Danfoss ECL Comfort 210/310, A237/A337 Operating instructions

Type
Operating instructions
OperatingGuide
ECLComfort210/296/310,applicationA237/A337
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................13
2.3Mounting...........................................................16
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................30
2.7Checklist............................................................36
2.8Navigation,ECLApplicationKeyA237/A337................37
3.0Dailyuse.........................................................43
3.1Howtonavigate...................................................43
3.2Understandingthecontrollerdisplay..........................44
3.3Ageneraloverview:Whatdothesymbolsmean?...........47
3.4Monitoringtemperaturesandsystem
components........................................................48
3.5Influenceoverview................................................49
3.6Manualcontrol.....................................................50
3.7Schedule............................................................51
4.0Settingsoverview............................................52
5.0Settings...........................................................55
5.1IntroductiontoSettings..........................................55
5.2Flowtemperature/Inlettemperature.........................56
5.3Roomlimit..........................................................60
5.4Returnlimit.........................................................62
5.5Flow/powerlimit.................................................68
5.6Optimization........................................................73
5.7Controlparameters................................................79
5.8Application.........................................................83
5.9Heatcut-out........................................................94
5.10Tanktemperature..................................................97
5.11Alarm..............................................................102
5.12Alarmoverview..................................................105
5.13Anti-bacteria......................................................106
6.0Commoncontrollersettings............................108
6.1Introductionto‘Commoncontrollersettings..............108
6.2Time&Date.......................................................109
6.3Holiday............................................................110
6.4Inputoverview...................................................112
6.5Log.................................................................113
6.6Outputoverride..................................................114
6.7Keyfunctions.....................................................115
6.8System.............................................................117
7.0Miscellaneous................................................124
7.1ECA30/31setupprocedures.................................124
7.2Overridefunction................................................132
7.3Severalcontrollersinthesamesystem......................135
7.4Frequentlyaskedquestions....................................138
7.5Definitions........................................................141
7.6Type(ID6001),overview.......................................144
7.7ParameterIDoverview..........................................145
©Danfoss|2017.06VI.LG.R3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA237
(ordercodeno.087H3806).
TheECLApplicationKeyA237contains4subtypes:
A237.1andA237.2(applicableinECLComfort210,296and310)
A337.1andA337.2(applicableinECLComfort310)
A237.1:HeatingandDHWheating
A237.2:HeatingandDHWcharging
A337.1:HeatingandDHWheating.Externalsetpointoptional
(0-10V)
A337.2:HeatingandDHWcharging.Externalsetpointoptional
(0-10V)
TheA237applicationkeyalsocontainsaFloor(Screed)Drying
Program.Seeseparatedocumentation.(InEnglishandGerman
languageonly).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,M-busandEthernet
(Internet)communication
ECLComfort310foradvancedsolutions,M-bus,Modbusand
Ethernet(Internet)communication.
TheApplicationKeyA237complieswithECLComfort210/310
controllersasoffirmwareversion1.11.
TheApplicationKeyA237compliesalsowithECLComfort296
controllersasoffirmwareversion1.58.
Thefirmware(controllersoftware)versionisvisibleatstart-upof
thecontrollerandinCommoncontrollersettings’in‘System .
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedforremotemonitoringandsetting.Thebuilt-inroom
temperaturesensorcanbeutilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
2|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
VI.LG.R3.02
©Danfoss|2017.06|3
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
4|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.LG.R3.02
©Danfoss|2017.06|5
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.0Installation
2.1Beforeyoustart
Thetwoapplications,A237.1/A337.1arealmostidentical.
However,A337.1hassomeextrafunctionswhicharedescribed
additionally.
TheapplicationsA237.1/A337.1areveryflexible.Thesearethe
basicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3
‘Comfort’periods/day.Avalueforthedesiredroomtemperature
canbesetineachofthemodes.
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.Inboiler-basedheatingsupplythe
returntemperatureshouldnotbetoolow(sameadjustment
procedureasabove).
Ifthemeasuredroomtemperature(directlyconnectedtemperature
sensorESM-10(S2)orRemotecontrolunitECA30/31)doesnot
equalthedesiredroomtemperature,thedesiredflowtemperature
canbeadjusted.
ThecirculationpumpP1isONatheatdemandoratfrost
protection.ThecirculationpumpP1canbeswitchedOFFwhen
heatingtheDHW.Ifthesystemhasachangeovervalve(P2/M2)
betweentheheatingandDHWcircuit,thecirculationpumpP1
isONwhenheatingtheDHW.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
Thefrostprotectionmodemaintainsaselectableflowtemperature
value,forexample10°C.
Analarmcanbeactivatediftheactualflowtemperaturediffers
fromthedesiredflowtemperature.
TypicalA237.1/A337.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7
Flow/energymeter(pulsesignal)
S8
DHWtanktemperaturesensor,lower
P1
Circulationpump,heating,circuit1
P2DHWpump,circuit2
P3
DHWcirculationpump,circuit2
M1
Motorizedcontrolvalve(3-pointcontrolled).
Alternative:Thermoactuator(DanfosstypeABV)
A1
Alarm
6|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
A237.1,ex.a,A337.1,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit
can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot
differmorethanasetvaluefromthedesiredtemperature
(dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe
heatingcircuitastheDHWheatingtemperature(parallel
mode).
A237.1usedinECL296/310
Theflow/powersignalcancomeasapulsesignaloranM-bus
signal.
A337.1
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan
limitthefloworpowertoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
M-busdatacanbetransferredtotheModbuscommunication.
Heatingingeneral
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
VI.LG.R3.02
©Danfoss|2017.06|7
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode.Theweekschedulecanhaveupto3‘Comfort’
periods/day.AvalueforthedesiredDHWtemperaturecanbe
setineachofthemodes.
DHWheatingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthestart
temperature,theheatingcirculationpumpP1isswitchedOFFand
theDHWheatingpumpP2isswitchedON.
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain
theheatingtemperatureatS3.
AdelayedstartoftheDHWheatingpumpcanbearranged.Inthis
case,S3mustbeplacedintheheat-exchanger.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5-10degreeshigherthanthedesired
DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis
active,canbelimitedtoasetvalue.
Chargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthanthe
charging-stoptemperature,theDHWheatingpumpP2isswitched
OFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
WhenthemeasuredDHWtemperatureS6gets2Khigherthanthe
heating-starttemperatureANDthelowertanktemperatureS8gets
higherthantheheating-stoptemperature,theDHWheatingpump
P2isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled
priority-valve,betweentheheatingandtheDHWcircuits,the
changeovervalveisactivatedatDHWheatingdemand.The
circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications:
Ifthechargingtemperaturehasavalueclosetothedesiredflow
temperatureintheheatingcircuit,thecirculationpump(P1)inthe
heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcircuitcanbeconnectedprimarilyandthevalve‘P2/
M2’operatesasON/OFFvalve.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periods/day.
TheDHWcirculationpumpP3canbeswitchedOFFduringDHW
heating/charging.
A237.1/A337.1examplea:
A237.1/A337.1exampleb:
A237.1/A337.1examplec:
A237.1/A337.1exampled:
8|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.1andA337.1,ingeneral
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
InECLComfort296/310theM-busdatacanfurthermorebe
transferredtotheModbuscommunication.
Thetwoapplications,A237.2/A337.2arealmostidentical.
However,A337.2hassomeextrafunctionswhicharedescribed
additionally.
TheapplicationsA237.2/A337.2areveryflexible.Thesearethe
basicprinciples:
Heating(circuit1):
Theheatingcircuitworksasdescribedpreviously.
A237.2,ex.a,A337.2,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit
can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot
differmorethanasetvaluefromthedesiredtemperature
(dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe
heatingcircuitastheDHWheatingtemperature(parallel
mode).
A237.2usedinECL296
Theflow/powersignalcancomeasapulsesignaloranM-bus
signal.
A337.2
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be
controlledbymeansofanexternalvoltageintherange0-10volt.
TypicalA237.2/A337.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7
Flow/energymeter(pulsesignal)
S8
DHWtanktemperaturesensor,lower
P1
Circulationpump,heating,circuit1
P2DHWpump,circuit2
P3
DHWcirculationpump,circuit2
P4
DHWchargingpump,circuit2
M1
Motorizedcontrolvalve(3-pointcontrolled).
Alternative:Thermoactuator(DanfosstypeABV).
A1
Alarm(A337.2only)
VI.LG.R3.02
©Danfoss|2017.06|9
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode.Theweekschedulecanhaveupto3‘Comfort’
periods/day.AvalueforthedesiredDHWtemperature
canbesetineachofthemodes.
DHWchargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe
charging-starttemperature,theheatingcirculationpumpP1is
switchedOFFandtheDHWheatingpumpP2isswitchedON.
AdelayedstartoftheDHWchargingpumpP4canbearranged.
Also,itcanbearrangedthatthestartofthechargingpump
dependsontheDHWheatingtemperature.Inthiscase,S4mustbe
placedintheheat-exchanger.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5-10degreeshigherthanthedesired
DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis
active,canbelimitedtoasetvalue.
TheDHWheatingtemperatureatS3isadaptedtothedesiredDHW
chargingtemperatureatS4.IftheDHWchargingtemperatureat
S4cannotbereached,theECLcontrollergraduallyincreasesthe
desiredDHWheatingtemperatureatS3inordertoobtaintheDHW
chargingtemperature.TheECLcontrollerrememberstheadapted
S3temperature.Amaximumtemperaturevaluecanbeset.
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain
thechargingtemperatureatS4.
DHWchargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthan
thecharging-stoptemperature,theDHWchargingpumpP4is
switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
WhenthemeasuredDHWtemperatureS6gets2Khigherthan
thecharging-starttemperatureANDthelowertanktemperature
S8getshigherthanthecharging-stoptemperature,theDHW
chargingpumpP4isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled
priority-valve,betweentheheatingandtheDHWcircuits,the
changeovervalveisactivatedatDHWheatingdemand.The
circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications:
Ifthechargingtemperaturehasavalueclosetothedesiredflow
temperatureintheheatingcircuit,thecirculationpump(P1)inthe
heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
A237.2/A337.2examplea:
A237.2/A337.2exampleb:
10|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.2andA337.2,ingeneral:
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
A237,ingeneral
Flow/energylimitation.
ECLComfort210:
ThesubtypesA237.1andA237.2canutilizetheflow/powersignal
comingasapulsesignal.
ECLComfort296:
ThesubtypesA237.1andA237.2canutilizetheflow/powersignal
comingasapulsesignaloranM-bussignal.
ECLComfort310:
ThesubtypesA337.1andA337.2canutilizetheflow/powersignal
comingasanM-bussignal.
Alarm
A237.1:
AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
A237.2:
Noalarmfunctionpresent
A337.1,A337.2:
AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
Inputconfiguration
Inputs(asfromS7andup)whicharenotpartoftheapplication
canbeconfiguredtobePt1000,0-10VoltorDigitalinput.This
featuremakesitpossibletocommunicateextrasignals,suchas
temperatures,pressures,ON/OFFconditions,viaModbusand
ECLPortal.
TheconfigurationisdonebymeansoftheECLTool(freesoftware
fordownload)ordirectlyinadedicatedmenuintheECLPortal.
Dependingonsystemtype,itisrecommendedtochangesome
factorysettingsindividuallyinordertooptimizethefunctionality.
Thesesettingchanges,ifrequired,arelistedbelowthesystem
typesinthesection'Identifyingthesystemtype'.
WhentheA237hasbeenuploadedtheECLComfortcontroller
startsinManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
VI.LG.R3.02
©Danfoss|2017.06|11
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
12|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.LG.R3.02
©Danfoss|2017.06|13
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication
examples.Someoftheapplicationexamplesneedchangeof
dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered
withtheapplicationkey.
A237.1,ex.a
A337.1,ex.a
Twopumpsystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
ON
A237.1,ex.b
A337.1,ex.b
OnepumpandChange-overvalvesystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Change-overvalve
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
A237.1,ex.c
A237.1,ex.d
A337.1,ex.c
A337.1,ex.d
DHWheatingconnectedprimarily:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Change-overvalve
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
DHWcircuit(2):
Tankprimarily
MENU\Settings\Application:
'Tank,sec./prim'
12053
ON
14|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
A237.2,ex.a
A337.2,ex.a
Twopumpsystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
ON
A237.2,ex.b
A337.2,ex.b
OnepumpandChange-overvalvesystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
VI.LG.R3.02
©Danfoss|2017.06|15
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
16|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.LG.R3.02
©Danfoss|2017.06|17
OperatingGuideECLComfort210/296/310,applicationA237/A337
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
18|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.LG.R3.02
©Danfoss|2017.06|19
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150

Danfoss ECL Comfort 210/310, A237/A337 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI