Eurotherm X26 Temperature & Humidity Environmental Chamber Controller Owner's manual

Type
Owner's manual
Accurate programming of temperature and humidity is provided by
the advanced X26 controller. 50 customer named programs can be
stored with up to 100 steps per program and 500 steps in total.
Boost heat, boost cool and compressor On/Off outputs are included
as standard.
Two user programmable event outputs are available to activate
external devices - such as vibration test equipment.
A real time clock can be set to start a program at defined times of
the day and week.
Program profiles can be set up either through the controller front
panel from iTools or via a Windows setpoint program editor. This
allows the storage of an unlimited number of programs and easy
editing and transfer of programs between controllers. iTools
software will save and reproduce, the complete configuration of the
controller. iTools also provides trend plotting facilities for
monitoring the process.
The advance features include program holdback, to guarantee soak
time at temperature and humidity and six sets of PID parameters to
give accurate control under varying combinations of temperature
and humidity.
The humidity can be derived from wet and dry bulb inputs or taken
directly from a humidity probe.
Modbus digital communications is available for connection to
supervisory computers or Programmable Logic Controllers.
X26
MODEL
Temperature & Humidity
Environmental Chamber Controller
Designed for:
Climate simulation
Component testing
Ceramic drying rooms
Plant growth chambers
Features:
CONTROLS
DATA MANAGEMENT
PROCESS AUTOMATION
abc
Heating
Humidify
Spray
Heaters
Temperature probe
Humidity probe
By-pass
Compressor
on/off
Cooling/dehumidify
50 stored programs
500 program steps
0.1% accuracy
Real time clock
iTool program editor
software
OPC link to Labview
Modbus digital
communications
Rear Terminal Connections
1A
1B
1C
1D
HA
HB
HC
HD
HE
HF
L
N
D8
E1
E2
DC
D1
D2
D3
D4
D5
3A
3B
3C
3D
AA
AB
AC
BA
BB
BC
D6
D7
VH
VI
V+
V-
Line
Neutral
Earth
100 to 240Vac -15%, +10%
C
O
M
M
S
M
O
D
U
L
E
4A
4B
4C
4D
5A
5B
5C
5D
6A
6B
6C
6D
Common
Program Run Input
Program Hold Input
Boost Cool Output
Water Drain Valve
Program Event Output 1
High
Temperature
Alarm
Humidity
Probe
Input
Boost Heat Output
Program Event Output 2
Temperature Input
(Dry bulb)
Dual triac/relay
outputs for
compressor &
by-pass control
OR 2nd retrans
Output
Heating
Output
Cooling
Output
Wet bulb
Input
OR
Humidity
Probe
Supply
M
O
D
U
L
E
4
M
O
D
U
L
E
5
M
O
D
U
L
E
6
M
O
D
U
L
E
3
Humidfy
Output
Dehumidfy
Output
M
O
D
U
L
E
1
Temp or
Humidity
Retrans
+
-
Program Reset
Control Block Diagram
D1
3A
D1
3C
Cooling by-pass
Wait
Alarms
run
hold
reset
D1
D1
D1
D2
D1
D8
D1
V+
D1
V-
D1
6C
D1
6D
Wet
bulb
input
Humidity
Function
Block
D1
BA
D1
BB
Temp
PID
Hum
PID
Humidity
probe input
Temp PV (Dry bulb)
OR
Setpoint
Program
Real
Time
Clock
a
b
a>b
a
b
a>b
0
0
OP
OP
a
b
AND
a
b
A>b
1°C/33°F
Humidity/Temp retrans
Humidity/Temp retrans
D1
D5
D1
4A
Drain valve
D1
1A
D1
4A
D1
4B
Min-On
Timer
Compressor
On/Off
Dehum OP
Humidify OP
D1
5A
D1
5C
Heating OP
Cooling OP
Humidity
SP
Temp. setpoint
Event outputs
Lo Event
10S delay
Hi Event
10S delay
Boost
Heat SP
Boost
Cool SP
D1
D4
D1
D3
Boost heat OP
Boost cool OP
D1
D6
D1
D7
Event 1
Event 2
%RH
iTools is an advanced sofware tool for configuring the X26 and setting up the setpoint programs. The iTools configurator will edit,
store and ‘clone’ complete controller configurations. iTools employs an OPC to Modbus server to communicate with the X26. The
OPC server can be used as a link to other client software packages such as Labview and Wonderware.
iTools Software
The setpoint program editor is a simple
way of setting up the humidity and
temperature profiles and the
programmable event outputs. The
editor will store, retrieve and download
program profiles. It will work ‘on-line’,
when program values are edited ‘live’ in
a connected controller, or ‘off-line,
when programs are edited before being
downloaded to a selected controller.
The number of stored programs is
limited only by the capacity of the PC
hard disk.
OPC scope is an iTools utility providing
trend plots of the process variables.
The time axis can be adjusted between
1 minute and 1 month. Data can also
be logged to hard disk in CSV format.
This can then be recalled and analysed
in an Excel spreadsheet.
Setpoint Program Editor
Technical Specification
Temperature inputs (Wet and Dry bulbs)
Input types J, K, T, L, N thermocouples. 3-wire Pt100
Accuracy ±0.1%
Sample rate 9Hz
Cold Junction >30 to 1 rejection of ambient temp. change
Compensation
3-wire Pt100 input Bulb current: 0.3mA. Up to 22ohm in each
lead without error
Humidity probe input
Probe trans supply 24Vdc, 20mA max
Input signal range 0-1Vdc or 0-10Vdc (equivalent to 0-100%Rh)
Accuracy ±0.1%
Run, hold and reset digital inputs
Open circuit voltage 4Vdc nominal
Closed circuit current 0.8mA nominal
Heating, cooling, humidifying and dehumidifying outputs
Relay rating 2A, 264Vac resistive
Logic output 8Vdc, 12mA
Triac outputs 1A, 264Vac max
DC outputs 0-20mA or 0-10Vdc
Temperature and humidity retransmission outputs
Range 0-20mA or 0-10VDC (isolated)
Resolution 12 bits
Control Functions
Control mode PID
Tuning Automatic one-shot tuning
Auto manual control Bumpless transfer between auto and
manual
Alarms
Number of alarms One high temperature alarm
Setpoint programming
Number of programs 50
Number of setpoints 500
Event outputs 2
Program holdbacks High and low holdback settable per
segment
Communications
Modbus RS232, RS422 or RS485 (2 or 4-wire)
General
Display range Five digits with one decimal place
Supply 100 to 240Vac -15%. +10%
Operating ambient 0 to 55°C and 5 to 95% RH non-
condensing
Storage temperature -10 to +70°C
Panel sealing IP65
Dimensions (mm) 96W x 96H x 150D
EMC standards Meets generic emissions standard
EN50081-1 and immunity standard
EN50082-2 for Heavy Industrial,
Light Industrial, Residential and
Commercial Environments
Safety standards Meets EN61010, installation category II,
pollution degree 2
Part No. HA027707 Issue 2 Printed in England 04.02
Ordering codes
Supply Voltage
VH 85 to 264Vac
X26
Controller
Type
VH
Supply
Voltage
Module 1
Retrans
Module 3
Hum + Dehum
Module 4
Module 5
Heat + cool
Module 6 Comms
Manual
Module 1
96
96
Dimensional details
150
Panel cut-out
-0.0
+0.8
92 x 92
All dimensions in mm
EUROTHERM LIMITED http://www.eurotherm.co.uk email: [email protected]
© Copyright Eurotherm Limited 2001
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm
Limited. Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our
products which could, without notice, result in amendments or omissions to this specification. We cannot accept responsibility for damage, injury loss or expenses resulting
therefrom.
UK SALES OFFICE
Eurotherm Ltd
Faraday Close Durrington Worthing BN13 3PL United Kingdom
Sales and support: Tel. +44 (0)1903 695888 Fax +44 (0)1903 695666
Sales and support in over 30 countries worldwide
Enquiries/orders to:
Tel. +44 (0)1903 268500 Fax +44 (0)1903 265982
U.S. OFFICE
Eurotherm Inc.
741 Miller Drive SE,
Suite F, Leesburg.
VA 20175-8993
Telephone Leesburg (+1 703) 443 0000
Fax (+1 703) 669 1300
http://www.eurotherm.com
Retransmission output
XX Not fitted
First character
T- Temp. retrans.
H- Humidity retrans.
Second character
-Y 0-20mA
-A 4-20mA
-W 0-5Vdc
-G 1-5Vdc
-V 0-10Vdc
Module 3
Humidity + dehumidify
outputs
XX Not fitted
TP Dual logic outputs
RR Dual relay outputs
TT Dual triac outputs
DO Dual 4-20mA OP’s
Module 4
XX Not fitted
Compressor on/off &
by-pass outputs
TT Dual triac
RR Dual relay output
2nd retransmission OP
First character
T- Temp. retrans.
H- Humidity retrans.
Second character
-Y 0-20mA
-A 4-20mA
-W 0-5Vdc
-G 1-5Vdc
-V 0-10Vdc
Module 5
Heating + cooling
outputs
XX Not fitted
TP Dual logic outputs
RR Dual relay outputs
TT Dual triac outputs
DO Dual 4-20mA OP’s
Module 6
Wet bulb or Trans
supply
XX Not fitted
PV Wet bulb input
MS 24Vdc Humidity
transmitter supply
Comms
XX Not fitted
Modbus
A2 RS232
F2 4-wire,
RS485/RS422
Y2 2-wire RS485
Manual
XXX Not fitted
ENG English
FRA French
GER German
SPA Spanish
Temp (dry
bulb) Input
Wet bulb
Input
Units
Humidity
Input
Dry and Wet Bulb Inputs
Units
C
F °F
Humidity Input
X Not used
N 0-1Vdc
V 0-10Vdc
Y 0-20mA
A 4-20mA
W 0-5Vdc
XX Not used
°C Range °F
Resistance thermometer
Z Pt100(RTD) -200 to 850 -325 to 1562
Thermocouples
J Type J -210 to 1200 -340 to 2192
K Type K -200 to 1372 -325 to 2500
T Type T -200 to 400 -325 to 750
L Type L -200 to 900 -325 to 1650
N Type N -200 to 1300 -325 to 2370
Process inputs (linear)
M -100 to +100mV Scaleable -1999 to 9999
Y 0 to 20mA Scaleable -1999 to 9999
A 4 to 20mA Scaleable -1999 to 9999
W 0 to 5Vdc Scaleable -1999 to 9999
G 1 to 5Vdc Scaleable -1999 to 9999
V 0 to 10Vdc Scaleable -1999 to 9999
Hardware coding Configuration coding
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4