Micro Motion Gas Flow Computers - Model 3711 Owner's manual

Type
Owner's manual
Configuration and Use Manual
P/N 20002983, Rev. A
October 2005
Micro Motion
®
Model 3711
Gas Flow Computers
Configuration and Use Manual
©2005, Micro Motion, Inc. All rights reserved. ELITE, ProLink, and the Micro Motion logo are registered trademarks of Micro
Motion, Inc., Boulder, Colorado. MVD and MVD Direct Connect are trademarks of Micro Motion., Inc., Boulder, Colorado. Micro
Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Emerson logo is a trademark of Emerson Electric
Co. All other trademarks are property of their respective owners.
Configuration and Use Manual i
Contents
Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 About the Model 3711 Gas Flow Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.1 Model 3711 system components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.2 User programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.3 Implementation overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Communication tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Model 3711 configuration overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5.1 Quick start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5.2 Basic configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5.3 Advanced options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.6 Model 3711 administration overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.7 Documentation resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.8 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Chapter 2 Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Starting the Model 3711 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Installing ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3.1 PC requirements for ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3.2 Installing ROCLINK 800. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Using ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4.1 Starting ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4.2 ROCLINK 800 user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4.3 TLP system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Configuration files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.1 Managing device configuration files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.2 Creating a new device configuration file . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.3 Device configuration backup and duplication. . . . . . . . . . . . . . . . . . . . . . 13
2.6 Setting up devices and groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7 First connection to the Model 3711 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.1 Disconnecting and closing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Chapter 3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Setting the Model 3711 clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 Configuring security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.1 ROCLINK 800 security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.2 Device security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3.3 Access level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4 Configuring Model 3711 device information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5 Configuring display options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ii Micro Motion
®
Model 3711 Gas Flow Computers
Contents
Chapter 4 Setting Up Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Connecting to the Model 3711 through the LOI . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4 Connecting to the Model 3711 through COMM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4.1 Using ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4.2 Using a host program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.5 Configuring communications parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.5.1 Configuring COMM 2 on the Model 3711 . . . . . . . . . . . . . . . . . . . . . . . . 27
4.5.2 Configuring ROCLINK 800 communications parameters . . . . . . . . . . . . 30
4.6 Configuring communications for RBX alarming . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.7 Configuring passthrough mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 5 Configuring the Core Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2 Configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3 Using ROCLINK 800 with the Micro Motion core interface . . . . . . . . . . . . . . . . . . . . 38
5.4 Core interface configuration panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.4.1 Mass Flow panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.4.2 Density panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4.3 Temperature panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.5 Special topics in configuring the core interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.5.1 Characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.5.2 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.5.3 Meter factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.5.4 Slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.6 Zeroing the meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 6 Configuring Volumetric Flow Measurement . . . . . . . . . . . . . . . . . . 49
6.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.2 Terminology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3 Configuration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.1 Input Defs panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.2 Mass Compensation panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.4 Gas Quality panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.1 Advanced panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.4.2 Sampler panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.5 AO Assignment panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5.1 Alarms panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Chapter 7 Configuring I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.3 Configuring I/O type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.4 Configuring analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.4.1 Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.4.2 Analog Input – General panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.4.3 Analog Input – Advanced panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.4.4 Analog Input – Alarms panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Configuration and Use Manual iii
Contents
7.5 Configuring an analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7.5.1 Analog Output – General panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
7.5.2 Analog Output – Advanced panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
7.6 Configuring discrete inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7.6.1 Discrete Input – General panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7.6.2 Discrete Input – Advanced panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
7.6.3 Discrete Input – Alarms panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.7 Configuring the discrete outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.7.1 Discrete Output – General panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.7.2 Discrete Output – Advanced panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.7.3 Discrete Output – TDO Parameters panel . . . . . . . . . . . . . . . . . . . . . . . . 76
7.8 DOUT Type options and examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.8.1 Accuracy of Time Duration and TDO Toggle . . . . . . . . . . . . . . . . . . . . . . 78
7.8.2 Durations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.8.3 Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.9 Configuring pulse inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
7.9.1 Pulse Input – General panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
7.9.2 Pulse Input – Advanced panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
7.9.3 Pulse Input – Alarms panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 8 Managing History, Events, and Alarms . . . . . . . . . . . . . . . . . . . . . 85
8.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.2.1 History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.2.2 Events and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.3 Configuring history points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
8.3.1 Archive types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
8.3.2 Standard history predefined points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
8.4 Using the historical databases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
8.4.1 Viewing history data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
8.4.2 Viewing alarm logs and event logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
8.4.3 Using the log display window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 9 Monitoring and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.2 Model 3711 display variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.2.1 Display rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.2.2 Configuring display variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.3 ROCLINK 800 I/O monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.4 ROCLINK 800 custom displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.4.1 Creating a custom display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.4.2 Saving and loading custom displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
9.4.3 Editing a custom display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.4.4 Using custom displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Chapter 10 PID Control Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.2 PID control loops overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
10.2.1 PID control loop example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10.3 Configuring a PID control loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
10.4 Tuning the PID control loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
10.5 Monitoring the PID control loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
iv Micro Motion
®
Model 3711 Gas Flow Computers
Contents
Chapter 11 Function Sequence Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.2 FST overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.3 FSTs and Model 3711 points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.4 FST Editor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.5 Developing an FST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
11.6 Monitoring and tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.6.1 Monitor mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
11.6.2 Trace mode and debugging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
11.7 Using FSTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
11.7.1 Saving, reading and downloading FSTs . . . . . . . . . . . . . . . . . . . . . . . . 117
11.7.2 Starting and stopping FSTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
11.7.3 FST storage and restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
11.7.4 Deleting an FST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
11.7.5 Printing and exporting an FST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
11.7.6 Editing an FST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
11.7.7 Troubleshooting an FST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
11.8 FST command library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
11.8.1 Mathematical commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
11.8.2 Logical commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
11.8.3 Comparison commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
11.8.4 Time-related commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
11.8.5 Control-related commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
11.8.6 Database commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
11.8.7 Miscellaneous commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
11.9 FST examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
11.9.1 Example 1 – Writing data to a history point . . . . . . . . . . . . . . . . . . . . . . 128
11.9.2 Example 2 – Stopping an FST after task completion . . . . . . . . . . . . . . 129
11.9.3 Example 3 – Cycling an FST on a periodic basis . . . . . . . . . . . . . . . . . 130
11.9.4 Example 4 – Calculate an FST’s approximate execution rate . . . . . . . . 131
Chapter 12 Modbus Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.3 Modbus overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.4 Modbus and Model 3711 points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
12.5 Configuring the Modbus interface on the Model 3711 . . . . . . . . . . . . . . . . . . . . . . 135
12.5.1 Modbus scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
12.5.2 Datatype conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12.5.3 Modbus register ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
12.5.4 Modbus date and time formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12.6 Accessing Model 3711 data via the Modbus interface . . . . . . . . . . . . . . . . . . . . . . 145
12.6.1 Register addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12.6.2 Accessing history data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12.6.3 Accessing event and alarm data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Chapter 13 Model 3711 Operator Interface. . . . . . . . . . . . . . . . . . . . . . . . . . 149
13.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
13.2 Viewing process data and system information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
13.2.1 Using the Rates & Totals windows. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
13.2.2 Using the volumetric flow measurement configuration panels. . . . . . . . 151
13.2.3 Using the core interface configuration panels . . . . . . . . . . . . . . . . . . . . 151
Configuration and Use Manual v
Contents
13.3 Initial calculations and recalculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
13.4 Viewing sensor alarms and communication statistics . . . . . . . . . . . . . . . . . . . . . . . 153
13.5 Reading and writing to the core processor Modbus interface . . . . . . . . . . . . . . . . . 154
Chapter 14 Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
14.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
14.2 Initializing the Model 3711 and managing memory. . . . . . . . . . . . . . . . . . . . . . . . . 157
14.2.1 Using the jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
14.2.2 Using ROCLINK 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
14.3 Model 3711 memory structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
14.4 Meter default values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
14.5 Event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
14.6 Alarm log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
14.7 Advanced communications and system controls . . . . . . . . . . . . . . . . . . . . . . . . . . 163
14.8 Using the optional dial-up modem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
14.9 Managing user programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
14.10 Managing device configuration files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
14.10.1 Opening a device configuration file . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
14.10.2 Closing a device configuration file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
14.10.3 Downloading a device configuration file to the Model 3711. . . . . . . . . . 166
14.11 Printing and exporting a device configuration file . . . . . . . . . . . . . . . . . . . . . . . . . . 167
14.12 Updating firmware and user programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
14.12.1 Updating the Model 3711 device firmware. . . . . . . . . . . . . . . . . . . . . . . 167
14.12.2 Updating the user programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
14.13 Upgrading hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Chapter 15 Maintenance and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 171
15.1 About this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
15.2 Troubleshooting the connection between ROCLINK 800 and the Model 3711 . . . . 171
15.3 Debugging ROCLINK 800 communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
15.4 Dial-up modem and FCC compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.5 Diagnostic monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
15.6 Low power shutdown mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
15.7 MPU loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
15.8 Backup battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.9 Automatic self-tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.10 Status alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.11 Checking process variables and test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
15.12 Checking slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
15.13 Checking the characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
15.14 Checking the calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
15.15 Diagnosing wiring problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
15.15.1 Checking the power supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
15.15.2 Checking the sensor-to-transmitter wiring . . . . . . . . . . . . . . . . . . . . . . . 180
15.15.3 Checking grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
15.16 Checking the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
15.16.1 Evaluating the test points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
15.16.2 Drive gain problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
15.16.3 Low pickoff voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
15.17 Checking the core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
15.17.1 Checking the core processor LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
15.17.2 Core processor resistance test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
vi Micro Motion
®
Model 3711 Gas Flow Computers
Contents
15.18 Checking sensor pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
15.18.1 Remote core processor with remote transmitter installation . . . . . . . . . 184
15.18.2 4-wire remote installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Appendix A Installation Types and Components. . . . . . . . . . . . . . . . . . . . . . . 189
A.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
A.2 Installation architectures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
A.3 Remote core processor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
A.4 I.S. barrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
A.5 Termination boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Appendix B Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
B.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
B.2 Calibrating an analog input or RTD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
B.2.1 Preparing for calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
B.2.2 Calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
B.2.3 Verification procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
B.2.4 Viewing calibration values for analog inputs or RTD . . . . . . . . . . . . . . . 197
B.3 Calibrating the analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
B.4 Density calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
B.4.1 Preparing for calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
B.4.2 Calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Appendix C Points and the TLP System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
C.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
C.2 Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
C.3 TLP system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
C.3.1 Points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
C.3.2 Logical numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
C.3.3 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Appendix D Soft Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
D.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
D.2 Soft point overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
D.3 Configuring soft points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Appendix E Opcode Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
E.1 About this appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
E.2 Opcode table overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
E.3 Configuring opcode tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Configuration and Use Manual 1
Getting Started CommunicationsSystemBefore You Begin
Chapter 1
Before You Begin
1.1 Overview
This chapter provides an orientation to the use of this manual, and includes a pre-configuration
worksheet. This manual describes the procedures required to start, configure, use, maintain, and
troubleshoot the Micro Motion
®
Model 3711 Gas Flow Computer system.
1.2 Safety
Safety messages are provided throughout this manual to protect personnel and equipment. Read each
safety message carefully before proceeding to the next step.
1.3 About the Model 3711 Gas Flow Computer
The Micro Motion Model 3711 is a compact, high-performance gas flow computer specifically
designed to provide fiscal measurement data for gas applications. The Model 3711 uses a Micro
Motion Coriolis sensor with MVD
technology to measure the gas flow.
The Model 3711 system performs flow measurement compliant with API MPMS Chapter 21.1a in
accordance with the AGA8-92 gas measurement standard.
1.3.1 Model 3711 system components
The Model 3711 system includes the following components:
Model 3711 Gas Flow Computer
Micro Motion sensor
Micro Motion core processor (may be mounted on sensor)
MVD Direct Connect
I.S. barrier
See Figures A-1 and A-2 for diagrams.
1.3.2 User programs
The Model 3711 functionality is implemented via two user programs:
Core Interface – handles communication between the Model 3711 and the sensor; performs
the sensor zero and density calibration procedures
Gas Flow Computer Calculations – performs volumetric flow measurement and displays flow
rates and totals; manages pressure compensation on mass flow rate
These two programs are preloaded onto the Model 3711.
2 Micro Motion
®
Model 3711 Gas Flow Computers
Before You Begin
1.3.3 Implementation overview
A typical Model 3711 gas measurement system is configured to write measurement data to history at
minute, hourly, daily, and user-specified intervals. The history data is then delivered to an external
system for various accounting and analysis procedures. The delivery interval is controlled by the user.
The event and alarm logs contain information related to configuration changes and various system
conditions. Events and alarms are logged automatically. The event and alarm logs may also be
delivered to an external system.
Two methods for delivering history, event, and alarm data are available:
Manual – The user manually saves the history, event, or alarm data to a file, and then sends the
file to the appropriate parties.
Remote communications – A host system connects to the Model 3711 and retrieves the history
data. The host communications program may use either Modbus or ROC protocol.
- If Modbus protocol will be used, the Modbus interface on the Model 3711 must be
configured.
- No special setup is required to use ROC protocol.
Measurement data may also be viewed on the Model 3711 LCD, or on various ROCLINK
800
windows.
1.4 Communication tools
A special version of the ROCLINK 800 software program has been developed for configuration,
operation, and maintenance of the Model 3711. This version is written to include the two user
programs described in Section 1.3.2, which are presented as custom displays accessed via the Meter
menu. This version of ROCLINK 800 is available from Micro Motion. Installation and basic use of
ROCLINK 800 is discussed in Chapter 2.
If desired, a host program may be written to communicate with the Model 3711.
1.5 Model 3711 configuration overview
To get the Model 3711 system into operation using default values for most parameters, follow the
“quick start” steps in Section 1.5.1. The default values have been defined to provide the required
measurement and history data for most applications.
Section 1.5.2 lists the tasks involved in a basic setup and configuration. Chapters 2 through 8 of this
manual present the required tasks in the order listed here.
Section 1.5.3 lists configuration options which may or may not be implemented in your application.
More information on these options is provided in Chapters 9 through 12.
1.5.1 Quick start
1. Start the Model 3711 – see Section 2.2
2. Install ROCLINK 800 software – see Section 2.3
3. Make a direct connection to the Model 3711 – see Section 2.7
4. Set the Model 3711 clock – see Section 3.2
5. Configure the system of units to be used (U.S. or metric) – see Section 3.4
Configuration and Use Manual 3
Before You Begin
Getting Started CommunicationsSystemBefore You Begin
6. Configure the following parameters for volumetric flow measurement:
Averaging technique – see Section 6.3.1
Pressure compensation – see Section 6.3.2
Gas quality data – see Section 6.4
Pressure data for pressure compensation – see Section 6.4.1
1.5.2 Basic configuration
To perform a complete basic setup, the following tasks are required:
Start the Model 3711
Install ROCLINK 800 software
Make a direct connection to the Model 3711
Set the Model 3711 clock
Define a device configuration file for the Model 3711
Define all required devices and groups
Configure security for ROCLINK 800
Configure security for the Model 3711
Configure device information for the Model 3711
Configure the Auto Scan interval and TLP display options
Configure communications
Configure the sensor interface
Configure volumetric flow measurement
Configure I/O
Configure history
Before configuring history, review any requirements for special history setup.
1.5.3 Advanced options
The following advanced options may or may not be implemented:
Reconfigured or custom displays
The I/O monitor
PID control loops
•FSTs
Remote communications access:
- Via Modbus protocol – requires configuration of the Model 3711 Modbus interface
- Via ROC protocol – no setup required
4 Micro Motion
®
Model 3711 Gas Flow Computers
Before You Begin
1.6 Model 3711 administration overview
To administer the Model 3711 effectively, you should know why, when, and how to perform the
following tasks:
Writing to flash memory
Saving configuration to a file
Downloading configuration data to the Model 3711
Removing and restoring power to the Model 3711
Performing the different types of warm starts and cold starts
Updating user programs
Updating the Model 3711 firmware
Upgrading the Model 3711 hardware
Information on these tasks is provided in Chapter 14.
1.7 Documentation resources
Table 1-1 lists documentation resources for other required or useful information. All listed documents
are available on the Micro Motion web site.
1.8 Micro Motion customer service
For customer service, phone the support center nearest you:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
In Canada and Latin America, phone (303) 527-5200
In Asia, phone (65) 6770-8155
In the U.K., phone 0800 - 966 180 (toll-free)
Outside the U.K., phone +31 (0) 318 495 670
Table 1-1 Documentation resources
Topic Document
Model 3711 installation Micro Motion Model 3711 Gas Flow Computers: Installation Manual
Sensor installation Appropriate sensor installation manual
Core processor installation (if not installed
with sensor)
Micro Motion Model 3711 Gas Flow Computers: Installation Manual
Writing host programs using ROC protocol
TLP system
ROC Protocol User Manual
Using the Modbus host user program Modbus Host User Program Manual
Using the core processor Modbus interface Using Modbus Protocol with Micro Motion Transmitters (manual and map)
Modbus Mapping Assignments for Micro Motion Transmitters (map only)
Configuration and Use Manual 5
Getting Started CommunicationsSystemBefore You Begin
Chapter 2
Getting Started
2.1 Overview
This chapter discusses the following topics:
Starting the Model 3711
Installing ROCLINK 800
•Using ROCLINK800
Configuration files
Defining groups and devices
Connecting to the Model 3711
2.2 Starting the Model 3711
To start the Model 3711:
1. Supply power to the unit. See the installation manual for power requirements.
2. Unscrew the front cover from the Model 3711.
3. Insert the reset jumper on the face of the Model 3711 into the NORM (left and center) slots.
See Figure 2-1.
4. Insert the power jumper on the face of the Model 3711 into the ON (center and right) slots.
5. Replace the front cover. Tighten securely but do not over-tighten.
Figure 2-1 Power and reset jumpers
Reset jumper
Power jumper
6 Micro Motion
®
Model 3711 Gas Flow Computers
Getting Started
On initial power-up, all configuration parameters are set to default values. If your unit includes the
optional dial-up modem card, set it to Auto Answer before supplying power. (Auto Answer is the
default setting.)
To remove power from the unit, insert the power jumper into the OFF slots (the left and center slots).
After initial power-up, there are several ways to initialize the Model 3711. See Section 14.2.
2.3 Installing ROCLINK 800
This section describes the PC requirements for ROCLINK 800 and the ROCLINK 800 installation
procedure.
2.3.1 PC requirements for ROCLINK 800
To install and run ROCLINK 800 on a PC, the PC must meet the following minimum requirements:
Pentium-class processor (233 MHz or greater recommended)
•CD-ROM drive
Windows 98, ME, NT 4.0 (SP6), 2000 (SP2), or XP
64 MB of RAM
SVGA color monitor, 800 by 600 pixels, small fonts
15-50 MB of available hard disk space depending on operating system and revision level
EIA-232 (RS-232) serial port
2.3.2 Installing ROCLINK 800
Insert the ROCLINK 800 CD into your PC’s CD-ROM drive.
If the installation program starts automatically (AutoRun):
1. Click the
Install a ROCLINK Product button in the main menu.
2. Click the
Install ROCLINK 800 button in the installation screen.
3. Follow the instructions on the screen.
4. Once you have exited the main menu, remove the installation CD-ROM.
Note: A restart may be necessary.
If the installation program does not start automatically:
1. Click the Windows
START button.
2. Navigate to the CD-ROM drive, and select
Setup.exe. If the CD-ROM drive is drive D, the
location will be
D:\Installs\ROCLINK800_W68130\Setup.exe.
3. Click
OK in the Navigation window.
4. Click
OK in the Run window.
5. Follow the steps in the preceding installation procedure (AutoRun).
Configuration and Use Manual 7
Getting Started
Getting Started CommunicationsSystemBefore You Begin
2.4 Using ROCLINK 800
This section describes how to start ROCLINK 800, how to log into ROCLINK 800, and how to
connect from ROCLINK 800 to the Model 3711.
2.4.1 Starting ROCLINK 800
You can start ROCLINK 800 using any of the following methods:
Double-clicking the
ROCLINK 800 shortcut on the desktop
Selecting
Start > Programs > ROCLINK 800 > ROCLINK 800
Double-clicking the file ROCLINK.EXE. In typical installations, this file is located in
C:\Program Files\ROCLINK 800.
Enter your ROCLINK 800 operator ID and password, and click
OK. If you have not yet defined
ROCLINK 800 operator IDs and passwords, use the ROCLINK 800 default values:
Operator ID:
LOI
•Password:
1000
Note: This operator ID allows you to start ROCLINK 800. It does not provide access to the
Model 3711.
Note: To enter the default values (LOI and 1000) automatically, press ALT-ENTER or CTRL-ENTER
at the sign-on screen.
Note: For information on defining ROCLINK 800 operator IDs and passwords, see Section 3.3.1. For
information on defining Model 3711 operator IDs and passwords, see Section 3.3.2.
2.4.2 ROCLINK 800 user interface
Upon successful login, the Device Directory window, shown in Figure 2-2, is displayed.
Figure 2-2 Device Directory window
Device directory
Toolbar
Menu bar
Connection indicator
Direct Connect icon
Connect icon
8 Micro Motion
®
Model 3711 Gas Flow Computers
Getting Started
ROCLINK 800 uses a standard Windows interface. Use standard Windows techniques to open and
close windows and dialog boxes, expand and hide options, etc.
ROCLINK 800 windows
ROCLINK 800 windows can be maximized, minimized, or resized, using the standard Windows
controls.
In addition, the Windows menu lists all windows that are currently open, and allows you to arrange
them on the screen or bring a specific window to the top. Figure 2-3 shows ROCLINK 800 with three
windows open and cascaded.
Figure 2-3 Cascaded windows
Configuration and Use Manual 9
Getting Started
Getting Started CommunicationsSystemBefore You Begin
ROCLINK 800 buttons
Several buttons are used to manage the ROCLINK 800 interface or data exchange with the
Model 3711 component. They do not interact with the core processor component. These buttons are
found on many ROCLINK 800 windows and dialog boxes (see Figure 2-4):
OK – Closes the current window or dialog box. If there are any unsaved changes on the screen,
a popup is displayed, asking the user if the changes should be saved to the Model 3711
configuration.
Apply – Writes the configuration parameters that are currently shown on the ROCLINK 800
display to the Model 3711 configuration.
Cancel – Closes the current window or dialog box without changing any parameters, and
without displaying a confirmation popup.
Update – Updates the display from current values in the Model 3711.
Auto Scan and Stop Scan – Enables and disables the Auto Scan feature. Auto Scan
automatically updates the display from the Model 3711, at configured intervals. See
Section 3.5 for information on configuring the Auto Scan interval.
If Auto Scan is not enabled, it may be useful to click
Apply, then click Update, so that the screen
displays the results of your actions.
Figure 2-4 Common buttons
Two additional buttons – the
Write Config and Read Config buttons – manage data exchange with
the core processor component as well as the Model 3711 component:
•The
Write Config Data button writes the displayed configuration parameters to the core
processor. If you have changed a parameter in ROCLINK 800, but not written it to the
Model 3711, a popup is displayed to allow you to save the change to the Model 3711.
- If you click
Yes, the change is saved to the Model 3711, and then written to the core
processor.
- If you click
No, the change is discarded and nothing is written to the Model 3711 or the
core processor.
•The
Read Config Data button reads configuration parameters from the core processor and
updates the ROCLINK 800 display. If you have changed a parameter in ROCLINK 800 but
not written it to the Model 3711, a popup is displayed to allow you to save the change.
- If you click
Yes, the change is written to the Model 3711 and the core processor before
values are read back to the display.
- If you click
No, the change is discarded and the existing values in the core processor are
read back to the display.
These buttons appear only on the Mass Flow, Density, and Temperature panels (see Section 5.4).
Note: The core processor is the component which provides preprocessing of the sensor data. In the
Model 3711 system, ROCLINK 800 communicates with the Model 3711 component, which in turn
communicates with the core processor component, which communicates with the sensor.
10 Micro Motion
®
Model 3711 Gas Flow Computers
Getting Started
2.4.3 TLP system
Particular locations, or “points,” in Model 3711 memory are identified using a TLP system, where:
•T = Type
L = Logical number
•P = Parameter
For example, a TLP value of
AOU B3, EU represents the value, in engineering units, of the analog
output associated with point B3 in the Model 3711’s physical memory.
ROCLINK 800 uses the TLP system during configuration. When the TLP symbol (an ellipsis, or
...) is
displayed on a button, the button provides access to the Select TLP dialog box, shown in Figure 2-5.
Figure 2-5 Select TLP dialog box
TLP notation can be text, as shown here, or numeric. For example, if numeric notation is configured,
AOU B3, EU will be represented as 4 18, 6. See Section 3.5 for information on configuring TLP
notation.
To use the Select TLP dialog box:
1. Highlight the point type of the desired point.
2. Highlight the logical number of the desired point.
3. Highlight the desired parameter associated with the specified point.
See Appendix C for additional information on points and the TLP system.
Configuration and Use Manual 11
Getting Started
Getting Started CommunicationsSystemBefore You Begin
2.5 Configuration files
When using ROCLINK 800 to configure the Model 3711, two types of configuration files are
involved:
The ROCLINK 800 configuration file is specific to each installation of ROCLINK 800 on a
PC. It is created automatically, and automatically saved to a file each time that ROCLINK 800
is closed. It contains device and group definitions (see Section 2.6), and other items that are
specific to the ROCLINK 800 software, rather than to a device. No user actions are required to
create and maintain the ROCLINK 800 configuration file.
A device configuration file is a set of operating parameters that are defined in ROCLINK 800,
then applied or downloaded to the Model 3711. Multiple device configuration files may be
defined in ROCLINK 800, and stored as files on the PC; however, only one device
configuration file can be loaded into the Model 3711 at any one time. A device configuration
file must be specifically created and saved by the user.
2.5.1 Managing device configuration files
The ROCLINK 800 File menu is used to open and close device configuration files within
ROCLINK 800, and to save a device configuration file to the PC. The File menu is also used to print a
device configuration file (see Section 14.11) and to download a device configuration file into the
Model 3711 (see Section 14.10.3).
All device configuration files use the .800 extension. You can create as many device configuration
files as you need. Each device configuration file contains information describing one Model 3711,
including its interaction with the sensor, its I/O configuration, its history setup, and so on.
Note: If you use this installation of ROCLINK 800 to interact with other devices, including
non–Model 3711 devices, their device configuration files will also use the .800 extension. Be sure to
name the device configuration files so that you will be able to identify the device and device type.
Only one device configuration file can be loaded to a Model 3711. However, multiple device
configuration files can be open within ROCLINK 800 at one time. Each device configuration file
displayed in a separate Configuration Tree window. The Window menu can be used to select the
device configuration file that you want to view or use.
Saving a device configuration file to the PC is not the same as saving it to flash memory in the
Model 3711. To save a device configuration to flash memory, click
Device > Flags >
Save Configuration
. The configuration data in flash memory is used in all cold restarts, and may be
used in warm restarts. For more information on flash memory and restart options, see Section 14.2.
2.5.2 Creating a new device configuration file
You do not have to be connected to a Model 3711 to create a device configuration file. However, you
will need to be connected to a Model 3711 to configure many of the properties that are saved in a
device configuration file.
To create a new device configuration file:
1. Click
File > New.
2. In the upper left corner of the New Configuration File window, set
Configuration Type to
FB104/3711. The shown in Figure 2-6 is displayed.
12 Micro Motion
®
Model 3711 Gas Flow Computers
Getting Started
Figure 2-6 New Configuration File dialog box
3. Specify your I/O type.
If your Model 3711 was ordered without the optional 6-point I/O expansion termination
board, select
6-point no I/O.
If your Model 3711 was ordered with the optional 6-point I/O expansion termination
board, select
6-point with I/O.
4. If you specified
6-point with I/O, an External I/O frame is displayed. Use the options in this
frame to specify how five of the six I/O channels will be used (the sixth channel is always used
as a discrete output). The I/O types specified here must be compatible with the I/O wiring and
switches (see the Model 3711 installation manual for wiring instructions). You can change
these specifications later (see Section 7.3).
5. Specify the number of PID control loops that will be configured for this Model 3711. The
maximum value is 1. This value can be changed later. See Chapter 10 for more information.
6. Specify the maximum number of history points to be used for standard history and extended
history. If you add history points later, you will lose all existing history, so make sure that the
number specified will be sufficient for your Model 3711. See Chapter 8 for more information
about history.
7. Click
Start.
8. Specify a name and location to be used for the configuration file, and click
Save. All
ROCLINK 800 configuration files use the .800 extension.
9. If you want to continue with configuration, open the file when prompted. If you will perform
configuration later, close the file.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234