Biasi Riva Advance M110.24SM/C, M110.32SM/C User manual

Category
Water heaters & boilers
Type
User manual
Wall hung, fan flue, room sealed, high efficiency gas boiler
User manual and
Installation instructions
RIVA ADVANCE HE
Models
M110.24SM/C
M110.32SM/C
Congratulations on your choice.
RIVA ADVANCE HE are condensing high efficiency sealed chamber fan flue gas boilers.
They are fully elec tronically controlled and have electronic ignition.
Thematerialstheyaremadeofandthecontrolsystemstheyareequippedwithgiveyousafety,
a high level of comfort and energy savings to allow you to get the greatest benefit out of
independent heating.
RIVA ADVANCE HE allow a highe r efficiency by r educi ng the flue gas temperature such that
the water vapour formed during the combustion is condensed out.
This allows a gain of useful heat that otherwise would be lost.
Remember that...
n The manual
--- must be read thoroughly, so that you will
be able to use the boiler in a safe and sen-
sible way;
--- must be carefully kept. It may be necess-
ary for reference in the future.
n First lighting up must be carried out by
competent and responsible engineer.
n The manufacturer
--- disclaim all liability for any translations of
the present manual from which incorrect in-
terpretation may occ ur
--- cannot be held responsible for non---ob-
servance of instructio ns co ntained in this
manual or for the co nsequences of any pro-
cedure not specifically described.
Using the boiler...
n Before lighting the boiler you are ad-
vised to have a professionally qualified per-
son check that the installation of the gas
supply
--- is gas ---tight;
--- isofthecorrectgaugefortheflowtothe
boiler;
--- is fitted with all the safety and control de-
vices required by the current Regulations.
n Ensure that
--- the installer has connected the pressure
relief valve outlet to a drain pipe. The manu-
facturers are not responsi ble for damage
caused by opening of the pressure relief
valve and conseque nt escape of water, if not
connected correctl y to the drain.
--- the install er has connected the conden-
sate outlet to a suitable drain pipe.
n On detecting the smell of gas
--- don’t operate any electrical switches, the
telephone or any device that may produce
sparks;
--- open the windows and doors at once to
create a draught of air which will purge the
area;
--- shut off the gas cocks;
--- get the assistance of a qualified person.
n Do not touch the appliance with parts of
thebodythatarewetordampand/orbare
feet.
n Do not block or modify the condensate
outlet and pipework
n In case of structural work or mainten-
ance near the exhaust duct and/or fume ex-
haust devices or their attachments, turn off
the appliance. On completion of the work,
have a professio nall y qualified person check
their efficiency.
n Repairs (under guarantee) must be car-
ried out only by an approved engineer, using
genuine spare parts. Thus do no more t han
switching off the boiler yourself (see the in-
structions) .
n Your boiler allows heating up of water to
a temperature less than boiling point;
--- must be connec ted to a c entral heating
system and/or a hot water supply system,
compatible with its performance and output;
---canbeusedonlyforthosepurposesfor
which it has been specially designed;
--- must not be touched by children or by
those unfamiliar with its operation;
--- must not be exposed to weather condi-
tions.
n During the operation it is quite normal
that the boiler produces a white plume of
condensation vapour from the flue terminal.
This is due to the high efficiency of the ap-
pliance and may be particularly evident with
low out door temperatures.
Safe handling of
substances
Biasi products are manufactured in accordance
with ISO 9000 and do not, and will not, contain any
hazardous materials or substances such as as-
bestos, mercury or C.F.C.’s.
The app liance packaging does not contain any
substances, which may be considered a hazard to
health.
Combustion chamber panels
Material: mineral fibres
Known hazards --- Some p eople can suffer red-
dening and itching of the skin. Fibre entry into the
eye will cause foreign body irritation, which can
cause severe irritation to people wearing contact
lenses. Irritation to respiratory tract.
Precautions --- Dust goggles will protect eyes.
People with a history of skin complaints may be
particularly susceptible to irritation. High dust le-
vels are only likely to arise following harsh ab-
rasion. In general, normal handling and use will
not present high risk, follow good hygiene prac-
tices, wash handsbefore, touching eyes, consum-
ing food, drinking or using the toilet.
First aid --- Medical attention must be sought fol-
lowing eye contact or prolonged reddening of the
skin.
Thermostat / Temperature gauge
Description --- Sealed phial and capillary contain-
ing liquid.
Known hazards --- irritating to skin, eyes and
throat. Vapour is harmful. Inflammable --- do not
extinguish with water.
Precautions --- Do not incinerate. Avoid contact
with broken/leaking phials. Do not purposely
puncture.
First aid medical attention must be sought follow-
ing eyes/skin contact, wash with clean water.
