Installation & Maintenance Manual
®
C
US
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury,
death, or property damage.
—Donotstoreorusegasolineorotherammablevaporsand
liquidsinthevicinityofthisoranyotherappliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phoneinyourbuilding.
• Leavethebuildingimmediately.
• Immediatelycallyourgassupplierfromaneighbour's
phone. Follow the gas supplier’s instructions.
• Ifyoucannotreachyourgassupplier,callthere
department.
—Installationandservicemustbeperformedbyaqualied
installer,serviceagencyorthegastter.
DelRay Square
INDOOR DIRECT VENT GAS FIREPLACE
DRSQC38NI CONTEMPORARY
DRSQC38LI CONTEMPORARY
DRSQC38NI-2 CONTEMPORARY
DRSQC38LI-2 CONTEMPORARY
DRSQ38NI TRADITIONAL
DRSQ38LI TRADITIONAL
DRSQ38NI-2 TRADITIONAL
DRSQ38LI-2 TRADITIONAL
A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this
appliance and must be installed for the protection
of children and other at-risk individuals.
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
DANGER
Installation and service must be performed by a qualied installer,
service agency or the gas tter. Check local codes and read all
instructions prior to installation.
Some materials used in the manufacturing process of this product can
expose you to Benzene which is known in the State of California to
cause cancer and birth defects or other reproductive harm. For more
information go to www.P65warnings.ca.gov
WARNING
Installer: Leave this manual with the appliance. Please refer to the
Montigo website for the most current version of the replace manual
Consumer: Retain this manual for future reference. Please refer to the
Montigo website for the most current version of the replace manual
NOTICE
2
General
XG0230 - 052020
Figure 1 DRSQ pecications
Congratulations on your purchase of a Montigo Fireplace.
With over 30 years of experience, Montigo is committed to providing
you with a gas fireplace that is not only a beautiful addition to your
space, but that is also designed and manufactured to the highest
safety, reliability and engineering standards.
We strongly encourage you to read and carefully follow the
instructions laid out in this Installation, Operation and Maintenance
Manual and retain it for your future reference. Pay special attention
to all cautions, warnings, and notices throughout this manual
intended to ensure your safety.
This manual covers installation, operation and maintenance. Lighting,
operation and care of this replace can be easily performed by the
homeowner. All installation and service work should be performed
by a qualied or licensed installer, plumber or gas tter as certied
by the state, province, region or governing body where the replace
is being installed.
This installation, operation and maintenance manual is applicable
to the models described in Table 1. Refer to your rating plate to
verify included options.
Warranty and Installation Information: (See Appendix B)
The Montigo warranty will be voided by, and Montigo disclaims any
responsibility for, the following actions:
Modication of the replace and/or components including Direct-
Vent assembly or glass doors.
Use of any component part not manufactured or approved by
Montigo in combination with this Montigo replace system.
Installation other than as instructed in this manual.
Consult your local Gas Inspection Branch on installation
requirements for factory-built gas replaces. Installation & repairs
should be done by a qualied contractor.
Eciencylisting
MODEL
P.4. 1-15
Eciency
DRSQ38NI 63.40%
DRSQ38NI-2 64.97%
DRSQ38LI 61.82%
DRSQ38LI-2 61.54%
DRSQC38NI 63.40%
DRSQC38NI-2 64.97%
DRSQC38LI 61.82%
DRSQC38LI-2 61.54%
BTU Listing
MODEL
Natural Gas
Propane
BTU / hr
Conversion kit req.
SIT Elect. Ignition
SIT Elect. Ignition BASIC
Vent size
Reduce to 4/7?
DRSQ38NI X 20,500
X 5/8 Yes
DRSQ38NI-2 X 24,000
X 5/8 Yes
DRSQ38LI X 16,500
X X 5/8 Yes
DRSQ38LI-2 X 19,500
X X 5/8 Yes
DRSQC38NI X 20,500
X 5/8 Yes
DRSQC38NI-2 X 24,000
X 5/8 Yes
DRSQC38LI X 16,500
X X 5/8 Yes
DRSQC38LI-2 X 19,500
X X 5/8 Yes
Introduction
Efficiency
Safety Alert Key
Young children should be carefully supervised when they are in the
same room as the appliance. Toddlers, young children, and others
may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at-risk individuals in the house. To restrict
access to a replace or stove, install an adjustable safety gate to keep
toddlers, young children, and other at-risk individuals out of the room
and away from hot surfaces
CAUTION
Indicates a hazardous situation which, if
not avoided, WILL result in death or serious
injury or property damage.
Indicates a hazardous situation which, if not
avoided, WILL result in minor or moderate
injury.
Indicates a hazardous situation which, if not
avoided, COULD result in death or serious
injury or property damage.
Indicates practices that are important, but
not related to personal injury.
DANGER
CAUTION
WARNING
NOTICE
3
General
XG0230 - 052020
Contents
Safety Alert Key .................................................................................. 2
Introduction ....................................................................................... 2
Efficiency ............................................................................................. 2
Section A: Before You Begin .......................................................................4
Installation Checklist ......................................................................................4
Standard Installation Checklist ....................................................................5
Rating Plate Sample .......................................................................................6
Section 1: Dimensions ....................................................................... 7
DelRay Square Dimensions ..........................................................................7
Section 2: Framing ............................................................................ 8
In Wall and Corner Dimensions ..................................................................8
Rear vent, rigid or flex ...................................................................................8
Top vent, flex ...................................................................................................8
Top vent, rigid .................................................................................................. 8
Clearances ........................................................................................................9
Section 3: Venting .............................................................................. 9
Restrictor plate ..............................................................................................10
Primary air adjustment ...............................................................................10
Section 3-3-1: Venting Layout ......................................................... 11
DRSQ38 5/8 TOP Venting - .........................................................................11
Wall and roof termination ..........................................................................11
DRSQ38 4/7 TOP Venting - .........................................................................11
Wall and roof termination ..........................................................................11
DRSQ38 Rear Venting ..................................................................................12
45° Corner Installation 5''/8'' .....................................................................12
45° or less Corner Installation 5''/8'' ........................................................12
Section 3-2: Installing a Roof Mounted Direct Vent Termination
............................................................................................................ 13
Section 3-2-1: Venting Layout ...................................................................13
Section 3-3: Installing a Wall Mounted Termination ................... 14
Section 3-1: Converting top/rear vent ....................................................15
Section 3-3-2.2: Alternate Venting Components 5"/8" ........................16
Section 3-3-2.2: Alternate Venting Components 4"/7" (For reduced
DRSQ38 units) ...............................................................................................17
Section 3-3-3: Heat Shields .............................................................. 18
Section 4: Wiring .............................................................................. 19
DRSQ (N/L) I Wiring Diagram .....................................................................19
Installation of the wall switch .....................................................................19
DRSQ (N/L) I-2 Wiring Diagram .................................................................20
Installation of Electrical Supply .................................................................20
Section 5: Installing the gas line.....................................................21
Fuel Type .........................................................................................................21
Gas Pressure .................................................................................................21
Section 5-3: GAS CONNECTION ................................................................ 21
Finishing Safety Zone ...................................................................................21
Section 6: Finishing .......................................................................... 22
Finishing Around the Fireplace .................................................................22
Sidewall clearances ......................................................................................22
Cement Board Install ................................................................................... 22
Elevated surface temperatures ...............................................................23
Standard installation ....................................................................................23
Venting ports open w/ vented chase .......................................................23
Heat distribution kit installed ....................................................................23
Section8:Removing&InstallingtheScreen/Door .................... 24
Removing the Screen...................................................................................24
Reinstalling the Screen ................................................................................24
Removing the door ......................................................................................24
Reinstalling the door ....................................................................................24
PropaneConversion ........................................................................ 25
Section 9: Installing the Accessories .............................................. 27
The DelRay Square transitional burner ...................................................27
Installing glass media ...................................................................................27
Installing a contemporary scene (glass and stone) .............................27
Installing the speckled stone media ........................................................27
Traditional Logset Installation ...................................................................28
Birch Logset Installation..............................................................................30
Driftwood Logset Installation.....................................................................31
Black Reflective Glass ..................................................................................32
Brick Liner Install ..........................................................................................33
Section 10: Cleaning and Maintenance ........................................ 35
General............................................................................................................35
Cleaning ..........................................................................................................35
Pilot Burner Adjustment. ............................................................................35
Indoor fireplace in protected outdoor applications ...........................36
See through fireplace ..................................................................................36
Notes ...............................................................................................................36
Single sided fireplace ...................................................................................36
Appendix A: Venting Terminations ................................................ 37
Appendix B: Warranty ..................................................................... 38
Appendix B: Warranty Continued .................................................. 39
Appendix C: Amendment ................................................................ 40
(Gas Fireplace / Equipment sold in the State of Massachusetts) 40
Thisappliancemaybeinstalledinanaftermarket,
permanently located, manufactured home (USA
only)ormobilehome,wherenotprohibitedby
local codes.
