs in and out of the enclosure should be secured using 2-screw connectors or equivalent as shown
at the right. Proper conduit or equivalent wire channels should be used according to local codes and regulations.
BREAKER FEEDS TO CONTROLLERS
The Controllers power supply should be wired to a dedicated circuit breaker. When multiple enclosures containing controllers are in
close proximity to one another, it is recommended to share the same breaker to all Main Controllers; no more than nine controllers
may be connected to a 20amp breaker – allow up to 200W@120VAC per InFusion Controller. Do not share the same breaker with
controllers and modules. Please see Main Lug / Circuit Breaker options on page 7.
MAIN CONTROLLER TO MAIN CONTROLLER WIRING
NOTE: the use of Ethernet connections for Controller to Controller communication is recommended. Please see the InFusion
Controller instruction sheet for additional information.
When connecting multiple Main enclosures via the Main Enclosure Terminal Board’s Controller Bus screw terminals, it is
recommended to use station bus wire mentioned below or an equivalent between enclosures. This is a polarized connection with two
“+” and two “–” screw terminals for in and out wire runs. The maximum wire length for all controllers connected together on one bus
should not exceed 2,000ft. using the Station Bus wire specication.
STATION BUS WIRE SPECIFICATION
Vantage wire, part #VDA-0143-BOX or VPLENUM-CABLE – 2C, 16AWG / 1.31mm2, twisted, non-shielded, <30pF per foot. Separate
a minimum of 12” / 30.5cm from other parallel communication and/or high-voltage runs.
STATION BUS WIRING
WireLink stations connect to the Station Bus screw terminals on the Main Enclosure Terminal Board. Use station bus wire, (above).
Maximum total station bus wire for each run = 2,000 feet with no station more than 1,000 feet from enclosure (typically the second
half of the station bus loops back to enclosure with only one end connected). Station Bus should be separated a minimum of 12” from
other parallel communication and/or high-voltage runs.
Connector Torque Wire Range
Module Terminal 20 Inch Pounds 14-10 AWG*
Controller Power 20 Inch Pounds 14-10 AWG*
PROPER HIGH-VOLTAGE TERMINATIONS / PROPER TORQUE
GENERAL WIRING
WIRING
6
IS-00706 – Rev. 7
MAIN & SECONDARY ENCLOSURE TO SECONDARY ENCLOSURE WIRING
Connecting a Main enclosure to a Secondary enclosure or Secondary enclosure A to Secondary enclosure B, requires 16/18-gauge
4-conductor twisted, non-shielded wire. Three of the wires are always used to connect a Main enclosure to a Secondary enclosure
and chained secondary enclosures. This is a polarized connection with “+”, “–” and “Gnd” screw terminals for communication. The 4th
wire is for Manual Override and is optional. Each Secondary enclosure bus can support two Secondary enclosures for a maximum
of six Secondary enclosures per Main enclosure (see InFusion wiring below). Maximum wiring distance from Main enclosure to
Secondary enclosure is 200ft including an A/B Secondary system (e.g., 100ft from Main enclosure to Secondary enclosure A and an
additional 100ft from Secondary enclosure A to Secondary enclosure B).
MAIN TERMINAL BOARD TERMINATOR
If only one or two Main enclosures are used, the Controller Bus Termination switch must be ON. This switch is located on the
Enclosure Terminal Board. If more than two Main enclosures are used ONLY the rst and last Enclosure Terminal Boards on each
controller bus should have the Network Termination switch set to ON.
RS-232 (PORTS 1-5) FOR MAIN ENCLOSURES
The Main Enclosure Terminal Board has ve RS-232 ports. Use these ports to connect any device that uses RS-232 communication.
Only connect one RS-232 device at a time to an RS-232 port. If additional RS-232 ports are needed, Vantage also manufactures an
RS-232 Station or, some products like the IRX II, have built-in RS-232 ports.
Controllers serial communication typically use RX, TX and GND for communication but also supports RTS and CTS for some
applications on RS-232 Ports 1 and 2. RS-232 Ports 3-5 only have TX, RX and GND., however, all ve ports can use software ow
control. The default communication protocol may be changed through Design Center software.
Communication protocol parameter settings:
Standard baud rates 1200 – 115.2K
7-8 Data Bits
Even, Odd, Forced or No Parity
200ft. maximum wiring distance
Default protocol for RS-232 communication is:
Baud: 19200
Parity: None
Total bits: 8
Stop bits: 1
RS-485 CONNECTIONS
The Main Enclosure Terminal Board has two RS-485 ports. These ports are connected to the same screw terminals used for
Secondary enclosure ports 3 and 4. The ports may not be used for Secondary enclosure support and RS-485 support simultaneously.
However, if Secondary enclosure bus ports 3 and/or 4 are free they may be used as RS-485 communication ports. The RS-485 ports
are half-duplex, meaning that each port can transmit and receive but not at the same time. Maximum wiring distance for RS-485 ports
is 200ft.
POSSIBLE GROUND LOOP ISSUES
All RS-232/RS-485 connections between third party equipment and RS-232/RS-485 connections on the Main Enclosure Terminal
Board may produce a ground loop. Most often, the connected RS-232/RS-485 device is not using the same power source or is far
away from the enclosure resulting in a possible ground loop that may produce a data noise condition. If this condition is suspected,
Recommended: A third party RS-232/RS-485 Opto (optical) Isolation Module. Opto Isolation provides a communications link and is
an important consideration if a system uses different power sources, has noisy signals or must operate at different ground potentials.
AUXILIARY POWER
The enclosure, Main Enclosure Terminal Board has a 12VDC auxiliary power connection. The 12VDC connection is typically used for
one RFE1000 RadioLink Enabler or one RFLC-V232 Enabler. Total power is limited to 250ma. NOTE: Do not connect more than one
auxiliary device at a time to this power source. If additional powered devices are needed they must be separately powered with an
external, isolated type (usually no ground prong), power transformer.
WIRING (continued)
7
IS-00706 – Rev. 7
MANUAL OVERRIDE
In the unlikely event of a Main Controller failure, the Manual Override can be used to turn selected loads ON. If the system is in
override, individual loads can be controlled by dip-switches located on each module in the enclosure. Manual Override control can be
extended to other enclosures. It is common to extend Manual Override between a Main enclosure and its Secondary enclosures. It is
not recommended to extend Manual Override between Main enclosures.
WIRING AC TERMINALS
Keep breaker and load wire runs organized and managed as illustrated.
WIRING (continued)
LCAP32/44M/S SUPPORTED MODULE TYPES
NEUTRALS
Run a separate NEUTRAL for each load connected to dimming
devices. Failure to do this may cause loads, sharing the same
neutral, to icker slightly while ramping or dimming a load. The
potential for ickering occurs with all dimming systems due to the
changing load level coupling to the xed load through the neutral.
MUST MATCH BREAKER WIRE GAUGE
TORQUE: 20 inch pounds
PROPER: Insulation not
cut back too far
PROPER: Wire not forced
in screw terminal too far
SDM12-EM
4 LINE FEED 12 LOAD
STANDARD DIMMER
FANMOD
CEILING FAN MODULE
120V
MDR8CW301
8 LINE FEED 8 LOAD
RELAYS
UDM08-EM
4 LINE FEED 8 LOAD
UNIVERSAL DIMMER
INSTALL INSTRUCTIONS
Click on module names for install instructions.
8
IS-00706 – Rev. 7
manual
override
1
1
2
3
4
5
6
7
8
2
3
4
5
6
7
8
NOTE: The InFusion Controller plugs
into the Main Enclosure Terminal Board
after all connections have been made
WIRE TYPES WIRING KEY
6C 18-24AWG
2C 18-16AWG
4C 18AWG
RS232 Ports, Flow Control
RS232 Ports, Flow Control Via Software
Previous Controller Bus
Next Controller Bus
Station Bus Run-1
Station Bus Run-2
To Secondary Enclosure Board (S) Switch
RS485 Ports (If not used for Secondary Bus)
• See maximum wire lengths above •
TORQUE: 20 Inch Pounds
WIRE RANGE: 14-10 AWG*
* Must match breaker wire gauge
LCAPM ENCLOSURE TERMINATIONS
InFusion Main Controller Enclosure Terminations
CAUTION: FOR RETROFIT JOBS, THIS BOARD IS ALSO AVAILABLE IN A 24V VERSION
FOR THE IC-24-II CONTROLLER. NEVER CONNECT STATIONS THAT DO NOT DISPLAY
A CIRCLE SYMBOL ON THE SERIAL NUMBER STICKER TO AN IC-36-II SYSTEM.
9
IS-00706 – Rev. 7
LCAPS ENCLOSURE TERMINATIONS
INFUSION OVERRIDE WIRING EXAMPLES
InFusion Secondary Enclosure Terminations
InFusion Looped Enclosure Manual Override
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
OVERRIDE
SWITCH
10
IS-00706 – Rev. 7
INFUSION OVERRIDE WIRING EXAMPLES
InFusion Individual Enclosure Manual Override
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
OVERRIDE
SWITCH
OVERRIDE
SWITCH
NO CONNECT
to Secondary Enclosure
Terminal Board
11
IS-00706 – Rev. 7
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
Secondary Enclosure
Terminal Board
AB
Enclosure
Select
Enclosure
Bus
Termination
INFUSION MAIN ENCLOSURE TO SECONDARY ENCLOSURES WIRING OVERVIEW
Note the position of the enclosure selecet switch and the Enclosure Bus Termination switch on each Secondary Enclosure Terminal
Board. All “A” boards are homerun to the Controller board and all “B” boards are homerun to its parent, “A” board. The termination
switch is OFF for all “A” boards only if they have a “B” board connected. The termination switch is ON for all “B” boards.
JUNCTION FOR ALL OVERRIDES
It is also possible to extend
Override from one Secondary
Enclosure to the next Secondary
Enclosure, as long as it daisy
chains back to the Main Enclosure
12
IS-00706 – Rev. 7
MULTI-VIEW LINE DRAWINGS
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
44.5” / 113cm
24” / 61cm
4.575”
11.6cm
LCAP44M/S
SIDE PANEL FRONT BACK
N
N
N
N
N
N
N
N
32” / 81cm
24” / 61cm
4.575”
11.6cm
ENCLOSURE MULTI-VIEW
LCAP32M/S
ENCLOSURE MULTI-VIEW
SIDE PANEL FRONT BACK
13
IS-00706 – Rev. 7
ORDERING KEY FOR LCAP32/44M/S
LCAP32/44M/S/LO/CB PANELS WITH MAIN LUG PANEL OPTION
PART #S FOR MODULES / MODULE PLACEMENT
KIT PART
NUMBER
CONTENTS
LCAP32M-KIT
Included (1) LCAP32M Panel with (2) 103160-1 Module boards,
(1) IC-36-II Controller
Optional (1) Module model in locations 1 and 2,
(1) COM-HV-BARRIER Voltage barrier, and
(1) VA-RRU-1-120V or VA-RRU-1-277V
LCAP32S-KIT
Included (1) LCAP32S Panel with (2) 103160-1 Module boards,
(1) Secondary enclosure terminal board
Optional (1) Module model in locations 1 and 2,
(1) COM-HV-BARRIER voltage barrier, and
(1) VA-RRU-1-120V or VA-RRU-1-277V
LCAP44M-KIT
Included (1) LCAP44M Panel with (4) 103160-1 Module boards,
(1) IC-36-II Controller
Optional (1) Module model in locations 1, 2, 3, and 4,
(1) COM-HV-BARRIER Voltage barrier, and
(1) VA-RRU-120V or VA-RRU-1-277V
LCAP44S-KIT
Included (1) LCAP44S Panel with (4) 103160-1 Module boards,
(1) Secondary Enclosure Terminal Board
Optional (1) odule model in locations 1, 2, 3, and 4,
(1) COM-HV-BARRIER Voltage barrier, and
(1) VA-RRU-1-120V or VA-RRU-1-277V
Module Model: Select one module for each location
Replace the asterisk with one of the following:
C - For MDR8CW301, Relay Module, 8-Line Feed 120V-277V
FA - For FANMOD Ceiling Fan Module - 120V
F - For SDM12-EM, Standard Dimming Module - 120V-277V
forward phase)
U - For UDM08-EM Universal Dimming Module - 120V-277Vx
(forward or reverse phase)
X - Blank module position
(Allowed only after populated module positions)
LCAP32M or S - Support for up to 2 modules
LCAP44M or S - Support for up to 4 modules
MAIN LUG CIRCUIT BREAKER OPTION
The LCAPM and LCAPA series enclosures can be congured as a load feed through panels (LCAP PANEL only) or as main lug
panels with the addition of load circuit breakers below the load control feed through compartment. Main lug options can also contain
a main breaker. The Main Lug option is available for the LCAP-M/S and LCAP-A series panels – click to see the LCAP44A/S/LO/
CB install sheet. The circuit breaker options are based on the panel size, number and type of loads, and circuit breaker rating
requirements. Once the main lug panel and circuit breaker options are selected the panel is built and prewired* in the factory and
delivered to the project ready to be installed.
NOTE: Panels With GFI Breakers: GFI breakers are not installed or pre-wired and are shipped separately.
14
IS-00706 – Rev. 7
LCAP32/44M/S/LO/CB PANELS WITH MAIN LUG PANEL OPTION (continued)
SETUP IN DESIGN CENTER
APPLICATIONS
The LCAP32M/S and 44M/S are designed for medium to large spaces requiring control of up to 48 separate line voltage lighting
circuits. The built-in integration and networking capabilities of the LCAP32M and LCAP44M easily meet requirements in spaces
with shades, comfort control needs, lighting, and other automation integration systems using this panel. Adding an Equinox 41 or
73 touchscreen to the project allows the facility manager or end user to create, change, and manage scenes, schedules, and user
proles.
FEATURES
Modular LCAP load section; pre-congured solution from the factory. Just connect line voltage and load wires
Pre-congured Main Lug Panel solution options
System is expandable using other LCAP series primary or secondary panels and LCAP Main Lug / Circuit Breaker options
Can be congured with additional emergency rated relays for emergency lighting
When connected to the local LAN the panel can be remotely programmed
Low-voltage 2 wire station bus for connecting keypads can extend up to 4,000 ft.*
Connects to DLM systems for a whole building control solution
Ability to integrate plug load
DMX-DALI supported with additional hardware (see DMXDALI-GW)
Daylight and occupancy sensors are connected to keypads or contact input stations. No power packs needed
Dimmers have programmable start/stop and dimming curve adjustment features to customize dimming linearity
Forward phase and reverse phase dimmers are available; SDM12/forward phase and UDM08/forward and reverse phase, each
have 65kA ratings
Simple programming from a single software solution - Design Center
LCAP32M and LCAP44M include controller, add up to six LCAP32S or LCAP44S panels for expansion of dimming and load
control capabilities; network additional controllers for further scalability
One LCAP32/44M series enclosure supports up to six additional LCAP32S and LCAP44S panels for expansion of dimming and
load control capabilities. LCAP32M and LCAP44M series support up to 30 additional M-series enclosures with controllers for
almost unlimited scalability
Adding one BACnet enabled controller to a system allows the entire system to be controlled through BACnet
Main Lug Panel options range from 18 to 36 circuits, 208-480V, and 10kAIC to 65kAIC and may be congured with a main
breaker option
UNDERSTANDING LCAP AND MAIN LUG PANELS
LCAP panels with the Main Lug option is a larger enclosure that holds the traditional
LCAP components in the upper section of the enclosure and includes a breaker
section in the lower section of the enclosure.
LCAP panels with the Main Lug option are built in Design Center the same way as
standard LCAP panels. The only difference is the Main Lug option has been selected.
Follow the steps below to create an LCAP panel with the Main Lug option selected.
1. In Design Center | Object Explorer select:
Vantage Objects,
Enclosures, Commercial,
LCAP model:
LCAP32-44M/S-KIT (Main Lug)
Set module count to two (2) for LCAP32/M
- or -
Set module count to four (4) for LCAP44/M
Select model LCAP 44A-KIT (Main Lug) - see LCAP44A install
2. Right click in the enclosure and select Populate to automatically add modules in the
enclosure or select modules and drag into the enclosure as wanted. (It is not possible
to drag a module below a blank module location in an LCAP enclosure – ll enclosure
from top to bottom).
15
IS-00706 – Rev. 7
SETUP IN DESIGN CENTER (continued)
LCAP32/44M/S/LO/CB SERIES SPECIFICATIONS
3. Notice that breakers are automatically added to the Main Lug section of the enclosure as modules are added.
4. It is possible to add additional breakers in the Main Lug section by right clicking below existing breakers and selecting Add
Breaker until the maximum number of breakers allowed is reached.
5. Select the Main Lug section of the enclosure and change the type to MCB to add a Main Breaker option or leave as MLO for
standard load breakers only.
Specications LCAP32/M/S/LO LCAP32/M/S/CB LCAP44/M/S/LO LCAP44/M/S/CB
Cabinet / Panel Cover
Dimensions - HWD
55.5” x 24” x 4.75”
140.97cm x 60.96cm x
12.06cm
64.5” x 24.0” x 4.75”
163.83cm x 60.96cm x
12.06cm
68.0” x 24.0” x 4.75”
172.72cm x 60.96cm x
12.06cm
77.0” x 24.0” x 4.75”
195.58cm x 60.96cm x
12.06cm
LCAP Panel Door
Dimensions - HWD
28” x 16” x 0.75”
71.12cm x 40.64cm x 1.9cm
40.5” x 16.0” x 0.75”
102.87cm x 40.64cm x 1.9cm
Panel Insert - HWD 29.5” x 21” x 4.175”
75cm x 53.3cm x 10.6cm
42” x 21” x 4.175”
106.7cm x 53.3cm x 10.6cm
Weight - Panel Insert M-18.7 lbs. 8.48 kg
S-15.4 lbs. 6.99 kg
M-23 lbs. 10.43 kg
S-20 lbs. 9.07 kg
Number of Modules Up to 2 Up to 4
Load Capacity Up to 24 Up to 48
Line Feeds Up to 17 Up to 33
Breakers Up to 18 Up to 36
Main Lug Panel Door
Dimensions - HWD
16” x 12.5” x 0.75”
40.64cm x 31.75cm x
1.9cm
23” x 12.5” x 0.75”
58.42cm x 31.75cm x
1.9cm
16” x 12.5” x 0.75”
40.64cm x 31.75cm x
1.9cm
23” x 19” x 0.75”
58.42cm x 48.26cm x
1.9cm
Weight - Enclosure
with Cover
110 - 130 lbs / 49.9 -
58.97 kg
115 - 135 lbs / 52.16 -
61.23 kg
165 - 175 lbs / 74.84 –
79.38 kg
170 - 180 lbs / 77.11 –
81.65 kg
*Flash Memory (via controller)
Enclosure Finish Galvanized Steel
Door Finish Black - Poweder Coated
Cover Vented, hinged
Wire Copper wire, MIN. of 80°C / 176°F insulation
Ventilation Maintained 36” front clearance
Ambient Operating
Temperature
0-40°C / 32-104°F
Ambient Operating
Humidity
5-95% non-condensing
UL, CUL, and CE
Listed
Yes
16
IS-00706 – Rev. 7
STANDARD LCAPM SERIES AND LCAPA SERIES ENCLOSURES WITH MAIN LUG ENCLOSURES
LCAP32M/S CONFIGURED WITH LCAP32/M/LO/CB EXAMPLE:
LCAP44M/S CONFIGURED WITH LCAP44/M/LO/CB EXAMPLE:
LCAP32M/S
Main Lug options LO or CB come
with (up to) 18, 20A breakers
Finished LCAP32/LO enclosure:
55.5” high
Finished LCAP32/CB enclosure:
64.5” high
See additional specications on pg
15 and drawings on pg 17
LCAP32M/S
Main Lug options LO or CB come
with (up to) 18, 20A breakers
Finished LCAP44/LO enclosure:
68” high
Finished LCAP44/CB enclosure:
77” high
See additional specications on pg
15 and drawings on pg 17
17
IS-00706 – Rev. 7
COMMUNICATION CONDUIT
GROUND BAR
NEUTRAL
BAR
CIRCUIT
BREAKERS
DIMMER
SECTION
BARRIER
COMMUNICATION
CONDUIT
GROUND BAR
CIRCUIT
BREAKERS
NEUTRAL
BAR
BARRIER
DIMMER
SECTION
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
LCAP32 PANEL SURFACE TRIM
BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP32 PANEL
MAIN LUGS WITH DOORS
& DEADFRONT REMOVED
LCAP32 PANEL SURFACE MOUNT
BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP32 PANEL
MAIN BREAKER WITH DOORS
& DEADFRONT REMOVED
480Y/277V 30 4W
(14KAIC)
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A MAIN LUGS
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
100A
100A
MAIN
BKR.
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/277V 30 4W
(14KAIC-*35KAIC-*65KAIC)
*SERIES RATED
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A MAIN BREAKER
24.0” (60.96cm)
24.0” (60.96cm)
32.25” (81.915cm) 23.25” (59.055cm)
4.5” (11.43cm)
4.5” (11.43cm)
32.25” (81.915cm) 32.25” (81.915cm)
55.5” (140.97cm)
64.5” (163.83cm)
100A
100A
2P
MAIN
BKR.
LCAP32M/S/LO
1. Enclosure upper section for
LCAP32M/S Panel
2. Enclosure lower section for
up to 18 breakers. Select the
Main Lug option MLO option
for (up to) 18, 20A breakers
3. Breaker section may be
congured for 4-wire or
3-wire power congurations
4. See last page for breaker/
order options
LCAP32M/S/CB
1. Enclosure upper section for
LCAP32M/S Panel
2. Enclosure lower section for
up to 18 breakers. Select
the Main Lug type and
change to MCB to add a
Main Breaker option
3. Breaker section may be
congured for 4-wire or
3-wire power congurations
4. See last page for breaker/
order options
LCAP32M/S/LO WITH MAIN LUG ENCLOSURE MULTI-VIEW
LCAP32M/S/CB WITH MAIN LUG/ MAIN BREAKER ENCLOSURE MULTI-VIEW
18
LCAP44M/S/LO WITH MAIN LUG ENCLOSURE MULTI-VIEW
DIMMER
SECTION
DIMMER
SECTION
LCAP44 PANEL SURFACE TRIM
BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP44 PANEL
MAIN LUGS WITH DOORS
& DEADFRONT REMOVED
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/277V 30 4W
(14KAIC)
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A MAIN LUGS
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
100A
100A
MAIN
BKR.
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
G
N
D
B
U
S
N
E
U
T
R
A
L
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/277V 30 4W
(14KAIC-*35KAIC-*65KAIC)
*SERIES RATED
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A MAIN BREAKER
4.5” (11.43cm)
23.25” (59.055cm)
CIRCUIT
BREAKERS
BARRIER
100A
100A
2P
COMMUNICATION CONDUIT
GROUND BAR
NEUTRAL
BAR
44.75” (113.665cm)
68” (172.72cm)
24.0” (60.96cm)
LCAP44-18 PANEL SURFACE
MOUNT BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP44-18 PANEL
MAIN BREAKER WITH DOORS
& DEADFRONT REMOVED
4.5” (11.43cm)
CIRCUIT
BREAKERS
BARRIER
COMMUNICATION CONDUIT
GROUND BAR
NEUTRAL
BAR
77” (195.58cm)
24.0” (60.96cm)
32.25” (81.915cm)44.75” (113.665cm)
MAIN
BKR.
LCAP44M/S/LO
1. Enclosure upper section for
LCAP44M/S Panel
2. Enclosure lower section for
up to 18 breakers. Select the
Main Lug option MLO option
for (up to) 18, 20A breakers
3. Breaker section may be
congured for 4-wire or
3-wire power congurations
4. See last page for breaker/
order options
LCAP44M/S/CB
1. Enclosure upper section for
LCAP44M/S Panel
2. Enclosure lower section for
up to 18 breakers. Select
the Main Lug type and
change to MCB to add a
Main Breaker option
3. Breaker section may be
congured for 4-wire or
3-wire power congurations
4. See last page for breaker/
order options
LCAP44M/S/CB WITH MAIN LUG/MAIN BREAKER ENCLOSURE MULTI-VIEW
19
IS-00706 – Rev. 7
LCAP44M/S/CB
1. Enclosure upper section for LCAP44M/S Panel
2. Enclosure lower section for up to 36 breakers. Select the Main
Lug type and change to MCB to add a Main Breaker option
3. Breaker section may be congured for 4-wire or 3-wire power
congurations
LCAP44M/S/LO/36 BREAKERS WITH MAIN LUG ENCLOSURE MULTI-VIEW
LCAP44M/S/CB/36 BREAKERS WITH MAIN LUG/MAIN BREAKER ENCLOSURE MULTI-VIEW
LCAP44M/S/LO
1. Enclosure upper section for LCAP44M/S Panel
2. Enclosure lower section for up to 36 breakers.
Select the Main Lug option MLO option for (up to)
18, 20A breakers
3. Breaker section may be congured for 4-wire or
3-wire power congurations
4. See last page for breaker/order options
DIMMER
SECTION
BREAKER
SECTION
DIMMER
SECTION
BREAKER
SECTION
G
N
D
B
U
S
N
E
U
T
R
A
L
G
N
D
B
U
S
N
E
U
T
R
A
L
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/277V/30 4W
(14KAIC)
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A MAIN LUGS
LCAP44-36 PANEL SURFACE
MOUNT BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP44-36 PANEL
MAIN BREAKER WITH DOORS
& DEADFRONT REMOVED
4.5” (11.43cm)
CIRCUIT
BREAKERS
BARRIER
COMMUNICATION
CONDUIT
NEUTRAL BAR
GROUND
BAR
77” (195.58cm)
24.0” (60.96cm)
32.25” (81.915cm)44.75” (113.665cm)
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
LCAP44-18 PANEL SURFACE
MOUNT BOX 4 1/2” DEEP
WITH DOORS INSTALLED
LCAP44-18 PANEL
MAIN BREAKER WITH DOORS
& DEADFRONT REMOVED
4.5” (11.43cm)
CIRCUIT
BREAKERS
BARRIER
COMMUNICATION CONDUIT
GROUND BAR
NEUTRAL
BAR
77” (195.58cm)
24.0” (60.96cm)
32.25” (81.915cm)44.75” (113.665cm)
G
N
D
B
U
S
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
20
20
20
20
20
15
31
33
35
32
34
36
225A
225A
100A
MAIN
BKR.
3P
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
BUS DIAGRAMS
100A - 225A
MAIN BREAKER
480Y/277V 30 4W
(14KAIC-*35KAIC-*65KAIC)
*SERIES RATED
NEUTRAL
G
N
D
B
U
S
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
20
20
20
20
20
15
31
33
35
32
34
36
225A
225A
100A
MAIN
BKR.
2P
120V/240V 10 3W
(10KAIC-22KAIC-65KAIC)
NEUTRAL
20
IS-00706 – Rev. 7
CONFIGURATION FOR LCAP32 ADDER - Branch Breakers Each, 1-Pole, 20A
SIZE HEIGHT BASE PANEL CONFIGURATION 10kAIC 14kAIC
11kAIC 35kAIC 65kAIC
18 Circuits
100A
Bussing
56”
240V - MLO (Single Phase) BAB
QHB GHB
208V - MLO BAB
QHB GHB
480V - MLO GHB
65”
240V - MCB (Single Phase) (Up to 100A, 65kAIC)
BAB*
208V - MCB (up to 100A, 65kAIC)
BAB*
480V - MCB (up to 100A, 35kAIC)
GHB*
480V - MCB (up to 100A, 65kAIC)
GHB*
CONFIGURATION FOR LCAP44 ADDER - Branch Breakers Each, 1-Pole, 20A
SIZE HEIGHT BASE PANEL CONFIGURATION 10kAIC 14kAIC
11kAIC 35kAIC 65kAIC
18 Circuits
100A
Bussing
68”
240V - MLO (Single Phase) BAB
QHB GHB
208V - MLO BAB
QHB GHB
480V - MLO GHB
77”
240V - MCB (Single Phase) (Up to 100A, 65kAIC)
BAB*
208V - MCB (up to 100A, 65kAIC)
BAB*
480V - MCB (up to 100A, 35kAIC)
GHB*
480V - MCB (up to 100A, 65kAIC)
GHB*
CONFIGURATION FOR LCAP44 - 36 BREAKER ADDER - Branch Breakers Each, 1-Pole, 20A
SIZE HEIGHT SIZE 10kAIC 14kAIC
11kAIC 35kAIC 65kAIC
18 Circuits
100A
Bussing
77”
240V - MLO (Single Phase) BAB
QHB GHB
208V - MLO BAB
QHB GHB
480V - MLO GHB
240V - MCB (Single Phase) (Up to 225A, 65kAIC)
BAB*
208V - MCB (up to 225A, 65kAIC)
BAB*
480V - MCB (up to 100A, 35kAIC)
GHB*
480V - MCB (110A - 225A, 35kAIC)
GHB*
480V - MCB (up to 100A, 65kAIC)
GHB*
480V - MCB (100A - 225A, 65kAIC)
GHB*
BREAKER RATING LEGEND (Single Phase)
MLO = Main Lug Option Type BAB 10kAIC
MCB = Main Lug with Main Circuit Breaker Type QBH 22kAIC
208V - MLO BAB
LCAP WITH OPTIONAL MAIN LUG PART NUMBER ORDERING KEY
Design Center will generate LCAP32/34/M/S/LO/CB part numbers automatically as the enclosures are built. This key is for help in
understanding and creating orders in the LCAP Quote Tool online ordering tool.
BREAKER TYPES FOR LCAPM/S/LO/CB ENCLOSURE CONFIGURATIONS
BREAKER TYPES FOR LCAPM/S/LO/CB ENCLOSURE CONFIGURATIONS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21

Legrand LCAP32M Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI