  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210/310, A237/A337 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA237/A337
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................13
2.3Mounting...........................................................16
2.4Placingthetemperaturesensors................................20
2.5Electricalconnections.............................................22
2.6InsertingtheECLApplicationKey..............................30
2.7Checklist............................................................36
2.8Navigation,ECLApplicationKeyA237/A337................37
3.0Dailyuse.........................................................43
3.1Howtonavigate...................................................43
3.2Understandingthecontrollerdisplay..........................44
3.3Ageneraloverview:Whatdothesymbolsmean?...........47
3.4Monitoringtemperaturesandsystem
components........................................................48
3.5Influenceoverview................................................49
3.6Manualcontrol.....................................................50
3.7Schedule............................................................51
4.0Settingsoverview............................................52
5.0Settings...........................................................55
5.1IntroductiontoSettings..........................................55
5.2Flowtemperature/Inlettemperature.........................56
5.3Roomlimit..........................................................60
5.4Returnlimit.........................................................62
5.5Flow/powerlimit.................................................68
5.6Optimization........................................................73
5.7Controlparameters................................................79
5.8Application.........................................................83
5.9Heatcut-out........................................................94
5.10Tanktemperature..................................................97
5.11Alarm..............................................................102
5.12Alarmoverview..................................................105
5.13Anti-bacteria......................................................106
6.0Commoncontrollersettings............................108
6.1Introductionto‘Commoncontrollersettings..............108
6.2Time&Date.......................................................109
6.3Holiday............................................................110
6.4Inputoverview...................................................112
6.5Log.................................................................113
6.6Outputoverride..................................................114
6.7Keyfunctions.....................................................115
6.8System.............................................................117
7.0Miscellaneous................................................124
7.1ECA30/31setupprocedures.................................124
7.2Overridefunction................................................132
7.3Severalcontrollersinthesamesystem......................135
7.4Frequentlyaskedquestions....................................138
7.5Definitions........................................................141
7.6Type(ID6001),overview.......................................144
7.7ParameterIDoverview..........................................145
©Danfoss|2017.06VI.LG.R3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA237
(ordercodeno.087H3806).
TheECLApplicationKeyA237contains4subtypes:
A237.1andA237.2(applicableinECLComfort210,296and310)
A337.1andA337.2(applicableinECLComfort310)
A237.1:HeatingandDHWheating
A237.2:HeatingandDHWcharging
A337.1:HeatingandDHWheating.Externalsetpointoptional
(0-10V)
A337.2:HeatingandDHWcharging.Externalsetpointoptional
(0-10V)
TheA237applicationkeyalsocontainsaFloor(Screed)Drying
Program.Seeseparatedocumentation.(InEnglishandGerman
languageonly).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,M-busandEthernet
(Internet)communication
ECLComfort310foradvancedsolutions,M-bus,Modbusand
Ethernet(Internet)communication.
TheApplicationKeyA237complieswithECLComfort210/310
controllersasoffirmwareversion1.11.
TheApplicationKeyA237compliesalsowithECLComfort296
controllersasoffirmwareversion1.58.
Thefirmware(controllersoftware)versionisvisibleatstart-upof
thecontrollerandinCommoncontrollersettings’in‘System .
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedforremotemonitoringandsetting.Thebuilt-inroom
temperaturesensorcanbeutilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
2|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
VI.LG.R3.02
©Danfoss|2017.06|3
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
4|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.LG.R3.02
©Danfoss|2017.06|5
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.0Installation
2.1Beforeyoustart
Thetwoapplications,A237.1/A337.1arealmostidentical.
However,A337.1hassomeextrafunctionswhicharedescribed
additionally.
TheapplicationsA237.1/A337.1areveryflexible.Thesearethe
basicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Saving’mode.Theweekschedulecanhaveupto3
‘Comfort’periods/day.Avalueforthedesiredroomtemperature
canbesetineachofthemodes.
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.Inboiler-basedheatingsupplythe
returntemperatureshouldnotbetoolow(sameadjustment
procedureasabove).
Ifthemeasuredroomtemperature(directlyconnectedtemperature
sensorESM-10(S2)orRemotecontrolunitECA30/31)doesnot
equalthedesiredroomtemperature,thedesiredflowtemperature
canbeadjusted.
ThecirculationpumpP1isONatheatdemandoratfrost
protection.ThecirculationpumpP1canbeswitchedOFFwhen
heatingtheDHW.Ifthesystemhasachangeovervalve(P2/M2)
betweentheheatingandDHWcircuit,thecirculationpumpP1
isONwhenheatingtheDHW.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
Thefrostprotectionmodemaintainsaselectableflowtemperature
value,forexample10°C.
Analarmcanbeactivatediftheactualflowtemperaturediffers
fromthedesiredflowtemperature.
TypicalA237.1/A337.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7
Flow/energymeter(pulsesignal)
S8
DHWtanktemperaturesensor,lower
P1
Circulationpump,heating,circuit1
P2DHWpump,circuit2
P3
DHWcirculationpump,circuit2
M1
Motorizedcontrolvalve(3-pointcontrolled).
Alternative:Thermoactuator(DanfosstypeABV)
A1
Alarm
6|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
A237.1,ex.a,A337.1,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit
can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot
differmorethanasetvaluefromthedesiredtemperature
(dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe
heatingcircuitastheDHWheatingtemperature(parallel
mode).
A237.1usedinECL296/310
Theflow/powersignalcancomeasapulsesignaloranM-bus
signal.
A337.1
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be
controlledbymeansofanexternalvoltageintherange0-10volt.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
AconnectedfloworenergymeterbasedonM-bussignalcan
limitthefloworpowertoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedflow/power.
M-busdatacanbetransferredtotheModbuscommunication.
Heatingingeneral
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
VI.LG.R3.02
©Danfoss|2017.06|7
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode.Theweekschedulecanhaveupto3‘Comfort’
periods/day.AvalueforthedesiredDHWtemperaturecanbe
setineachofthemodes.
DHWheatingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthestart
temperature,theheatingcirculationpumpP1isswitchedOFFand
theDHWheatingpumpP2isswitchedON.
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain
theheatingtemperatureatS3.
AdelayedstartoftheDHWheatingpumpcanbearranged.Inthis
case,S3mustbeplacedintheheat-exchanger.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5-10degreeshigherthanthedesired
DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis
active,canbelimitedtoasetvalue.
Chargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthanthe
charging-stoptemperature,theDHWheatingpumpP2isswitched
OFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
WhenthemeasuredDHWtemperatureS6gets2Khigherthanthe
heating-starttemperatureANDthelowertanktemperatureS8gets
higherthantheheating-stoptemperature,theDHWheatingpump
P2isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled
priority-valve,betweentheheatingandtheDHWcircuits,the
changeovervalveisactivatedatDHWheatingdemand.The
circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications:
Ifthechargingtemperaturehasavalueclosetothedesiredflow
temperatureintheheatingcircuit,thecirculationpump(P1)inthe
heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcircuitcanbeconnectedprimarilyandthevalve‘P2/
M2’operatesasON/OFFvalve.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periods/day.
TheDHWcirculationpumpP3canbeswitchedOFFduringDHW
heating/charging.
A237.1/A337.1examplea:
A237.1/A337.1exampleb:
A237.1/A337.1examplec:
A237.1/A337.1exampled:
8|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.1andA337.1,ingeneral
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
InECLComfort296/310theM-busdatacanfurthermorebe
transferredtotheModbuscommunication.
Thetwoapplications,A237.2/A337.2arealmostidentical.
However,A337.2hassomeextrafunctionswhicharedescribed
additionally.
TheapplicationsA237.2/A337.2areveryflexible.Thesearethe
basicprinciples:
Heating(circuit1):
Theheatingcircuitworksasdescribedpreviously.
A237.2,ex.a,A337.2,ex.a
DuringDHWheating,thecirculationpumpP1intheheatingcircuit
can:
beswitchedOFF(DHWprioritymode)
or
remainON,aslongastheheatingtemperatureatS3doesnot
differmorethanasetvaluefromthedesiredtemperature
(dependentparallelmode)
or
becontinuouslyON.Thismeanssametemperatureinthe
heatingcircuitastheDHWheatingtemperature(parallel
mode).
A237.2usedinECL296
Theflow/powersignalcancomeasapulsesignaloranM-bus
signal.
A337.2
Thedesiredflowtemperatureoftheheatingcircuitcan,viaS10,be
controlledbymeansofanexternalvoltageintherange0-10volt.
TypicalA237.2/A337.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
Roomtemperaturesensor
S3
Flowtemperaturesensor,circuit1
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7
Flow/energymeter(pulsesignal)
S8
DHWtanktemperaturesensor,lower
P1
Circulationpump,heating,circuit1
P2DHWpump,circuit2
P3
DHWcirculationpump,circuit2
P4
DHWchargingpump,circuit2
M1
Motorizedcontrolvalve(3-pointcontrolled).
Alternative:Thermoactuator(DanfosstypeABV).
A1
Alarm(A337.2only)
VI.LG.R3.02
©Danfoss|2017.06|9
OperatingGuideECLComfort210/296/310,applicationA237/A337
DHW(circuit2):
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode.Theweekschedulecanhaveupto3‘Comfort’
periods/day.AvalueforthedesiredDHWtemperature
canbesetineachofthemodes.
DHWchargingstart,DHWtankwith1or2temperaturesensors
WhenthemeasuredDHWtemperatureS6getslowerthanthe
charging-starttemperature,theheatingcirculationpumpP1is
switchedOFFandtheDHWheatingpumpP2isswitchedON.
AdelayedstartoftheDHWchargingpumpP4canbearranged.
Also,itcanbearrangedthatthestartofthechargingpump
dependsontheDHWheatingtemperature.Inthiscase,S4mustbe
placedintheheat-exchanger.
TheDHWheatingtemperatureisdeterminedbythedesiredDHW
temperatureatS6plusthesetchargingdifference.Thecharging
temperatureistypically5-10degreeshigherthanthedesired
DHWtemperature.
ThereturntemperatureS5,whentheDHWheating/chargingis
active,canbelimitedtoasetvalue.
TheDHWheatingtemperatureatS3isadaptedtothedesiredDHW
chargingtemperatureatS4.IftheDHWchargingtemperatureat
S4cannotbereached,theECLcontrollergraduallyincreasesthe
desiredDHWheatingtemperatureatS3inordertoobtaintheDHW
chargingtemperature.TheECLcontrollerrememberstheadapted
S3temperature.Amaximumtemperaturevaluecanbeset.
ThemotorizedcontrolvalveM1iscontrolledinordertomaintain
thechargingtemperatureatS4.
DHWchargingstop,DHWtankwith1temperaturesensor
WhenthemeasuredDHWtemperatureS6getshigherthan
thecharging-stoptemperature,theDHWchargingpumpP4is
switchedOFF.Apost-runtimecanbeset.
Chargingstop,DHWtankwith2temperaturesensors
WhenthemeasuredDHWtemperatureS6gets2Khigherthan
thecharging-starttemperatureANDthelowertanktemperature
S8getshigherthanthecharging-stoptemperature,theDHW
chargingpumpP4isswitchedOFF.Apost-runtimecanbeset.
Iftheinstallationhasachangeovervalve(P2/M2),alsocalled
priority-valve,betweentheheatingandtheDHWcircuits,the
changeovervalveisactivatedatDHWheatingdemand.The
circulationpump(P1)isONwhenheatingtheDHW.
Parallelmodeintwo-pumpapplications:
Ifthechargingtemperaturehasavalueclosetothedesiredflow
temperatureintheheatingcircuit,thecirculationpump(P1)inthe
heatingcircuitwillnotbeswitchedOFFduringDHWheating.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
TheDHWcirculationpump(P3)hasaweekscheduleforupto3
ON-periodsperday.
A237.2/A337.2examplea:
A237.2/A337.2exampleb:
10|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
ApplicationA237.2andA337.2,ingeneral:
Unusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.In
ECLComfort310theM-busdatacanfurthermorebetransferred
totheModbuscommunication.
A237,ingeneral
Flow/energylimitation.
ECLComfort210:
ThesubtypesA237.1andA237.2canutilizetheflow/powersignal
comingasapulsesignal.
ECLComfort296:
ThesubtypesA237.1andA237.2canutilizetheflow/powersignal
comingasapulsesignaloranM-bussignal.
ECLComfort310:
ThesubtypesA337.1andA337.2canutilizetheflow/powersignal
comingasanM-bussignal.
Alarm
A237.1:
AlarmA1(=relay4)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
A237.2:
Noalarmfunctionpresent
A337.1,A337.2:
AlarmA1(=relay6)canbeactivated:
iftheactualflowtemperaturediffersfromthedesiredflow
temperature
ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
Inputconfiguration
Inputs(asfromS7andup)whicharenotpartoftheapplication
canbeconfiguredtobePt1000,0-10VoltorDigitalinput.This
featuremakesitpossibletocommunicateextrasignals,suchas
temperatures,pressures,ON/OFFconditions,viaModbusand
ECLPortal.
TheconfigurationisdonebymeansoftheECLTool(freesoftware
fordownload)ordirectlyinadedicatedmenuintheECLPortal.
Dependingonsystemtype,itisrecommendedtochangesome
factorysettingsindividuallyinordertooptimizethefunctionality.
Thesesettingchanges,ifrequired,arelistedbelowthesystem
typesinthesection'Identifyingthesystemtype'.
WhentheA237hasbeenuploadedtheECLComfortcontroller
startsinManualmode.Thiscanbeusedforcheckingthecontrolled
componentsforcorrectfunctionality.
VI.LG.R3.02
©Danfoss|2017.06|11
OperatingGuideECLComfort210/296/310,applicationA237/A337
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
12|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.LG.R3.02
©Danfoss|2017.06|13
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
Factorysettingsinthesubtypeswillrunthemostapplication
examples.Someoftheapplicationexamplesneedchangeof
dedicatedsettings.
Seethedocumentationforapplicationsandsubtypes,delivered
withtheapplicationkey.
A237.1,ex.a
A337.1,ex.a
Twopumpsystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
ON
A237.1,ex.b
A337.1,ex.b
OnepumpandChange-overvalvesystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Change-overvalve
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
A237.1,ex.c
A237.1,ex.d
A337.1,ex.c
A337.1,ex.d
DHWheatingconnectedprimarily:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Change-overvalve
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
DHWcircuit(2):
Tankprimarily
MENU\Settings\Application:
'Tank,sec./prim'
12053
ON
14|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
Adviceforsettings:
A237.2,ex.a
A337.2,ex.a
Twopumpsystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
ON
A237.2,ex.b
A337.2,ex.b
OnepumpandChange-overvalvesystem:
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(2):
Pump
MENU\Settings\Application:
'Ch.-o.valve/P'
12051
OFF
VI.LG.R3.02
©Danfoss|2017.06|15
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
16|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.LG.R3.02
©Danfoss|2017.06|17
OperatingGuideECLComfort210/296/310,applicationA237/A337
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
18|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.LG.R3.02
©Danfoss|2017.06|19
OperatingGuideECLComfort210/296/310,applicationA237/A337
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
20|©Danfoss|2017.06
VI.LG.R3.02
OperatingGuideECLComfort210/296/310,applicationA237/A337
/