This appliance is only for use with the type of gas
indicatedontheratingplate.Aconversionkitis
supplied with the appliance.
4
General
XG0230 - 052020
IMPORTANT MESSAGE: SAVE THESE INSTRUCTIONS
The DelRay replaces must be installed in accordance with these
instructions. Carefully read all the instructions in this manual rst.
Consult the Local Gas Branch to determine the need for a permit prior
to starting the installation. It is the responsibility of the installer to
ensure this replace is installed in compliance with the manufacturers
instructions and all applicable codes.
InstallationChecklist
Determine the desired install location of your replace.
See Section 1, Dimensions on Page 6, and refer to the Framing
Section 2 for details.
Select the location of your termination and resulting vent run.
Should it be impossible to meet the venting requirements laid out
in Section 3: Venting, please contact your Montigo dealer regarding
the use of a Montigo Power Vent.
Lay out the Vent run; calculating the required elbows and straight
runs of 5"/8" ex and/or rigid pipe.
Layout Electrical Requirements refer to Section 4: Wiring, for Details.
Refer to Section 5: Installing the Gas Line, for details on the gas
connection and access.
Refer to local codes and guidelines for installation requirements.
Installation and repairs should be done by a qualied contractor
and must conform to:
Installations in Canada must conform to the local codes or in the
absence of local codes to the current version of Natural Gas and
Propane Installation Code, CSA B149. Electrical installations must
conform to the local codes or, in the absence of local codes, to the
current version of Canadian Electrical Code, CSA C22.1.1
Installations in the USA must conform to the local codes or in the
absence of local codes to the current version of National Fuel Gas
Code, ANSI Z223.1/NFPA 54. Electrical installations must conform
to the local codes or, in the absence of local codes, to the current
version of the National Electrical Code, ANSI/NFPA 70. See Appendix
C for installation within the State of Massachusetts
Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the appliance
and to replace any part of the control system and any gas control that
has been under water
Due to high temperatures, the appliance should be located out of
trac and away from furniture and draperies
Children and adults should be alerted to the hazards of high surface
temperature and should stay away to avoid burns or clothing ignition
A barrier designed to reduce the risk of burns from the hot viewing
glass is provided with this appliance and shall be installed for the
protection of children and other at-risk individuals
Clothing or other ammable material should not be placed on or near
the appliance
Installation and repair should be done by a qualied service person.
The appliance should be inspected before use and at least annually
by a professional service person. More frequent cleaning might be
required due to excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners, and circulating air
passageways of the appliance be kept clean
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
ThisappliancemaybeinstalledasanOEMinstallationina
manufacturedhome(USAonly)ormobilehomeandmustbe
installed in accordance with the manufacturers instructions and
the Manufactured Home Construction and Safety Standard, Title 24
CFR, Part 3280, in the United States, or the Standard for Installation in
Mobile Homes, CAN/CSA Z240 MH, in Canada.
This appliance is only for use with the type(s) of gas indicated on
theratingplate.Aconversionkitissuppliedwiththeappliance.
Section A: Before You Begin
5
General
XG0230 - 052020
StandardInstallationChecklist
This standard installation checklist is to be used by the installer in conjunction with, not instead of, the instructions contained within this
installation manual.
Customer Date Installed:
Install Address: Location of Fireplace:
Installer:
Model (circle one): DRSQ38NI, DRSQ38NI-2, DRSQ38LI, DRSQ38LI-2,
Dealer Phone:
Serial #:
YES NO IF NO, WHY NOT?
Appliance Install: Section 2
Framing complies with install manual.
Standos have been installed.
Proper clearances have been maintained.
Venting: Section 3
Venting conguration complies with vent diagrams.
Venting installed, fastened, and secured in place maintaining proper clearance.
Firestops installed.
Exterior wall/roof ashing installed and sealed in compliance with local building code.
Terminations installed and sealed in compliance with local building code.
Direct vent termination is highest point in vent assembly.
Wiring/Electrical: Section 4
Unswitched power provided to the appliance PPO box.
Low voltage wire connected to dry contact wall switch (non-powered)*
Gas: Section 5
Proper appliance for fuel type.
Was a conversion performed?
Leak check performed & inlet pressure veried.
Finishing: Section 6
Only non-combustible materials installed in non-combustible areas.
Clearances meet installation manual requirements
Mantels and/or projections comply with install manual
Appliance Setup: Section 7 through 9
Media, door, and screen installed according to install manual
Manual given to home owner.
Started appliance and veried no gas leaks exist.
Comments:
6
General
XG0230 - 052020
Rating Plate Sample
Figure 1.1 Rating Plate for DelRay DRSQ38NI Figure 1.2 Rating Plate for DelRay DRSQ38NI-2
Serial No.:
N & H ( 0 - 4500 ft. / 0 - 1371 m.)
Max. Input Min. Input Output / Orifice Size / Taille D'Orifice Gas Manifold
Max. Entrée Min. Entrée
Rendement
Front/Avant Rear/Derrière Pressure / Pression
BTU/H BTU/H BTU/H
D'Admission Du Gaz
X
20,500 14,500 N/A 2.1 mm / N/A 3.5" W.C.
LAB Z21.88-2019 DRSQ38NI-2 V1.0
N'enlevez Pas Cette
Étiquette
Propane / Gaz Propane
FOR USE WITH GLASS DOORS AND SCREENS CERTIFIED WITH THE APPLIANCE ONLY
Pour utilisation avec portes de verre and écrans de certifiés avec l'appareil seulement
*Refer to installation manual for more information.
*Référez-vous au manuel d'installation pour plus d'information.
Made in China
Fabriqué en Chine
16,500 13,500 N/A 1.2 mm / N/A 10" W.C. 13" W.C.
Fuel Type / Type De Carburant:
Min. Gas Supply
Pressure/ Min. Pression
Do Not Remove
This Label
D'Alimentation Du Gaz
Natural Gas / Gaz Naturel
5.5" W.C.
Mantel/Manteau: 6"
Tested To / Examiné À: CSA/ANSI Z21.88-2019 / CSA2.33-2019
Recess Depth/ Profondeur D'Encadrement:
N/A
Electrical Rating / Estimation Électrique:115V / 1Ph / 60Hz /less than 12A
Flue: 1"
Altitude Rating / Estimation D'Altitude:
X-XXXXXX-XXXXXX
Top-Top Vent/Du Haut-Évent Du Haut: 21"
Top-Rear Vent/Du Haut-Évent Arrière: 17"
Distributed by / distribué par: Canadian Heating Products Inc., Langley BC, (www.montigo.com)
Floor/Plancher: 0"
Montigo DelRay Corp., Ferndale, WA. (www.montigo.com)
Not for use with air filters. / Pas pour l'usage avec des filtres à air.
Sides/Côtés: 1"
Model No. Modèle.
DRSQ38NI
Back/Derrière: 1.5"
Type: Vented Gas Fireplace Heater For Indoor Use Only
*Clearance to Combustibles
Not for use with solid fuel. / Pas pour l'usage avec le combustible solide.
*Degagements Aux Combustibles
Serial No.:
N & H ( 0 - 4500 ft. / 0 - 1371 m.)
Max. Input Min. Input Output / Orifice Size / Taille D'Orifice Gas Manifold
Max. Entrée Min. Entrée
Rendement
Front/Avant Rear/Derrière Pressure / Pression
BTU/H BTU/H BTU/H
D'Admission Du Gaz
X
24,000 16,500 N/A 2.25 mm / N/A 3.5" W.C.
LAB Z21.88-2019 DRSQ38NI-2 V1.0
N'enlevez Pas Cette
Étiquette
Propane / Gaz Propane
FOR USE WITH GLASS DOORS AND SCREENS CERTIFIED WITH THE APPLIANCE ONLY
Pour utilisation avec portes de verre and écrans de certifiés avec l'appareil seulement
*Refer to installation manual for more information.
*Référez-vous au manuel d'installation pour plus d'information.
Made in China
Fabriqué en Chine
19,500 15,500 N/A 1.3 mm / N/A 10" W.C. 13" W.C.
Fuel Type / Type De Carburant:
Min. Gas Supply
Pressure/ Min. Pression
Do Not Remove
This Label
D'Alimentation Du Gaz
Natural Gas / Gaz Naturel
5.5" W.C.
Mantel/Manteau: 6"
Tested To / Examiné À: CSA/ANSI Z21.88-2019 / CSA2.33-2019
Recess Depth/ Profondeur D'Encadrement:
N/A
Electrical Rating / Estimation Électrique:115V / 1Ph / 60Hz /less than 12A
Flue: 1"
Altitude Rating / Estimation D'Altitude:
X-XXXXXX-XXXXXX
Top-Top Vent/Du Haut-Évent Du Haut: 21"
Top-Rear Vent/Du Haut-Évent Arrière: 17"
Distributed by / distribué par: Canadian Heating Products Inc., Langley BC, (www.montigo.com)
Floor/Plancher: 0"
Montigo DelRay Corp., Ferndale, WA. (www.montigo.com)
Not for use with air filters. / Pas pour l'usage avec des filtres à air.
Sides/Côtés: 0"
Model No. Modèle.
DRSQ38NI-2
Back/Derrière: 1.5"
Type: Vented Gas Fireplace Heater For Indoor Use Only
*Clearance to Combustibles
Not for use with solid fuel. / Pas pour l'usage avec le combustible solide.
*Degagements Aux Combustibles
7
Installation
XG0230 - 052020
DelRay Square Dimensions
Section 1: Dimensions
BASIC MODELS
DRSQ38NI DRSQC38NI
DRSQ38LI DRSQC38LI
FULL LOAD MODELS
DRSQ38NI-2 DRSQC38NI-2
DRSQ38LI-2 DRSQC38LI-2
965.403
38"
580.784
22
7
8
"
855.370
33
11
16
"
54.102
2
1
8
"
54.102
2
1
8
"
990.549
39"
533.400
21"
1015.086
39
15
16
"
810.514
31
15
16
"
582.613
22
15
16
"
184.614
7
1
4
"
222.409
8
3
4
"
419.075
16
1
2
"
990.549
39"
431.470
17"
775.487
30
1
2
"
12.548
1
2
"
526.298
20
3
4
"
857.758
33
3
4
"
201.473
7
15
16
"
419.075
16
1
2
"
POWER
SUPPLY
GAS
SUPPLY
Screen I.D.
opening
Fireplace I.D.
opening
TOP OR REAR
VENT
REVISIONS
REV.
DESCRIPTION
DATE
CHANGED BY
-
.
- -
ITEM NO.
PART NUMBER
DESCRIPTION
MATERIAL
QTY.
1
1-2 valve handle
Material <not specified>
1
2
3-8 to 3-8
Safety Valve
Material <not specified>
1
3
BR019-20
Side Ceramic Liner Bracket
26 GA Satin
2
4
CFL-DRSQ38A
CFL-DRSQ38A-Back Ceramic Fiber Liner
1
5
CM209
CABLE CLAMP
SATIN/26
2
6
DL36090-10
5" Blanking Disk
20GA Satin-Coated
2
7
DRSQ38-Gasket
Material <not specified>
1
8
DRSQ38001-20
Firebox Top
20 GA Satin
1
9
DRSQ38002-20
Right Side
16 GA Satin
1
10
DRSQ38003-20
Front Panel
20 GA Satin-Coated
1
11
DRSQ38004-20
Left Side
16 GA Satin
1
12
DRSQ38005-20
Back Wall
20 GA Satin
1
13
DRSQ38006-20
Back Top Spacer
20 GA Satin
1
14
DRSQ38007-20
Left Glass Bottom Bracket
20 GA Satin
1
15
DRSQ38008-20
Right Glass Bottom Bracket
20 GA Satin
1
16
DRSQ38010-10
Rock Tray
188 CRS PERF/20
1
17 DRSQ380100
DRSQ-Spring Latch Casing
Carbon Steel
2
18
DRSQ38011-20
Small Tray Bracket 20 GA Satin
2
19
DRSQ38012-20
Back Bord & Tray Bracket
16 GA Satin
3
20
DRSQ38013-20
Lower Door Retainer
18 Ga Satin-Coated
1
21
DRSQ38014-20
Glass Door Frame
16 GA Satin-Coated
1
22
DRSQ38015-20
Base Knob Plate
16 GA Satin
2
23
DRSQ38016-10
Top Knob Plate
14 GA Satin
2
24
DRSQ38017-20
Door Knob
14 GA Satin
2
25
DRSQ38018-20
Air Take off Box 1
20 GA Satin
1
26
DRSQ38019-20
Air Take off Box 2
20 GA Satin
1
27
DRSQ38020-20
Firebox Wrapper Top
20 GA Satin
1
28
DRSQ38021-20
Firebox Wrapper Bottom
20 GA Satin
1
29
DRSQ38022-10
Left & Right Spacer
20 GA Satin
2
30
DRSQ38023-20
Firebox Wrapper Top Support
16 GA Satin
2
31
DRSQ38030-20
Pilot Cover
16 GA 304 SS/NP
1
32
DRSQ38032-10
Fire Box Foot Support
20 GA Satin
2
33
DRSQ38033-20
Firebox Top
20 GA Satin
1
34
DRSQ38034-20
Front Panel Flange
20GA Satin-Coated
2
35
DRSQ38035-20
Side Front Panel Flange
20GA Satin-Coated
2
36
DRSQ38036-20
Back Wall Front Bracket
20 GA Satin
2
37
DRSQ38038-10
Screen Top Support
20 GA Satin-Coated
1
38
DRSQ38039-20
Outside Skin Wrapper
20 GA Satin
1
39
DRSQ38040-20
Outer Bottom Skin
20 GA Satin
1
40
DRSQ38042-20
Outer Skin Top / Vent
20 GA Satin
1
41
DRSQ38043-20
Valve Cover
18 GA Satin
1
42
DRSQ38044-10
8" Full Collar Lid
22 GA Satin-Coated
1
43
DRSQ38047-10
8" Collar Cover
22 GA Satin-Coated
1
44
DRSQ38048-20
5" Pipe
22 GA Satin
1
45
DRSQ38059-20
Top Burner
16 GA Aluminized steel
1
46 DRSQ38060
Safety Screen DRSQ38
Safety Mesh / Steel Frame
1
47
DRSQ38062-20
Firebox Top Side Bracket
22 GA Satin
2
48
DRSQ38063-20
Wall Support Bracket
20 GA Satin
2
49
DRSQ38064-20
Burner Baffle
26 GA Satin-Coated
1
50
DRSQ38068-20
Side Air Guide
22 GA Satin
2
51
DRSQ38069-20
Fron Air Guide
22 GA Satin
1
52
DRSQ38071-20
Air Flow Bracket
20 GA Satin
1
53
DRSQ38073-20
Top Insulation Bracket Left/Right
22 GA Satin
1
54
DRSQ38074-20
Outside Insulation Cover
20 GA Satin
2
55
DRSQ38079-20
Restriction Bracket Plate
20 GA Satin
1
56
DRSQ38085-20
Bottom Burner
16 GA Aluminized steel
1
57
DRSQ38086-20
Burner Tray
18 GA Satin-Coated
1
58
DRSQ38087-20
Media Tray Bracket 16 GA Satin
2
59
DRSQ38088-20
Insulation Back Wall
20 GA Satin
1
60
DRSQ38089-20
Media Tray
20 GA Satin
1
61
DRSQ38090-20
DRSQ38 Pilot Mounting Bracket
18 GA Satin-Coated
1
62
DRSQ38091-20
Insulation Wall Bracket
20 GA Satin
4
63
DRSQ38093-10
Restriction Plate
20 GA Satin
1
64
EBOX491
PO BOX OUTER COVER
22 Ga Satin
1
65
EBOX492
PO BOX INNER COVER
20 Ga Satin
1
66
EC1220
CLAMP CONNECTOR, 1/2", SL20C20
1
67
EC1378
Fan L/H
Material <not specified>
2
68
EC1509
Material <not specified>
2
69
GC3089
Proflame Valve W?Stepper Motor NG
1
70
GF1012
Material <not specified>
1
71
GF1111
Gas Orifice Mount
1
72
GF1114
Shutoff, Valve, 3/8" Flare to 3/8" Flare
Brass
2
73
GF2103
GF2103 90d. FORMED VENT. TUBE
1
74
GL4077
DRSQ38 Window Glass Neoceram Glass 5mm
1
75
GL5119
DRSQ38 Left Side-Black Ceramic Glass
4mm Black Ceramic Glass
1
76
GL5120
DRSQ38 Back-Black Ceramic Glass
4mm Black Ceramic Glass
1
77
GL5121
DRSQ38 Right Side-Black Ceramic Glass
4mm Black Ceramic Glass
1
78
H34122
FAN MOUNTING BRACKET
16Ga. SATIN
2
79
H42118
8" BLANKING DISK
22Ga. SATIN
1
80
H42119-10
5" BLANKING PLATE
16Ga. SATIN
1
81
HCOL001
5 COLLAR
22Ga. SATIN
1
82
HCOL003
8 COLLAR
22Ga. SATIN
1
83
HCOL004
8" PIPE
1
84
HE38022-10
Wire Gasket Clamp
10 Ga. Hot Roll
1
85
HW1009
Magnet block
2
86
HW2032
1/4"NC Machine Nut
2
87
HW2310
Compression Spring Ø .070
ASTM A401
2
88
HW2311
Bolt 0.25 NC x 3.5 in Hex Shoulder Bolt
2
89
HW2312
Cup-Centerpin Washer
2
90
HW2313
Washer .67"
16 GA Satin
2
91
HW2314
1/4-20 Hex Coupling Nut
Zink Plated - UNC
2
92
IN1066
8" COLLAR GASKET
1/8" MANNIGLASS
2
93
IN1125
Wire Gasket
CG365 1/4" (PSA 1 side
only)
1
94
IN1140
Orifice Mount Gasket
1/8" MANNIGLASS
1
95
IN1196
5 Collar gasket
1/8" Manniglas Grey
2
96
IN2075-s
DRSQ38 Burner Tray Gasket
1/8 MANNIGLASS
1
97
IN2076
DRSQ Lock Gasket
1/8 MANNIGLASS
2
98
IN2077
DRSQ Air Channel Gasket
1/8 MANNIGLASS
1
99
IN2079
DRSQ38 Insolation.
1/2" MINERAL WOOL
1
100
IN2080
Air flow box Insulation
1/2" MINERAL WOOL
1
101
IN2081
Outside Skin Insolation
1" MINERAL WOOL 2
102
MNR36010-20
Fire Box Foot
16 GA Satin-Coated
2
103
MNR36030-10
Service Door
20 GA Satin
1
104
MNR36034-20
Safety Screen Handle
20 GA Satin-Coated
2
105
MNR36041-20
7" Pipe Bracket 22 GA Satin-Coated
2
106
MNR36075-20
Gas Valve Base Bracket
18 GA Satin
1
107
MNR36076-20
Tray Clip
18 GA Satin
1
108
MNR36077-20
Control Drawer Slide
20 GA Satin-Coated
1
109
MNR36078-20
Drawer Slide Bracket
20 GA Satin
2
110
MNR36079-20
Gas Valve Bracket
16 GA Satin
1
111
MNR36087-20
Glass Bracket
22 GA Satin-Coated
2
112
MNR36097-20
THERMODISC BRACKET
22Ga. SATIN
1
113
OR0001
Gas Orifice P0512
1
114
PPOBOXONLY
Power Outlet Junction Box Only
1
115
sitpilot IPI
SIT PILOT ASSY IPI GC3036 (NG)
1
1:16
DWG. NO.
SHEET 2 OF 2
WEIGHT:
DRSQ38-Full Assembly
Finish
MATERIAL
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Revision / Date
Drawn by
DATE
NAME
25/10/2019
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Full Assembly
April-17-20 12:33:31 PM
SCALE
DM
Description
Full Assembly
Revision
8
Installation
XG0230 - 052020
1016
40"
MIN.
457
18"
1128
44
7
16
"
MIN.
1397
55"
1:24
DWG. NO.
SHEET 1 OF 2
WEIGHT:
DRSQ38-Rear Vent Chase Framing Assembly
Finish
MATERIAL
Revision / Date
Drawn by
DATE
NAME
05/05/2020
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Rear Vent Chase Framing Assembly
May-13-20 7:57:36 AM
SCALE
DM
Description
DRSQ38-Rear Vent Chase Framing Assembly
Revision
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Section 2: Framing
1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled replace shown below in table
NOTE: When constructing the framed opening, please ensure there is
access to install the gas line when the unit is installed
Figure 3.b Framing dimensions (Straight wall & Corner Installation).
In Wall and Corner Dimensions
A
3"
B
C
D
56
1
2
"
15.000
45.0°
8.000
1.000
1.000
REVISIONS
REV.
DESCRIPTION
DATE
CHANGED BY
-
.
- -
1:64
DWG. NO.
SHEET 1 OF 1
WEIGHT:
DRSQ38-Corner Framing Assembly
Finish
MATERIAL
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Revision / Date
Drawn by
DATE
NAME
16/01/2020
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Corner Framing Assembly
April-23-20 9:22:45 AM
SCALE
DM
Description
DRSQ38-Corner Framing Assembly
Revision
TOP VENTED
A B C D
DRSQ38
Flex 59'' 44⁄'' 18'' 40"
Rigid 62⁄'' 44⁄'' 18'' 40"
REAR VENTED
A B C D
DRSQ38
55'' 44⁄'' 18'' 40"
Rearvent,rigidorflex
Topvent,flex Topvent,rigid
HEAT DEFLECTOR
(REQUIRED FOR
FULL LOAD UNITS
ONLY)
HEAT DEFLECTOR (SUPPLIED)
MIN.
55"
30
1
2
"
24
1
2
"
17
1
16
"
MIN.
PTO4F
OUTDOOR
WALL
REAR VENT 5/8" CHASE ASSEMBLY
DELRAY
UNIT
FLOOR
1:48
DWG. NO.
SHEET 1 OF 2
WEIGHT:
DRSQ38 - Venting Assembly
Finish
MATERIAL
Revision / Date
Drawn by
DATE
NAME
05/05/2020
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Rear Vent Chase Full Assembly
May-15-20 7:53:41 AM
SCALE
DM
Description
DRSQ38 - Venting Assembly
Revision
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
MIN.
59"
1"
MIN.
8
1
2
"
14
1
2
"
MIN.
6
1
2
"
52
1
2
"
FLEX
PIPE
PTO4F
OUTDOOR
WALL
OUTDOOR
WALL
TOP VENT 5/8" FLEX PIPE
CHASE ASSEMBLY
MIN.
62
1
8
"
1"
MIN.
8
1
2
"
6
9
16
"
55
9
16
"
17
9
16
"
PTO4F
TOP VENT 5/8" RIGID PIPE
CHASE ASSEMBLY
RIGID
PIPE
FLOOR
FLOOR
DELRAY
UNIT
DELRAY
UNIT
REVISIONS
REV.
DESCRIPTION
DATE
CHANGED BY
-
.
- -
1:32
DWG. NO.
SHEET 2 OF 2
WEIGHT:
DRSQ36 - Venting Assembly
Finish
MATERIAL
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Revision / Date
Drawn by
DATE
NAME
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Top Flex Vent Chase Full Assembly
May-15-20 7:56:42 AM
SCALE
DM
Description
Revision
DRSQ36 - Venting Assembly
12/5/2020
MIN.
59"
1"
MIN.
8
1
2
"
14
1
2
"
MIN.
6
1
2
"
52
1
2
"
FLEX
PIPE
PTO4F
OUTDOOR
WALL
OUTDOOR
WALL
TOP VENT 5/8" FLEX PIPE
CHASE ASSEMBLY
MIN.
62
1
8
"
1"
MIN.
8
1
2
"
6
9
16
"
55
9
16
"
17
9
16
"
PTO4F
TOP VENT 5/8" RIGID PIPE
CHASE ASSEMBLY
RIGID
PIPE
FLOOR
FLOOR
DELRAY
UNIT
DELRAY
UNIT
REVISIONS
REV.
DESCRIPTION
DATE
CHANGED BY
-
.
- -
1:32
DWG. NO.
SHEET 2 OF 2
WEIGHT:
DRSQ36 - Venting Assembly
Finish
MATERIAL
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Revision / Date
Drawn by
DATE
NAME
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ38-Top Flex Vent Chase Full Assembly
May-15-20 7:56:42 AM
SCALE
DM
Description
Revision
DRSQ36 - Venting Assembly
12/5/2020
9
Installation
XG0230 - 052020
Clearances must be in accordance with local installation codes and
the requirements of the gas supplier
NOTICE
When this appliance is installed directly on ANY combustible other
than wood ooring (carpet, vinyl, etc.). It must be installed on an
equivalent wood or metal panel. This material must extend the full
width and depth of the appliance.
WARNING
Clearances
MODEL
Top - Top
vent†
Top - Rear
vent†
Rear
Sides
Floor
Mantel
Vent Pipe
DRSQ38*I 21" 17" 1.5" 1" 0" 6"
1'' all around
2" on the
horizontal
DRSQ38*I-2 21" 17" 1.5" 0" 0" 6"
1'' all around
2" on the
horizontal
NOTES:
Clearance from top of replace to a ceiling within the replace
enclosure.
Figure 4. Combustible Wall Clearances
When installing a shelf over the top of the replaces, the following
guidelines must be adhered to:
Section 3: Venting
Montigo oers a variety of direct venting and termination options. The
direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
Venting originates from the top or rear of the unit
Venting can terminate through the roof or through an exterior wall.
Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
Once the termination location has been established, refer to the
appropriate section below for installation details
All replaces shipped from the factory are top vent.
Silicone application is NOT required when joining Montigo vent
pipes and components.
Under no circumstances can Montigo ex venting be cut to
accommodate an installation. Use an alternative length to complete
your vent run. (Excluding ex included in the PVK05, MVK05)
NOTICE
PVK05 (5/8), PVK05F (5/8)
PVK05 Flex Vent Kit is a standalone 5 ft. vent kit that cannot
be combined with Montigo Flex or Montigo Rigid pipe to
extend beyond the 5ft of ex included in this kit. The Flex in
this kit can be cut down if shortening is required. Any other
venting conguration beyond the 5ft included in the kit will
require going to either Montigo Rigid pipe or Montigo Flex pipe
referenced in the manual pages Venting section.
PVK05 Includes RHS101 heat shield, 5’ ex pipe (with spacers),
and PTO4 termination
PVK05F (WITH TERM. FRAME) Includes RHS101 heat shield, 5’
ex pipe (with spacers), and PTO4F termination
Figure 4.a PVK05F Flex Vent Kit shown
10
Installation
XG0230 - 052020
Restrictor plate Primary air adjustment
The replace is equipped with a factory installed restrictor set at fully
open. If replace vent is terminated horizontally, NEVER CLOSE the
restrictor completely. Adjust the restrictor opening by judging ame
characteristics after 20 minutes of burn time (on cold start, for rst
few minutes the ames might be blue).
If ames ghost o the burners or if sooting occurs (mostly with propane)
open the restrictor fully and work backwards in increments to determine
the correct position.
FOR REAR VENT RESTRICTOR MUST BE LEFT FULL OPEN.
FOR POWER VENTED UNITS RESTRICTOR MUST BE CLOSED.
For most runs that include lengths of both horizontal and vertical pipe,
especially ones with multiple elbows or long horizontal runs, restrictor
should be full open.
Restrictor opening should be adjusted for long vertical lengths with
short horizontal runs or vertical only runs to reduce ue draft.
Recommended settings for vertical runs (depends on installation
specics, altitude, fuel and other factors):
For Verticals 3’ to 6’ – various between fully open to 1” open
For Verticals 7’ to 10’ – 1” open or fully closed
For Verticals over 10’ –fully closed
During initial installation, check primary air opening
(below are factory settings):
DRSQ38*I ⁄” for NG and ½” for Propane;
DRSQ38*I-2 ¼” for NG and full open for Propane.
The primary air might need adjusting from the factory setting for vertical
runs. If ame is sooting, primary air may need to be opened slightly
Smaller primary air opening means yellower ame.
Note: all adjustments to primary air must be made by qualied
installers. Very small changes in opening size make major changes in
ame appearance
Depending on desired ame appearance recommended primary air
adjustment limits: NG ⅛” – ¼” and propane ⅜” – Full open.
CLOSE
0.5" OPEN
1" OPEN
OPEN
1.75" OPEN
REVISIONS
REV.
DESCRIPTION
DATE
CHANGED BY
-
.
- -
1:4
DWG. NO.
SHEET 1 OF 1
WEIGHT:
DRSQ-Restriction Bracket Assembly
Finish
MATERIAL
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL
1/32"
TWO PLACE DECIMAL
.015"
THREE PLACE DECIMAL
.005"
ANGULAR
.5
ALL BENDS ARE ASSUMED
TO BE 90
UNLESS NOTED
OTHERWISE.
Revision / Date
Drawn by
DATE
NAME
28/05/2020
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
Y:\Products\Residential Products\R&D Projects\DelRay\DelRay Square\DelRay38\Cad Drawings\DRSQ-Restriction Bracket Assembly
May-28-20 2:38:29 PM
SCALE
DM
Description
DRSQ-Restriction Bracket Assembly
Revision
11
Installation
XG0230 - 052020
2'2'
16"16"
26'26'
24'24'
10'10'
6'6'
30'30'
14'14'
20'20'
4'4'
2'2'
13"
4"
13" min. vert
for wall term
4" min. vert
for wall term
(elbow right
on collar)
4' min. vert
for roof term
4' min. vert
for roof term
16" min. horiz for
wall term
16" min. horiz for
wall term
34' ok for straight
vertical runs
34' ok for straight
vertical runs
28'28'
12'12'
18'18'
8'8'
32'
34'
32'
34'
16'16'
22'22'
Vertical Height (Ft.) "V"
Vertical Height (Ft.) "V"
Horizontal Run (Ft.) "H"Horizontal Run (Ft.) "H"
6'6' 10'10' 14'14' 18'18' 22'22' 4'4' 8'8' 12'12' 16'16' 20'20' 24'24'
Section 3-3-1: Venting Layout
DRSQ38 4/7 TOP Venting -
Wall and roof termination
Maximumtotalventrunallowedis34ft.(V+H≤34ft.)
Forlongerventruns,apowerventisrequired
V + H are measured from the center of vent elbows
13” minimum vertical pipe run required
Maximum vertical run allowed is 32 ft. (V max).
Maximum horizontal run allowed is 25 ft. (H max).
DRSQ38 5/8 TOP Venting -
Wall and roof termination
Maximumtotalventrunallowedis34ft.(V+H≤34ft.)
Forlongerventruns,apowerventisrequired
V + H are measured from the center of vent elbows
Elbow may be attached directly to the top of the unit.
Maximum vertical run allowed is 32 ft. (V max).
Maximum horizontal run allowed is 25 ft. (H max).
Elbows:
Two 45° elbows = 90° elbow
Each elbow reduces vent run by 3’
Max elbows = 4
Elbows:
Two 45° elbows = 90° elbow
Each elbow reduces vent run by 3’
Max elbows = 4
*4" vertical minimum is based on the vent center of an elbow mounted
directly on the top of the unit.
22
V MIN. H MAX.
13" 16"
2' 9'
3' 16'
4'-9' 25'
10'-34' SEE GRAPH
V MIN. H MAX.
4"* 28"
1' 6'
2' 12'
3' 20'
4' 25'
10'-34' SEE GRAPH
Acceptable
vent run within
shaded areas.
Acceptable
vent run within
shaded areas.
1 elbow permitted
1 elbow permitted
1-2 elbows permitted
1-2 elbows permitted
1-3 elbows permitted
1-3 elbows permitted
1-4 elbows permitted
1-4 elbows permitted
12
Installation
XG0230 - 052020
DRSQ38 Rear Venting
A maximum 18" of horizontal run is allowed on rear vented applications ,
though the addition of a 45° elbow is permitted for corner installations.
REAR VENTING NOT PERMITTED FOR 4/7 VENTING.
Figure 9.b Straight run, Rear Vented, wall mounted termination.
Hearth
Termination
Heat Sheild
PXT20 Extention
18''
Max.
18'' Max. horozontal
run with no vertical lift
30½''
45°CornerInstallation5''/8''
Attach an EEL-45 (45° elbow) directly onto the ue collar and attach it
to the EEL-45, cut the MXT-20 to suit. Slide the replace into position
and attach to the termination.
45°orlessCornerInstallation5''/8''
Use an PTO-4 termination and an PFL-1 or PFL-2/PFL-2 (12" or 24"
compressed length) and a frame, if appropriate. Flex may be turned
to obtain desired degree of angle required but must not exceed 45°.
PVK05kitcanbealsobeused
NOTE: The PVK05 / PVK05F kit is available for top vent corner FLEX
application (NG only). The Kit includes a heat shield, ex pipe, and a
termination with or without a mounting frame.
Corner Installation is available for NATURAL GAS UNITS ONLY
NOTICE
RHS 101 (5"8")
Heat Sheild
RHS 101 (5"8")
Heat Sheild
PEL- 45 Elbow (5"/8")
PXT20 (5"8")
Flue Collar
Flue Collar
Termination
Termination
Flex Section
13
Installation
XG0230 - 052020
Roof mounted terminations
The following details are some possible congurations for roof mounted
terminations. See below.
This section applies to installations where the direct vent termination
will be roof mounted.
Section 3-2-1: Venting Layout
Selection of components and details of venting lay out should adhere
to the following guidelines:
The maximum termination point is 34’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern may
be aected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphalt shingles, cedar
shakes, etc). This distance should be measured from the high side of
the roof slope where the ue ashing intersects the roong materials.
See Appendix A for termination locations.
For a more detailed diagram of allowed termination locations, see
Appendix A.
A maximum of two osets (each oset is made up of 2-90° bends)
may be made for vertical vent runs.
Firestops must be installed as required by National & local codes.
Ensure all horizontal runs are supported with a minimum of 3
supports per 10’ of venting.
Install all roof ashing and storm collars as shown.
Figure 6. Top vent, roof mounted termi-
nation with no oset in vent run.
Figure 6.b Top vent, Roof mounted with 1
oset (1 oset= two 90° bends).
Figure 6.c Top vent, Roof mounted with 2
osets (1 oset= two 90° bends).
Figure 6.d Side vent, Roof mounted vent-
ing (1 = 90° bend).
Section 3-2: Installing a Roof Mounted Direct Vent
Termination
PVTK1
Termination
PVTK1
Termination
PVTK1
Termination
Storm collar
Storm collar
Storm collar
2' min2' min
2' min
2' min
Support straps
OR Support ring
and plates
Support ring
and plates
Firestop
PEXT
PEXT-10
Adaptor
Flue
Collar
Roof ashing
Roof ashing
Roof ashing
Firestop
Firestop
Firestop
34' Max.
34' Max.
34' Max.
34' Max.
Support straps
OR Support ring
and plates
Support straps
OR Support ring
and plates
Support straps
OR Support ring
and plates
PVTK1
Termination
Storm collar
Roof ashing
14
Installation
XG0230 - 052020
Figure 7. Installing a PTO4-F, MTO4-F termination.
Figure 7.b Installing a MTO, PTO termination with the MSR frame.
Figure 7.c Installing a MTO, PTO termination with the BSR frame.
Figure 7.d Installing a PTO termination with MOSR frame.
Figure 7.e Installing the VSS Vinyl Shield.
Figure 7.f Installing a MTO, PTO termination heat guard.
1
12”
2”
1
2”
12”
This section applies to installations where the direct vent termination
will be wall mounted. NOTE: If subject to a highly corrosive environment
i.e. Seaside, Montigo recommends using Stainless Steel Termination.
Section 3-3: Installing a Wall Mounted Termination
Installationofterminationwithbuiltinframe
A termination with a built-in frame is installed during framing of a
structure.
1. Frame the termination opening to 11" x 11".
2. Install exterior sheathing to the structure framing.
3. Fasten the termination to the sheathing using a minimum of 4 screws.
MSR Frame
PTO-4 (5"/8")
Termination
MTO-4 (4"/7")
Termination
PTO-4F (5"/8")
Termination
MTO-4F (4"/7")
Termination
Installationofaterminationshieldforvinylsiding
The VSS Termination shield is installed when the exterior of a structure
is clad with Vinyl siding. It is placed directly above, and on-center with
the termination.
Installation of termination frame at time of framing
Terminations with a MSR frame allow the installation of the frame prior
to installation of the termination.
1. Frame the termination opening to 12" x 12".
2. Secure the MSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the MSR Frame using a minimum of 4 screws.
1. Frame the MOSR opening to 12" x 12".
2. Fasten the MOSR frame to the interior side of the studs, concrete,
or nished wall construction using a minimum of 4 screws.
3. Insert the termination into the MOSR frame as shown here, (from
the inside) and attach to the MOSR by installing a min. quantity of 4
bolts into the threaded nuts on the MOSR Frame.
Installation of termination frame at time of framing in masonry
Terminations with a BSR frame allow the installation of the frame in
masonry prior to the installation of the termination
1. Frame the BSR opening to 12" x 12".
2. Secure the BSR Frame to the exterior sheathing of the structure.
3. Fasten the termination to the BSR Frame using a minimum of 4 screws.
BSR Frame
MTKOG 5"/8") MTKOG 4"/7")
Installing heat guards
Installing heat guards over terminations is recommended in installations
where the termination is located within 7' feet above grade, or above
a pedestrian walkway, and may be required by code in public areas.
1. Ensure that the two long mounting brackets are facing the bottom
of the termination (See inset). This will provide more heat protection
at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal
screws.
1”
11”
Framing
Exterior
Sheathing
Fastening Hard-
ware, minimum
4-screws
Framing
Exterior
Sheathing
Fastening Hardware,
minimum 4-screws
PTO-4 (5"/8")
Termination
MTO-4 (4"/7")
Termination
Framing
Exterior
Sheathing
Fastening Hardware,
minimum 4-screws
Exterior Vinyl
siding
PTO-4 (5"/8")
Termination
MTO-4 (4"/7")
Termination
VSS Vinyl shield
Installation of termination from inside structure
A Termination with a MOSR Frame is installed from the inside of the
structure. These are commonly used in high-rise construction.
MOSR Frame
PTO-4 (5"/8")
Termination
MTO-4 (4"/7")
Termination
12”
12”
Fastening Hardware,
minimum 4-screws
Framing,
concrete
or other
materials
Exterior
Sheathing, concrete
or other materials
15
Installation
XG0230 - 052020
Connectionandinstallationofthevent
components should adhere to the following
guidelines:
Use any combination of rigid and ex pipe as required and in any
orientation (Male connectors can face in any direction).
Flex sections may be stretched up to 50% of their total length (e.g.
a 24” section maybe stretched to 36”).
Connect all vent sections using a minimum of three sheet metal
screws on the outer pipe ue.
Ensure the pipe ends male to female slide in a minimum of 1 1/2”
of overlap.
Ensure all horizontal runs are supported with a minimum of 3
supports per 10’ of venting.
When hanging/supporting venting, ensure that 1” clearance is
maintained on sides and bottom of vent runs and 2” above horizontal
vent runs to any combustible material.
Rigid pipe may be cut less than half way from the FEMALE END ONLY.
Ensure when cutting sections of rigid pipe to maintain integrity of
internal supports.
Flex pipe cannot be cut
Place the springs, supplied with the pipe kit (ex only), between the
outer and inner pipes to keep the pipes separate and avoid any
possible hot spots.
Montigo recommends the use of a ex section for the rst section of
venting connected directly to the replace, oering greater exibility
of installation and absorption of movement.
Firestops must be installed as required by national & local codes.
Montigo recommends that all exterior corners and joints be sealed
with exterior caulking. However, we encourage you to consult your
Building Envelope Engineer or Waterproong Consultant for further
recommendations.
IMPORTANT:
Please refer to your Building Envelope Engineer
or Waterproong Consultant for a review of ALL
penetrations through exterior walls or the roof.
Figure 7. Flue cover and collar removal and install, Top Vented replace.
Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
Venting can originate from the unit through the top or through the rear
Venting can terminate through the roof or through an exterior wall.
Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
Once the termination location has been established, refer to the
appropriate section below for installation details
All replaces shipped from the factory are top vent.
Silicone application is NOT required when joining Montigo vent
pipes and components.
Section3-1:Convertingtop/rearvent
Use the following instructions to convert a unit for rear vent use:
Remove the rear ue cover and gasket on the ue outlet.
Next, Remove the Top ue collar's on the ue outlet.
Install the (removed) rear ue cover and gasket material, to the Top
vent outlet. Fasten the cover with included hardware.
Install the collars to the rear vent outlet using the included hardware.
16
Installation
XG0230 - 052020
Section 3-3-2.2: Alternate Venting Components 5"/8"
The following components are approved for use with Montigo products. Please contact your local Montigo
dealer for further information.
Component
Montigo Part Number
Simpson Duravent
Part Number
ICC
Part Number
MetalFab
Part Number
Selkirk
Part Number
Flexmaster
Part Number
Termination PTO4 (3" Length)
PTO4F (3" Length)
PVTK1SS (5/8 Vent)
58DVA-HC (Horiz. 5/8 vent)
58DVA-VCH (Vert.5/8 Vent)
Rigid Sections
(5/8 Vent)
PEXT - 1 (12" f/m)
PEXT - 2 (24" f/m)
PEXT - 3 (36" f/m)
PEXT - 4 (48" f/m)
PEXT - 6 (72" f/m)
58DVA-06 (6")
58DVA-09 (9")
58DVA-12 (12")
58DVA-18 (18")
58DVA-24 (24")
58DVA-36 (36")
58DVA-48 (48")
58DVA-60 (60")
5DL6 (6")
5DL9 (9")
5DL1 (12")
5DL2 (24")
5DL3 (36")
5DL4 (48")
5D6 (6")
5D12 (12")
5D18 (18")
5D24 (24")
5D36 (36")
5D48 (48")
5DT-06
5DT-09
5DT-12
5DT-18
5DT-24
5DT-36
5DT-48
5DVKIT58X01
5DVKIT58X01.5
5DVKIT58X02
5DVKIT58X03
5DVKIT58X04
5DVKIT58X06
Rigid Pipe Extension PXT12 (12" f/f)
PXT20 (20" f/f)
58DVA-08A (12")
58DVA-16A (20")
5DLT (12")
5DLS1 (12")
5DLT2 (20")
5DSL2 (20")
5DAL (3" to 10")
5DT-AJ12 (12")
Rigid Telescopic Pipe 58DVA-17TA
58DVA-24TA
5DLA30
Elbows
(5/8 Vent)
PEL-90MM (m/m 90º)
PEL-90FF ( f/f 90º)
PEL-90FM ( f/m 90º)
PEL-45FM ( f/m 45º)
58DVA-E30 (30°)
58DVA-E45 (45°)
58DVA-E60 (60°)
58DVA-E90 (90°)
5DE45 (45°)
5DE90 (90°)
5D45L (45°)
5D90L (90°)
5DT-EL45 (45°)
5DT-EL90 (90°)
SupportRing&Plate PSPXT-8 58DVA-DC 5CS 5DT-CS
Firestop FS-8 58DVA-WFS
58DVA-FS
5CS 5DFS 5DT-FS
Roof Flashing PRF-7 (1/12 - 7/12 pt.)
PRF-12 (7/12 - 12/12 pt.)
58DVA-FF (at roof)
58DVA-F6 (0/12 - 6/12 pt.)
58DVA-F12 (7/12 - 12/12 pt.)
5DF (0/12 - 6/12 pt.)
5DF-12 (7/12 - 12/12 pt.)
5DT-AF6
5DT-AF12
Metal/Tile Roof Flashing 58DVA-F6DS (0/12-6/12 pt.)
58DVA-F12DS (7/12-12/12 pt.)
Heat Shield RHS101 58DVA-WTU
58DVA-WT
5WT
5WTE
5DT-WT 2DVWTE58
Attic Radiation Shield 58DVA-IS 5AS
5RDS
5DT-AIS
Vinyl Siding Heat Shield VSS
VSSSS
58DVA-VSK (Vinyl Siding
Stando)
Wall Support 58DVA-WS 5WS 5DWS 5DTWSB
OsetSupport 58DVA-ES 5OS 5DT-OS
Vaulted Ceiling Support 58DVA-CS 5SS DRS 5DT-CCS
Storm Collar SC8 58DVA-SC 5SC
5SQSC
5DSC 5DT-SC
Montigo Fireplace
Adapter
58DVA-AD-M1 TM-5AA6 5DNA
Montigo Termination
Adapter
58DVA-AD-M2 TM-5TA1 5DMTA
17
Installation
XG0230 - 052020
Section 3-3-2.2: Alternate Venting Components 4"/7" (For reduced DRSQ38 units)
The following venting components are approved for use with Montigo products. Please contact your local
Montigo dealer for further information.
Duravent
Co-Axial to Co-linear adapt.
Decreaser 58DVA-X46
Adapter 46DVA-CLAA
3”ex25’ 3DFA-25
3”ex35’ 3DFA-35
Termination 46DVA-CL33K
Component MontigoPartNumber SimpsonDuraventPartNumber FlexmasterPartNumber
Termination MTO4 (3" Length)
MTO4F (3" Length)
MTO4FSS
46DVA-HC
46DVA-VCH
Frame Kits MSR (Stucco Frame)
MOSR (Stucco Frame)
BSR-4 (4" Brick Frame)
BSR-6 (6" Brick Frame)
Flex Sections MFL - 1 (12" f/f Connectors)
MFL - 18 (18" f/f Section)
MFL - 2 (24" f/f Section)
MFL - 3 (36" f/f Section)
MFL - 4 (48" f/f Section)
MFL - 6 (72" f/f Section)
46DVA-48FF (48" F/F Section)
46DVA-120FF (120"f/f Section)
4DVKIT4701
4DVKIT4701.5
4DVKIT4702
4DVKIT4703
4DVKIT4704
4DVKIT4706
Rigid Pipe
MEXT - 1 (12" f/m Section)
MEXT - 2 (24" f/m Section)
MEXT - 3 (36" f/m Section)
MEXT - 4 (48" f/m Section)
MEXT - 6 (72" f/m Section)
46DVA-06 (6" Section)
46DVA-09 (9" Section)
46DVA-12 (12" Section)
46DVA-18 (18" Section)
46DVA-24 (24" Section)
46DVA-36 (36" Section)
46DVA-48 (48" Section)
46DVA-60 (60" Section)
Rigid Pipe Extension EXT18 (18" f/f Section) 46DVA-08A (8½" Length)
46DVA-16A (16" Length)
Elbows MEL-90MM (m/m 90º Elbow)
MEL-90FF ( f/f 90º Elbow)
MEL-90FM ( f/m 90º Elbow)
MEL-45FM ( f/m 45º Elbow)
46DVA-E30 (30° Elbow)
46DVA-E45 (45° Elbow)
46DVA-E60 (60° Elbow)
46DVA-E90 (90° Elbow)
Wall Penetration Kit MFVK01F
SupportRing&Plate MSPXT7 46DVA-ES (Elbow strap)
46DVA-RS (Roof support)
Firestop FS7 46DVA-WFS
46DVA-WFS2
Roof Flashing MRF7 (1/12 - 7/12 pt.)
MRF12 (7/12 - 12/12 pt.)
46DVA-F6(DS) (0/12-6/12 pt.)
46DVA-F12(DS) (6/12-12/12 pt.)
46DVA-FF (Flat Roof Flashing)
Heat Shield RHS100 46DVA-WT
46DVA-WTS
2DVWTE47
Heat Guard MTKOG
Adaptors PVA5487 (5/8 to 4/7 reducer) 46DVA-AD-M1 Mounting Adapter
46DVA-AD-M2 Termination Adapter
(Montigo 4/7 to Duravent 4” x 6⅝”)
18
Installation
XG0230 - 052020
Section 3-3-3: Heat Shields
Installing a Wall Mounted Heat shield
The RHS10* Heat shield must be used if vent pipe passes through a
wall or ceiling within 6' of the unit.
To install the Heat shield, Slide the Inner Section over the vent pipe that
will connect to the replace. Then fasten the vent pipe to the back of
the replace with a minimum of three sheet metal screws. From the
outside slide the outer section on. To complete the installation fasten
the Heat Shield Outer Section & inner section to the structure.
Figure 11. RHS10* Installation. (Install by sliding over vent pipe where it passes through the
combustible construction).
Figure 11.b RHS10* Installation. (Install by sliding Outer Section over vent pipe where it passes
through the combustible construction.
Figure 11.c Heat Shield. After sliding the outer section in place.
Drywall / sheetrock
Drywall / sheetrock
RHS10* Heat Shield, inner Section
RHS10* Heat Shield, inner Section
Vent pipe, from replace
Vent pipe, from replace
Combustible framing
Combustible framingCombustible framing
RHS10* Heat Shield Outer Section
RHS10* Heat Shield Outer Section
Termination
Termination
3/8'' min.
Inner
shield
Outer
shield
A A
B
Installing the included heat shield
The included Heat shield CANNOT be used WITHIN 36" horizontal or
60" vertically of the replace. For applications within these dimensions
the RHS10* Heat Shield MUST be used.
To install the heat sheild frame an opening in combustible construction.
Slide the Heat shield in place over the vent pipe which attaches to the
replace. After the replace and vent pipe has been installed, clearances
should match the dimensions shown.
Figure 15.a Heat Shield Installation. (Install by sliding over vent pipe where it passes through the
combustible construction).
Wall Mounted RHS* heat shield
Vent Size A B
4/7 Shield 4/7 11" 1"min.
5/8 Shield 5/8 12" 1"min.
RHS100 5/8 11" 3/8''min.
RHS101 5/8 11" 3/8''min.
RHS102 5/8 12" 3/8''min.
RHS104 5/10 14" 3/8''min.
19
Installation
XG0230 - 052020
Installation of the wall switch
Montigo supplies 15' of low voltage wire to be plugged into the control
board. Connect to a standard single pole ON/OFF switch to the location
of your choice. You may extend these wires up to 30' in length with a
wire of equal quality.
Installations in Canada must be electrically grounded in accordance
with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70.
Optional remote control available through your Montigo Dealer.
DRSQ (N/L) I Wiring Diagram
BLACK
WHITE
GREEN
To PPO
SPARK
SENSOR
TO ON/OFF
WALL SWITCH
YELLOW/GREEN
ORANGE
GREEN
6
10
OPTIONAL CPI/IPI SWITCH
BLUE
WHITE
X1
X5
X4
X3
X2
3.15A FUSE
BLUE
RE

 

Figure 15. Wiring diagram for DRSQ38*I with SIT Proame Electronic Ignition
Section 4: Wiring
MODEL
DRSQ38NI DRSQC38NI
DRSQ38LI DRSQC38LI
1.5V AA type
1.5V AA type
1.5V AA type
1.5V AA type
BLACK
WHITE
GREEN
To PPO
SPARK
SENSOR
RED
BLACK
BATTERY
PACK
TO ON/OFF
WALL SWITCH
YELLOW/GREEN
ORANGE
GREEN
6
10
4
6
3
4
OPTIONAL CPI/IPI SWITCH
BLUE
WHITE
X1
X5
X4
X3
X2
LED Lights
LED1 - Red LED
LED2 Amber LED
3.15A FUSE
SW1
BLUE
RED
OPTIONAL
X10
X11
X12
X13
Main Power
120VAC 60Hz
6 amps
20
Installation
XG0230 - 052020
1.5V AA type
1.5V AA type
1.5V AA type
1.5V AA type
Installation of Electrical Supply
Installations in Canada must be electrically grounded in accordance
with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA must be grounded in accordance with local
codes or, in the absence of local codes, with the National Electrical
Code, ANSI/NFPA 70.
NOTE: If any of the original wire supplied with the appliance is replaced,
it must be replaced with the same type, or its equivalent.
Figure 15b. Wiring diagram for DRSQ38*I-2 with SIT Proame Electronic Ignition
DRSQ (N/L) I-2 Wiring Diagram
1.5V AA type
1.5V AA type
1.5V AA type
1.5V AA type
WHITE
BLACK
BLACK
WHITE
GREEN
Lights
ON/OFF
CONTROL
MAIN
Power
120VAC 60 Hz
6 Amps
SPARK
SENSOR
RED
BLACK
BATTERY
PACK
MAIN ON/OFF
SWITCH
YELLOW/GREEN
PILOT
R
ORANGE
GREEN
BLACK
BROWN
YELLOW
ORANGE
6
10
6
OPTIONAL CPI/IPI SWITCH
WHITE
LED Lights
LED1 - Red LED
LED2 Amber LED
SW1
LED
otroer
LED power
spp y
white
white
white



BLACK
WHITE
VARIABLE SPEED
COMFORT FANS
MODEL
DRSQ38NI-2 DRSQC38NI-2
DRSQ38LI-2 DRSQC38LI-2
VARIABLE SPEED
COMFORT FANS
HALOGEN LIGHTS
BLACK
RED
110V BV
TRANSFORMER
LED LIGHTS
LED1 - RED LED
LED2 AMBER LED
MAIN Power
120vac 60 hz
6 amps
3.15A FUSE
WHITE
RED
SPARK
SENSOR
X2
X3
X1
X10
X11
X4
X5
MAIN ON/OFF
SWITCH
BLACK
RED
1.5V AA TYPE
1.5V AA TYPE
1.5V AA TYPE
1.5V AA TYPE
BATTERY PACK
BLACK
WHITE
GREEN
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42

Montigo DelRay Square Series Operating instructions

Category
Fireplaces
Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI