©Copyright 2018 Dwyer Instruments, Inc. FR# 443696-00 Rev. 1
Upon final installation of the Series SCS Current Switches, no routine maintenance is
required. A periodic check of system calibration is recommended. The Series SCS is
not field serviceable and should be returned if repair is needed (field repair should not
be attempted and may void warranty). Be sure to include a brief description of the
problem plus any relevant application notes. Contact customer service to receive a
return goods authorization number before shipping.
Series SCS solid state
output does not
function
Set point screw
keeps turning
Motor is turned on
and switch does not
close
Verify that the maximum amperage range has not been
exceeded. Voltages or currents above the rated levels
may damage the Series SCS.
The set point screw has a slip clutch to prevent damage
at either end. To return the LED to its original setting, turn
the set point screw 20 full turns counterclockwise and
start the calibration procedure again.
Insufficient current to the load leads (for example a motor
or heater) to reach the set point threshold. To turn switch
on, wrap the cable multiple times through the sensing
hole (see Figure 5).
2. Slowly turn the set point screw clockwise until the Status Closed LED turns off and
the Status Open LED turns on.
3. Turn the setpoint screw an additional 1/4 turn clockwise to create a deadband to
prevent hunting.
The Series SCS is now calibrated to signal current flows above normal full load
amperes.
Output status:
• Normal: Output Open
• Alarm: Output Closed
STATUS
S
TATUS
O
PEN SETPOINT CLOSED
STATUS
STATUS
OPEN SETPOINT CLOSED
S
TATUS
STATUS
O
PEN SETPOINT CLOSED
3. Turn the setpoint screw an additional 1/4 turn counterclockwise to create a
d
eadband to prevent hunting.
T
he Series SCS is now calibrated to signal current flows below normal full load
a
mperes.
Output Status:
• Normal: Output Closed
•
Alarm: Output Open
1. Turn the set point screw counterclockwise until the Status Open LED turns off and
the Status Closed LED turns on.
Note: This is the default factory setting.
2. Slowly turn the setpoint screw counterclockwise until the Status Closed
LED turns on and the Status Open LED turns off.
STATUS
STATUS
OPEN SETPOINT CLOSED
Position the Series SCS such that the status output panel faces you. Confirm the
monitored load (for example, a motor or heater) is running, and then use the following
methods to calibrate the Series SCS.
1.
Turn the setpoint screw clockwise until the Status Closed Light-Emitting Diode
(LED) turns off and the Status Open LED turns on.
Failure to derate the current capacity could result in damage to the Series SCS when
using multiple turns to increase the measured current. Use the following formula to
determine the new maximum current:
New maximum current = SCS current rating / number of turns
For example, Model SCS-211125 with 4 turns = 135 A / 4 = 33.8 A, new maximum
current.
Use a 5 A Current Transformer (CT) to reduce the current passing through the SCS
as shown in figure 6. Run the current transformer secondary wire through the sensing
hole. Terminate the 2 secondary wires of the 5 A current transformer to each other,
and then install the 5 A current transformer on the monitored conductor.
I
f the measured current is too low to be detected or is higher than the maximum
c
urrent rating of the SCS, use the following methods to increase or decrease current.
Wrap the conductor (wire) through the sensing hole and around the SCS body to
produce multiple turns to increase the measured current. Use the below equation to
d
etermine how many wraps are necessary:
M
easured current = actual current times the number of turns. (See figure 5).
CONTACTOR
D
O
D
I
24 V AC/DC
RELAY COIL
FAN OR PUMP
CONTROL
POWER
120 VAC