Appliance category I
2H
Gas G20 20 mbar
Country of destination: United Kingdom (GB) Ireland (IE)
This appliance conforms with the EEC directive 90/396 and, consequently, it has the right to make use
of the brand name
Moreover, the ap pliance conforms with the EEC directive 87/308 relative to the prevention and elimina-
tion of radio disturbances.
Theapplianceisbuilttocomplywiththeregulationnowinforceregardinggasappliancessafetyand
the E uropean regulation now in force relative to safety of household and similar electrical appliances.
The manufacturer, in the continuous process to improve his products, reserves the right to modify the
data expressed in the present documentation at any time and without prior notice.
The present documentation is an informative support and it cannot be considered as a contract to-
wards third parties.
Boiler installation and commissioning tips
n The installation must be carried out by
a qualified person who will be responsible for
observing the current Regulations.
Installing the boiler...
n Donotforgettoremovethetransitcaps
and plugs from the boiler connections these
are fitted to every boiler.
n Keep the boiler clear of dust during in-
stallation and in particular do not allow any
dust or debris to enter the top o f the boiler
where the flue connection is made. It is rec-
ommended that you put a dust sheet over the
top of the boiler until you are ready to make
the flue connection.
n Because every boiler is fired and tested
live at the factory, a small amount of water re-
mains within the boiler. It is possible for this
water to initial ly cause the pump to seize. It is
therefore recommended that the pump rotor
be manually turned to free its rotation before
turning the boiler on.
n Remember to release the auto air purge
before filling the boiler. See the instructions to
identify the location of this device.
n This boiler allows to control the flow tem-
perature of the central heating system at very
low levels.
In case of underfloor heating system a tem-
perature limiting device (e.g. a safety thermo-
stat) is recommended to stop the boiler in
case that the water temperature exceeds the
design temperature.
n You are strongly advised to flush out the
system both cold and hot in order to remove
system and installation debris.
n It is also sensible to initially fire and com-
mission the boiler before connecting any ex-
ternal control s such as a room thermostat. By
this method if you have a subsequent prob-
lem following the addition of an external con-
trol you can eliminate the boiler from your
fault analysis.
n If the boiler is fitted with a digital pro-
grammer, when setting the times for auto-
matic operation, remember that for every
“ON” time there must be an “OFF time to fol-
low and that on every occasion you enter a
time you must also indicate which days that
you want the boiler to follow the timed set-
tings.
n Some products incorporate an anti cycl-
ing time delay. It is normal when first switc h-
ing the boiler on for the boiler to operate on
heating for a few seco nds then switc h off.
After 3--- 4 minutes has elapsed the boiler will
then re ignite and operate perfectly normally.
The ignition delay cycle does not prevent
normal operation of the boiler to provide
d.h.w.
n If you are in any doubts as to the ins talla-
tion or operation of the boiler please read the
instruc ti on manuals tho r oughly and then if
necessary contact Biasi UK for advice and
assistance.
Please remember that if you are in any doubt about the installation of this product you can contact our
Technical Helpline on tel. 0121 506 1350
TABLE OF CONTENTS
1
1 Appliance description 2..........
1.1 Overview 2......................
1.2 Control panel 2..................
1.3 Isolation valves 2.................
1.4 Technical data 2.................
1.5 Ope ration lights 3................
2 Instructions f or use 4............
2.1 Warnings 4......................
2.2 Refilling procedure 4..............
2.3 Ignition 4........................
2.4 C.h. circuit temperature 5..........
2.5 D.h.w. temperature 6..............
2.6 Extinguishing 7..................
2.7 Built in time switch 7..............
3Usefuladvice 10.................
3.1 Central heating 10.................
3.2 Frost pr otection 10................
3.3 Periodic maintenance 10...........
3.4 External cleaning 10...............
3.5 Operational faults 10...............
4 Technica l information 12..........
4.1 Overview 12......................
4.2 Main diagram 13..................
4.3 Technical data mod. M110.24SM/... 14
4.4 Technical data mod. M110.32SM/... 16
4.5 Hydraulic specifications 18.........
4.6 Expansion vessel 18...............
5 General requirements 19..........
5.1 Related documents 19.............
5.2 Location of appliance 19...........
5.3 Flue system 19....................
5.4 Gas supply 20....................
5.5 Air supply 20.....................
5.6 Ventilation 20.....................
5.7 Condensate drain 20..............
5.8 W ater circulation (c.h.) 21...........
5.9 Domestic water 22.................
5.10 W ater treatment 22................
5.11 Electrical supply 22................
6Installation 23....................
6.1 Warnings 23......................
6.2 Precautions for installation 23.......
6.3 Installing the bracket 23............
6.4 Overall dimensions 24.............
6.5 Joints 24.........................
6.6 Mounting the b oiler 24.............
6.7 Fittingthefluesystem 25...........
6.8 Choice of flue 25..................
6.9 Electrical connections 26...........
6.10 External frost protection 28.........
6.11 External temperature probe (optional) 28
7 Commissioning 30...............
7.1 Electrical installation 30............
7.2 Gas supply installation 30..........
7.3 Filli ng the d.h.w. system 30.........
7.4 Initial filling of the system 30........
7.5 Condensate pipe and traps 31......
7.6 Lighting the boiler 31..............
7.7 Checking the gas supply pressure 32
7.8 Maximum output in c.h. mode 33....
7.9 External temperature probe setting
(optional) 33......................
7.10 Checking the ignition device 34.....
7.11 Checking the flue system 34........
7.12 Checking th e condensate drain pipe 34
7.13 Instructing the user 34.............
8 Maintenance 35..................
8.1 Warnings 35......................
8.2 Dismantling the external panels 35...
8.3 Emptying the d.h.w. system 35......
8.4 Emptying the c.h. system 35........
8.5 Combustion ana lysis check 36......
8.6 Cleaning the condensing heat
exchanger and burner 36...........
8.7 Checking the pressurisation
in the expansion vessel 37..........
8.8 Cleaning the burner 37.............
8.9 Checking the flue 37...............
8.10 Drain pipe inspecti on 37............
8.11 Visual inspection of appliance 37....
8.12 Gas p ressures and soundness 37...
8.13 W ater inhibitor concentration 37.....
Abbreviations used in the manual:
C.h. = Central heating
D.h.w. = Domestic hot water
D.c.w. = Domestic cold water
USE
INSTALLATIONMAINTENANCE
2
1Appliancedescription
1.1 Overview
2
1
3
Fig. 1.1
1Casefrontpanel
2Controlpanel
3 Control panel cover
1.2 Control panel
4 C.h. circuit temperature and pressure ga uge
5 Time switch (c.h. control)
6 L o c k --- o u t s i g n a l l a m p
7 Lockout reset button
8 Function selector and c.h. temp. control knob
9 D.h.w. temperature control knob
10 Appliance operation lights
1.3 Isolation valves
14
12
16
13
15
11
Fig. 1.2 (bottom view of the boiler)
11 Condensate drain pipe
12 C.h. return valve
13 D.c.w. inlet valve
14 Gas inlet valve
15 D.h.w. outlet pipe
16 C.h. flow valve
1.4 Technical data
For detailed technical data see section 4.3 or 4.4
of this manual.
89 7 6 4510
Fig. 1.3
USE
Appliance description
3
1.5 Operation lights
Three lights (10 in Fig. 1.3) give detailed indication
regarding the operation of the boiler.
The f ollowing table gives the relationship between
each of the possible light combinations and their
meaningduringthenormaloperationoftheboiler.
A short pulse every 4
seconds:
stand--- by condition
Function selector in
position.
Anti--- freeze system active
1 second pulse every 2
seconds: normally
operating boiler. Function
selector in or
position
C.h. operation
D.h.w. operation
Frost protect operation
D.h.w. operation
Excessive temperature on
primary circuit
If the lights combination observed is not included
in the above table a fault may be indicated.
Reference should be made to the following table.
In this case switch off the boiler, as described in
section 2.6 on page 7 and call a competent and re-
sponsible service en gineer.
Faulty c.h. temperature
probe NTC
Faulty d.h.w temperature
probe NTC
F aulty primary circuit
(no water or absence of
flow)
Lack of burner ignition
Safety thermostat lock out
F aulty fan control system
Flue temperature probe
NTC lock out
Open flue temperature
probe NTC
F aulty external temp.
probe (if fitted)
Flame detection error
Other faults
Lack of power supply or
faulty electronic control
p.c.b.
Meaning of symbols
Lamp OFF
Lamp ON
Flashing lamp, alone or simultaneously
with an other lamp.
Flashing lamp, alternate with another
lamp.
USE
4
2 Instructions for use
2.1 Warnings
Biasi UK Ltd support t he Benchmark initiat-
ive. The Benchmark Log Book is located at
the back of this manual and should be com-
pleted by the Installing/Commissioning E n-
gineer and handed over to the User for fu -
ture reference by other visiting Engineers.
Also included is the Service Interval Record
card that should be completed by the Ser -
vice Engineer following the annual service
maintenance of the boiler and system.
All CORGI Registered Installers carry a
CORGI ID card, and have a registration
number. Both should be recorded in your
Benchmark Log Book. You can check your
installer is registered by calling CORGI di-
rect on 01256 372300.
In order to guarantee safety and correct oper-
ation, it is essential that all the tests are carried
out by a competent and responsible service
engineer before lighting up the boiler.
The tests are described in the installation in-
structions in section 7 c ommissioning.
Ensure that the c.h. circuit is regularly filled with
water (even if the boiler is only used for d.h.w.
supply) checking that the pressure indicated
on the temperature and pressure gauge 4 is
notlowerthanthatshowninFig.2.2.
If the pressure reading on the pressure gauge
is below that shown in Fig. 2.2, then the system
will require topping up. A filling loop is normally
provided by the installer for this purpose.
If you are in any doubt regarding this pro-
cedure you are advised to contact your In-
stalleroranApprovedEngineer.
This appliance is provided with a built in anti---
freeze system that operates the boiler when the
temperature is below 5 ˚C
Therefore, when the boiler is not lit or used in
cold weather, with consequent risk of freezing
do not switch off the boiler at the fused spur
isolationswitchorclosethegasinletcock.
When you do not expect to use the boiler for a
long period and the boiler is not to be used for
frost protection then follow the instructions
given in section 2.6 on page 7.
2.2 Refilling procedure
1 Isolate the boiler from the electrical supply at
the fused spur. Reconnect the f illing loop as
demonstrated i n Fig. 2.1.
Te mp o ra ry
connection
Control valve
Control valve
Double check valve
Supply pipe
(cold water inlet)
C.h. return pipe
Fig. 2.1
2 Open the valves of the filling loop and watch
the gaug e u ntil it reaches normal filling pres-
sure as shown in Fig. 2.2.
4
Normal filling
pressure
Fig. 2.2
3 Close the valves and remove the filling loop.
If you experience any difficulty with the oper-
ation of the boiler, switch off the boiler immedi-
ately at the fused spur isolation switch a nd
contactyourInstalleroranapprovedService
Engineer
Air introduced into the boiler during this filling pro-
cess will vent through the automatic air purger
fitted to the boiler. You may also find it necessary
to vent air from your radiator circuit using your
radiator key, however be aware that excessive
venting will cause the pressure in the system to
drop.
Always ensure that the p ressure gauge is set at the
required pressure.
2.3 Ignition
1 Check that the valves located in the lower part
of the boiler are open (Fig. 2.3).
USE
Instructions for use
5
Open position
Fig. 2.3
2 Turn on the electricity supply to the boiler,
switching on the fused spur isolation switch.
The appliance operation light 10 (Fig. 2.4) will
flash every 4 seconds (stand---by condition).
3 If the boiler isto be used for c.h. and d.h.w posi-
tion the function selector 8 as in Fig. 2.4.
The appliance operation light 10 will flash
every 2 seconds (operating boiler).
810
Fig. 2.4
4 If d.h.w. supply only is required, position the
function selector 8 as in Fig. 2.5.
The appliance operation light 10 will flash
every 2 seconds (operating boiler).
810
Fig. 2.5
2.4 C.h. circuit temperature
The output temperature of c.h. water is adjustable
from a minimum of about 25°C to a maximum of
about 85°C (Fig. 2.6), by turning the knob (8).
Adj ustment of the boiler temperature alters the
gas flow at the burner according to the thermal de-
mand in the system. So it is usual to see the burner
litattheminimumlevelformoreorlesslong
periods.
It is possible to fit to this boiler an optional outside
temperature sensor which helps to manage and
control the boiler and system efficiency. The fol-
lowing instructions indicate how to set the output
temperature of the c.h. water depending on
whether the optional outside sensor h as been
fitted.
Minimum
Maximum
Fig. 2.6
Adjustment WITHOUT the external tempera-
ture probe (optional) fitted
In order to achieve optimal settings for economy
and comfort, we recommend adjusting the oper-
ating temperature of the c.h. water according to
the outside temperature, positioning the knob as
follows:
USE
Instructions for use
6
Lower than
--- 5 ˚C
From5to15˚C
Between
--- 5 a n d + 5 ˚ C
Fig. 2.7
Your qualified installer will be able to recommend
the most suitable adjustment for your system.
The temperature and pressure gauge (4, Fig. 1.3
on page 2) will allow you to check that the set tem-
perature is obtained.
Adjustment WITH the external temperature
probe (optional)
When the boiler is connected to the external tem-
perature probe (optional), the temperature of the
c.h. flow is automatically adjusted with reference
to the external temperature.
Inthiscasetheboilermustbeproperlysetbythe
installer (as described in section 7.9 of this man-
ual) and the c.h. flow temperature control knob
must be positioned as illustrated in Fig. 2.8.
To satisfy temporary changes or different room
temperatures, the c.h. water temperature can also
be manually increased or decreased within a
range of ±15 ˚C by turning the knob 8 (Fig . 2.8).
More details are given in section 7.9 of this man-
ual.
8
+15
--- 1 5
Fig. 2.8
2.5 D.h.w. temperature
The temperature of the d.h.w. leaving the boiler
can be varied from a minimum of about 35°Ctoa
maximum of about 55°C (Fig. 2.9), by turning the
temperature control knob 9.
9
Minimum
Maximum
Fig. 2.9
Adjustment of the d.h.w. temperature is complete-
ly separate from that of the c.h. circuit.
The adjustment system integrated within the
boiler automatically controls the flow of gas to the
burner in order to keep the temperature of d.h.w.
delivered constant, between the limits of maxi-
mum and minimum output.
Where the d emand is at a low level or with the tem-
perature set to the minimum, it is normal to see a
cycle of lighting and exting uishing of the burner
when running.
Adjustment
It is advisable to adjust the d.h.w. temperature to
a level commensurate with the demand, minimis-
ing the need to mix with cold water. In this way, the
automatic control facilities will b e fully exploited.
Where lime scale is present in the water supply
(hard water areas) it is also advisable not to ex-
ceed the setting position of the d.h.w. temperature
control knob (9) as indicated in Fig. 2.10. This will
help to minimise the incidences of scale deposits
clogging the domestic hot water heat exchanger
of the boiler.
USE
Instructions for use
7
9
Fig. 2.10
In these cases, however, it is advisable to install a
small water treatment device or softener. With
such a device you should avoid periodic descal-
ing.
Consequently, the d.h.w. heat exchanger will keep
its performance consistent for a longer period of
time with resulting gas savings.
If the demand for d.h.w. is so great as to p revent
reaching a high enough temperature,have the ap-
propriate output limitin g valve installed by your in-
staller or an Authorised Service Engineer.
2.6 Extinguishing
To turn the boiler off set the function selector 8 to
the position shown in Fig. 2.11.
The appliance operation light 10 will flash every 4
seconds.
810
Fig. 2.11
When you do not expect to use the boiler for a long
period:
1 Switch off the electricity supply to the boiler, by
means of the fused spur isolation switch;
2 Shut off the g as supply cock 14 and the valves
forthewatercircuitsfittedundertheboiler
(Fig. 2.12).
3 Empty the water circuits, if necessary , as
shownintheinstallation instructions in the sec-
tion maintenance.
Closed position
14
Fig. 2.12
2.7 Built in time switch
The combi boilers a re equipped with a built in elec-
tronic time switch (5, Fig. 1.3 on page 2) which
controls the c.h. operation.
J
A
BCDEF
G
I
H
Fig. 2.13
Display and control panel
AModeselectorswitch
B Reset button
CEnterbutton
D Increase “+” setting button
E Decrease --- setting button
F O n --- o f f b u t t o n
G Day selection buttons
USE
Instructions for use
8
HDaydisplay
ITimedisplay
J O N --- O F F d i s p l a y
Setting the current time and weekday
Note: with a new unit or when the reset button B
has been pressed, the first day indicator H on the
left and the time display I are flashing.
Set the mode selector switch A to the
position
and press the buttons D or E until the current time
appears in the display I.
Press the da y selection button corresponding to
the current day, considering that button
1=Monday, button 2=Tuesday and so on.
The clock starts by moving the switch A to the
AUTO position.
Setting example shown in Fig. 2.14:
Current time 16.30, day Thursday.
A
Fig. 2.14
Setting the switching time and day (or days)
20 memory locations are available, corresponding
to 10 on--- off sequences.
Set the mode selector switch A to the C1 position.
The symbols shown in Fig. 2.15 appears in the
display.
A
Fig. 2.15
Press the buttons D or E to set the desired ON
time.
PressthebuttonsGtosetthedesireddayordays
of operation.
Press the enter” button C to confirm the setting
and to continue programming the OFF time.
SettheOFFtimeasexplainedabovefortheON
setting and confirm by pressing the enter” button
C. Proceed in the same way for other settings.
SettingexampleshowninFig.2.16:
A --- ON time 7.45, day Monday to Friday.
B --- OFF time 10.30, day Monday to Friday.
AB
Fig. 2.16
Activating the timed settings
Set the mode selector switch A to the AUTO posi-
tion shown in Fig. 2.17.
The current time and day appears in the display.
The ON--- OFF display J indicates the current state
of operation (according to the settings).
A
Fig. 2.17
Note: when the mode selector switch A is in the
AUTO position and the boiler is switched off at the
fused spur isolation switch, the display J indicates
only the OFF state. The other indications are
blanked.
Reading the timed settings
Set the mode selector switch A to the C1 position.
The symbols shown in Fig. 2.15 appears in the
display.
Press the “enter button C. Each time the button
is pressed the display shows the details of the next
setting.
The day display H gives a flashing indication of the
active day or group of days.
Changing or deleting the timed settings
Set the mode selector switch A to the C1 position.
The symbols shown in Fig. 2.15 appears in the
display.
Press the “enter button C until the display shows
the setting to be modified or deleted.
USE
Instructions for use
9
The d ay display H gives a flashing indication of the
activ e day or group of days.
Press the button (or the b u ttons) G corresponding
to the day (or days) for which it is intended to apply
the modification. The corresponding day display
stops flashing and a new switching time can be set
or deleted.
Thetimesettingcanbemodifiednowbypressing
button D or E and the operation can be switched
on or off by pressing the button F.
To deletea time set press the button D or E until the
symbols shown in Fig. 2.15 appears in the time
display I.
The new settings are memorised by moving the
switch A to a different position.
Manual operation
The operation of the time switch can be forced on
or off constantly or for a timed period.
To f o r ce constantly on or off the timer operation
set the mode selector switch A to the TIMER posi-
tion. The symbols shown in Fig. 2.18 appears on
the display .
Fig. 2.18
The opera tion can be switched p ermanently on or
off by pressing the button F and leaving the switch
AintheTIMER position.
To f or c e atimeddelayon or off operation, set the
mode selector switch A in the TIMER position.
SetthetimedelaybypressingthebuttonDorE
and the operation can be f orced on or off by pres-
sing the button F.
Thetimedelaycanbesetwithinthefollowing
ranges:
1to23hourswithstepsof1hour
1to27dayswithstepsof1day
The time delay setting is activated by moving the
switch A to the AUTO position.
The ON--- OFF display J flashes indicating that the
current state of operation has been forced.
To delete the timed d e lay setting, set the mode se-
lector switch A in the TIMER position, press the
button D or E until the symbols shown in Fig. 2.18
appears in the display and then set the mode se-
lector switch A to the AUTO position
SettingexampleshowninFig.2.19:
forced ON state for 4 hours.
Fig. 2.19
Resetting
To completely reset the timer, press the reset but-
ton with a pointed object (pencil).
CA UTION : pushing the reset button will complete-
ly erase the settings as well as all the data, includ-
ing the current time and day.
USE
10
3Usefuladvice
3.1 Central heating
For reasonably economical service install a room
thermostat.
Never shut off the radiator in the area where the
room thermostat is installed.
If a radiator (or a convector) does not heat up,
check that no a ir is present in it and that its valve
is open.
If the ambient temperature is too high, do not alter
the radiator valves. Reduce the central heating
temperature instead by means of the room ther-
mostat and the function selector (8 in Fig. 3.1).
8
Fig. 3.1
3.2 Frost protection
This appliance is provided with a built in anti---
freeze system that operates the boiler when the
temperature is below 5 ˚C
Therefore, when the boiler is not lit and used in
cold weather, with consequent risk of freezing do
not switch off the boiler at the fused spur isola-
tion switch or close the gas inlet cock.
3.3 P eriodic maintenance
For efficient and continuous operation of the
boiler, it is advisable to arrange maintenance and
cleaning by an Authorised Service C entre En-
gineer, at least once a y ear.
During the service, the most important compo-
nents of the boiler will be inspected and cleaned.
This service can be part of a maintenance con-
tract.
In particular, you are advised to have the following
checks carried out:
--- domestic hot water heat exchanger;
--- condensing heat exchanger
--- burner;
--- exhaust fume duct and flue;
--- pressurisation of the expansion tank;
--- filling up of the central heating circuit;
--- bleeding of air from the central heating system;
--- general check of the appliance’s operation.
3.4 External cleaning
Before carrying out any cleaning, disconnect the
appliance from the electrical mains, using the
fused spur isolation switch fitted adjacent to the
appliance.
To clean the external panels, use a cloth soaked in
soapy water. Do not use solvents, abrasive powd-
ers or sponges.
Do not carry out cleaning of the appliance and/or
its parts with readily flammable substances (for
example petrol, alcohols, n ap htha, etc.).
3.5 Operatio nal faults
If the lock---out signal lamp (6 in Fig. 3.2) comes
on
this indicates that the safety lock--- out has stopped
the boiler.
To re--- start the boiler, it is necessary to press the
boiler reset button 7 (F ig. 3.2).
7
6
Fig. 3.2
F or the first lighting up and following maintenance
procedures for the gas supp ly, it may be necess-
ary to rep eat the resetting operation several times
so as to remove the air present in the pipework.
After five consecutive resetting attempts the reset
button is inhibited. To restore its function it is
necessary to switch the boiler off and on from the
electrical mains, using the fused spur isolation
switch fitted adjacent to the appliance.
Safety lock--- out may occur even in case of an
blockage of the condensate drainage (e.g.
plugged drain pipe).
Itisadvisabletocheckthecondensatedrainage
pipe and traps for cleanness.
In this case and in case of persistent lock--- out call
a competent and resp onsible service engineer.
USE
Useful advice
11
If noises due to a ir bubbles are heard during
operation...
you should check that the pressure on the tem-
perature and pressure gaug e (Fig. 2.2 on pag e 4)
is not below the correct setting.
If required, top up the system correctly, as de-
scribed in the section 2.2 of this manual.
Bleed any air present in the radiators, if necessary.
If the pressure on the temperature and pres-
suregauge(4onpage2)hasgonedown...
it is necessary to top up the appliance with water
again, so as to raise the pressure to an adequate
level as d escribed in the section 2.2 of this manual.
If topping up with water has to be done very fre-
quently, have the system checked for leaks.
If water comes out of the pressure relief valve
Check on the temperature and pressure gauge (4
on page 2) that the pressure in the central heating
circuit is not close to 3 bars. In this case, tempera-
ture rise in the circuit can cause the pressure relief
valve to open.
So that this does not happen and to d ecrease the
pressure to a normal value, it is advisable to v ent
some of the water in the appliance through the
bleed valves present in the radiators.
If in time, a reduction in domestic hot water
supply is observed...
The likely causes may be impurities caught in the
domestic hot water flow switch filter or limescale
deposited in the domestic hot water heat ex-
changer. It is advisable to have the appliance
cleaned out by an Au thorised Service Centre En-
gineer.
If water should occasionally leak from the
boiler...
shut off the valves positioned under the b oiler
(Fig. 2.12 on page 7) and call an Authorised Ser-
vice Centre Eng ineer.
In this case or in case of problems other than
those mentioned here, switch off the boiler, a s
described in section 2.6 on page 7 and call a
competent and responsible service engineer.
USE
12
4 Technical information
4.1 Overview
26
19
37
38
31
21
25
34
18
35
27
30
22
17
28
29
32
39
20
36
24
33
23
Fig. 4.1
11 Condensate drain pipe
12 C.h. return valve
13 Domestic cold water inlet valve
14 Gas inlet valve
15 D.h.w. outlet pipe
16 C.h. flow valve
17 Condensing heat exchanger air p urger valve
18 C.h. temperature probe NTC
19 Condensing heat exchanger
20 Safety thermostat
2 1 F l a m e --- d e t e c t i n g e l e c t r o d e
22 Transformer
23 Air hose
24 C.h. pressure relief valve
25 Automatic air purg er valve
26 Main circuit drain valve
27 Pump
28 Pump vent plug
29 Gas valve
30 D.h.w. temperature probe NTC
31 Primary circuit flow switch
32 Condensate trap
33 D.h.w. heat exchanger
3 4 T h r e e --- w a y d i v e r t e r v a l v e
35 Fan
36 Spark generator
37 Ignition electrodes
38 Burner
39 Flue temperature probe NTC
40 D.h.w. flow switch
41 Gas valve inlet pressure test point
42 Gas valve outlet pressure test point
43 C. h. expansion tank
4 4 B y --- p a s s v a l v e
45 Domestic water circuit filter
46 D.h.w. flow limiter
47 Flue outlet pipe
48 Air intake pipe
49 Flue exhaust samp ling point
50 Air sampling point
INSTALLATION
Technical information
13
4.2 Main diagram
48
47
31
19
37
27
24
40
29
41
25
34
33
44
45
12 131614
43
35
21
18
30
15
20
38
26
46
32
11
39
49
50
17
42
Fig. 4.2
INSTALLATION
Technical information
14
4.3 Technical data
mod. M110.24SM/...
Heat input
Nominal
net
(A)
kW
BTU/h
25,0
85 295
gross
(B)
kW
BTU/h
27,8
94 848
Minimum
net
(A)
kW
BTU/h
6,0
20 470
gross
(B)
kW
BTU/h
6,6
22 518
Useful output
Maximum kW
BTU/h
24,4
83 248
Minimum kW
BTU/h
5,8
19 788
Maximum condensing kW
BTU/h
26,3
89 730
Minimum condensing kW
BTU/h
6,3
21 494
Centra l heating
Maximum flow temp. ˚C 85
Minimum flow temp. ˚C 25
Maximum pressure kPa
bar
250
2,5
Minimum pressure kPa
bar
30
0,3
Available head
(in 1000 l/h)
kPa
bar
23
0,23
Seasonal efficiency
(C)
band
%
A
90,0
Domestic hot water
Maximum temperature ˚C 60
Minimum temperature ˚C 35
Maximum pressure kPa
bar
1 000
10
Minimum pressure kPa
bar
30
0,3
Flow rate
minimum l/min 2,5
30˚ rise
(D)
l/min 12,4
35˚ rise
(D)
l/min 10,4
40˚ rise
(D)
l/min 9,1
Gas supply pressure G20
Norm. Pa
mbar
2 000
20
Max Pa
mbar
2 500
25
Min. Pa
mbar
1 700
17
1 mbar approximately equals 10 mm H
2
O
Gas rate
Max. m
3
/h 2,65
Min. m
3
/h 0,63
Restrictors references
Gas 5,40
Air Fuchsia
(A)
referred to the net calorific value at 15 ˚C and 1013,25 mbar: G 20 = 34,02 MJ/m
3
(B)
referred to the gross calorific value at 15 ˚C and 1013,25 mbar: G 20 = 37,78 MJ/m
3
(C)
The value is used in the UK Government’s Standard Assessment P rocedure (SAP) for energy rating
of dwellings. The test data from which it has been calculated h ave been certified by a notified body.
(D)
Values subject to tolerance
INSTALLATION
Technical information
15
Electrical Data
Voltage V~ 230
Frequency Hz 50
Power consumption W 108
Protection degree IPX4D
External fuse rating A 3
Internal fuse rating A 3,15 AF
Flue design
Flue pipe diameter
Coaxial mm 60/100
Twin split pipes mm 80
Roof mm 80/125
Nominal heat flow rate
(A)(E)
kW 25,0
Exhaust temperature
(E)
˚C 85
Smoke production
(E)
kg/h 42
CO
2
conte nts
CO
2
content
( r a n g e m i n --- m a x )
% 9,0--- 9,8
At nominal heat input of 25,0 kW
(A)(E)
CO
2
content
( r a n g e m i n --- m a x )
% 9,0
At minimum heat input of 6,0 kW
(A)(E)
Other flue gas figures
At nominal heat input --- non condensing
O
2
content % 4,8
CO content ppm 150
Exhaust temperature ˚C 85
Other specifications
Height mm 803
Width mm 400
Depth mm 350
Weight (dry) kg 45
Water volume in the boiler
(upto1bar)
l(kg) 2
(E)
Values refer to tests with a 1 m chimney working at the nominal heat input
INSTALLATION
Technical information
16
4.4 Technical data
mod. M110.32SM/...
Heat input
Nominal
net
(A)
kW
BTU/h
33,5
114 295
gross
(B)
kW
BTU/h
37,2
126 920
Minimum
net
(A)
kW
BTU/h
11,0
37 530
gross
(B)
kW
BTU/h
12,2
41 624
Useful output
Maximum kW
BTU/h
32,7
111 566
Minimum kW
BTU/h
10,6
36 165
Maximum condensing kW
BTU/h
35,1
119 754
Minimum condensing kW
BTU/h
11,6
39 577
Centra l heating
Maximum flow temp. ˚C 85
Minimum flow temp. ˚C 25
Maximum pressure kPa
bar
250
2,5
Minimum pressure kPa
bar
30
0,3
Available head
(in 1000 l/h)
kPa
bar
27
0,27
Seasonal efficiency
(C)
band
%
A
90,0
Domestic hot water
Maximum temperature ˚C 60
Minimum temperature ˚C 35
Maximum pressure kPa
bar
1 000
10
Minimum pressure kPa
bar
30
0,3
Flow rate
minimum l/min 2,5
30˚ rise
(D)
l/min 16,5
35˚ rise
(D)
l/min 14,0
40˚ rise
(D)
l/min 12,1
Gas supply pressure G20
Norm. Pa
mbar
2 000
20
Max Pa
mbar
2 500
25
Min. Pa
mbar
1 700
17
1 mbar approximately equals 10 mm H
2
O
Gas rate
Max. m
3
/h 3,54
Min. m
3
/h 1,16
Restrictors references
Gas 6,40
Air Blue
(A)
referred to the net calorific value at 15 ˚C and 1013,25 mbar : G 20 = 34,02 MJ/m
3
(B)
referred to the gross calorific value at 15 ˚C and 1013,25 mbar: G 20 = 37,78 MJ/m
3
(C)
The value is used in the UK Government’s Standard Assessment P rocedure (SAP) for energy rating
of dwellings. The test data from which it has been calculated h ave been certified by a notified body.
(D)
Values subject to tolerance
INSTALLATION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Biasi Riva Advance M110.24SM/C, M110.32SM/C User manual

Category
Water heaters & boilers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI