FläktGroup CentriFlow 3D GMMB_GPMB Marine Installation guide

Type
Installation guide
PUR (A, B, C, D)
SLIDE IN ROTOR CASSETTE
CENTRIFLOW 3D / CENTRIFLOW PLUS 3000 PLUG
FAN WITH AC MOTOR FOR MARINE
CONTENT PAGE
1. Important information ........................................................................ 2
2. Saferty notes ......................................................................................... 2
3. Technical description ........................................................................ 3
4. Transport .................................................................................................4
5. Mounting instructions ........................................................................ 6
6. Commissioning .................................................................................... 6
7. Maintenance ........................................................................................... 7
8. Faults ....................................................................................................... 9
9. Spare parts ........................................................................................9
10. Distances ............................................................................................... 9
11. Air flow measurement ..................................................................10
12. Disposal of the product ................................................................ 10
13. Declaration of conformity .............................................................11
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
CENTRIFLOW 3D / CENTRIFLOW PLUS 3000
MARINE PLUG FAN GMMB, GPMB
INSTALLATION AND MAINTENANCE
IMPORTANT INFORMATION, SAFETY NOTES
1. IMPORTANT INFORMATION
FläktGroup fans comply with the requirements for health and safety of
the EC Machinery Directive.
All fans leave the factory after being subjected to testing.
These instructions are intended for use by professional service staff.
The installation, commissioning and operation of the fans must be
carried out by professional staff who are familiar with the safety regu-
lations.
Tools and protective equipment necessary for preventing accidents
from occurring while installing and operating the fan must be used/
worn in accordance with the local safety regulations.
All personnel involved with the product must carefully study this oper-
ating manual and diligently comply with all orders and instructions.
FläktGroup does not accept responsibility for any damage that can be
attributed to non-observance of these instructions.
The warranty issued by the manufacturer will be forfeited if any changes
to the product are made without the manufacturer’s consent.
2. SAFETY NOTES
This symbol is designed to point out all safety and danger
related information regarding danger on the operating
personnel’s lives and health.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
2
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
3. TECHNICAL DESCRIPTION
The fan is used to generate a desired air volume at a given
pressure rise that corresponds to the pressure losses in the duct sys-
tem to which the fan is connected, and internal losses inside of the Air
Handling Unit.
The plug fan is intended to be used inside of the Air Handling Unit.
3.1 DESIGN
TECHNICAL DESCRIPTION
1. Front plate
2. Inlet cone
3. Impeller and hub
4. Motor
5. Base frame (sheet steel)
6. Base frame (steel profile, welded)
7. Motor bracket
8. Front plate support (GMMB size 056, GPMB all sizes)
9. Front plate support
10. Transverse support beam (not in all combinations)
11. Lifting lug (2/4 pcs depending on fan combination)
1
2
5
8
10
7
4
3
GMMB sizes 080-090.
GPMB.
1
2
9
6
7
4
3
1
2
9
6
7
4
3
1
2
8
6
11
7
4
3
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
3
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
GMMB sizes 071, motor IEC 112.
GMMB sizes 071, motor IEC 132.
TECHNICAL DESCRIPTION , TRANSPORT
4 TRANSPORT
4.1 TRANSPORT INSPECTION
Check the fan immediately after you receive it and make sure that it
has not been damaged during transport. If you discover any damage,
get in touch with the transportation company without delay. Briefly ro-
tate the fan impeller to see that it rotates easily. Check the information
on the fan rating plate.
Proper procedures must be followed when transporting the product!
Faulty conditions in transporting may result in serious damage on the
product
4.2 TRANSPORT SAFETY
The transport mode is to be selected according to the packaging and
the weight of the product. Loading must be carried out as instructed.
4.3 INTERMEDIATE STORAGE
If the fan is to be stored before or in between uses, the following
needs to be taken in account:
Original packaging is to be used. If the storage conditions require
it, additional protection may be added
The storage environment must be dry, dust-free and not have a
high level of humidity (<70%)
Storage temperature must be in between –25° C and +40° C
Before commissioning, the respective instructions must be
studied thoroughly.
3.2 OPERATING CONDITIONS
The standard operating temperature range of the fan is –20° C - +40° C /
+45 °C. The maximum permissible ambient temperature of the motors
is +40° C / +45 °C, see motor data.
If the fan is operated in conditions where the ambient temperature is
higher, the rated output will have to be reduced. See the instructions of
the motor manufacturer.
The fans are designed to be used as parts of equipment.
They are not ready for use as a stand-alone product and
the standard version does not have
protection against body contact, the appropriate
protective measures are to be taken according to
EN 292/294.
Only operate the fan up to the maximum permissible speed given in
the information on the fan rating plate.
3.3 MOTORS
Motors are IEC standard IE2 or IE3 marine classified AC motors.
The motors are equipped with a thermistor and they are designed for a
frequency converter use. Admissible environmental temperature: from
–15°C up to +40° C / +45° C, see motor data..
3.4. FREQUENCY CONVERTERS
All fans used in an Air Handling Unit in the European Union area shall
be equipped with a speed controller in accordance with the Regulation
1253/2014.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
4
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
TRANSPORT
Transverse beam must be used if needed. Beware of damaging the
fan while lifting. Always adjust chains/beams long enough not to get in
touch with motor or impeller.
4.4.2 GMMB 040-071 (motor IEC 132)
The fan is to be lifted with four lifting chains/beams, two attached to the
front plate supports and two to the motor bracket. See picture below.
4.4.3 GMMB 080
The fan is to be lifted with four lifting chains/beams, two attached to
the front plate supports and two to the motor bracket. See picture below.
Transverse beam must be used if needed. Beware of damaging the
fan while lifting. Always adjust chains/beams long enough not to get in
touch with motor or impeller.
Transverse beam must be used if needed. Beware of damaging the
fan while lifting. Always adjust chains/beams long enough not to get in
touch with motor or impeller.
4.4.4 GPMB
The fan is to be lifted with four lifting chains/beams, two attached to
the front lifting lugs and two to the motor bracket (in some fan combi-
nations there are lifting lugs in rear also).
Transverse beam must be used if needed. Beware of damaging the
fan while lifting. Always adjust chains/beams long enough not to get in
touch with motor or impeller.
4.4 LIFTING OF THE FAN
4.4.1 GMMB 071 (motor IEC 112)
The fan is to be lifted with three lifting chains/beams, one attached to
the front plate and two to the rear end of the fan. There are two alter-
native places to attach the rear lifting hooks as shown in the picture
below.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
5
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
6 COMMISSIONING
6.1 SAFETY CHECKING
Rotate the shaft and check that the impeller can move freely.
Make sure that there are no foreign objects in the fan or in the
ducting.
Also check that there is no unusual noise in the fan.
Check that the installation work has been carried out in
accordance with the relevant regulations.
All necessary protective devices must be installed.
The fan may only be commissioned after all proper procedures
have been followed and all necessary inspections have been car-
ried out.
6.2 TEST RUN
Briefly switch on the power supply to the motor to check whether the
fan impeller rotates in the correct direction. If the impeller is rotating in
the correct direction, the fan may be switched on.
Check that no abnormal mechanical sound and no surging occurs.
MOUNTING INSTRUCTIONS, COMMISSIONING
5 MOUNTING INSTRUCTIONS
5.1 INSTALLATION OF THE FAN
The fan is to be installed to a base frame using anti-vibration
mountings. Alternatively the base could be mounted on antivibration
mountings. The base must be level and stable. The fan must only be
mounted in a horizontal plane.
5.2 FITTING THE ACCESSORIES
The fan should normally be connected to the air handling unit by
means of flexible connection or other type of a gasket to eliminate vi-
bration transfer from fan to the AHU casing.
Providing necessary grounding for the accessories is within the con-
structor’s field of responsibility.
Inlet protective screen can be fitted directly to the front frame or out-
side AHU to the inlet opening.
5.3 SAFETY REGULATIONS AND CE-MARKING
The GMMB and GPMB fan is CE-marked as a Partly Completed
Machinery and must not be put into service until the final machi nery
into which it is to be incorporated has been declared in conformity
with provisions of the Machinery Directive 2006/42/EC. Other compli-
ant directives are shown in the Declaration of Conformity.
5.4 ELECTRICAL CONNECTIONS
All electrical connections must be wired by authorised personnel only.
The necessary electrical and safety precautions must be taken into
account. If the motor is operated across a frequency converter, the
connections must be made according to the instructions of the fre-
quency converter manufacturer. The motor must be grounded.
5.5 ADDITIONAL GROUNDING
The fan can be additionally grounded to the air handling unit or base.
The grounding wire (not included in the fan delivery) is recommended
to be securely attached to the motor outer grounding point whenever it
is possible or to the marked grounding spot on motor bracket (ground-
ing bolt, nut and washers included to delivery) and the other end of the
cable to the air handling unit or base.
Additional grounding on the motor bracket, spot marked by this sticker.
For GPMB-031-with IEC 132 motor: Additional grounding in the base frame.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
6
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
7. MAINTENANCE
7.1 WARRANTY
A precondition of the warranty is that regular maintenance has been
carried out. Defects under warranty must immediately be notified to
the manufacturer or the importer. The warranty does not cover service
work or indirect damages.
7.2 MAINTENANCE
7.2.1 BEFORE MAINTENANCE
Switch off the power supply to the fan at the safety switch and wait
until the impeller is fully stopped.
ENSURE THAT THE IMPELLER IS SURELY STILL BEFORE
AND DURING THE MAINTENANCE WORK.
7.2.2 INSPECTION
The fan is to be inspected at least once a year.
7.2.3 CHECKING THE MOTOR BEARINGS
The motors are meant to be operated in dry or humid air at an allowed
temperature, see motor table. The motor bearings have to be lubrica-
ted in accordance with the instructions that accompany the motor.
Bearings are to be replaced in accordance with the motor manufac-
turer’s instructions.
7.2.4 IMPELLER
The maximum permissible vibration level measured from the motor
bearing is 4.5mm/s RMS. The impeller can be cleaned by using a
vacuum cleaner, compressed air or by brushing. If the impeller is
coated with greasy dirt it can be washed with a detergent or a solvent.
The cleaning is to be done at least once a year. Badly tarnished impel-
ler will result in lower efficiency of the fan and increases energy con-
sumption.
MAINTENANCE
7.3 REPLACING THE MOTOR AND THE IMPELLER
The fan must be disconnected and taken out from the unit before the
motor can be replaced.
1. Dismantle the front plate supports (GMMB size 056 and bigger,
motor IEC 112 or smaller; GPMB all sizes) and the front plate and
inlet cone (front plate and inlet cone are permanently riveted to
each other).
or
1. Detach the triangular front plate supports (GMMB with motor IEC
132 and bigger) from the front plate (remove entirely if needed) and
remove the front plate and inlet cone (front plate and inlet cone are
permanently riveted to each other).
Clamp screw End bolt
and washer
Support
Support
2. Release the impeller from the motor shaft by loosening the clamp
screw and removing the end bolt and washer.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
7
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
MAINTENANCE
3. If needed, use an extraction tool to pull the impeller off the motor
shaft. There is a groove in the impeller hub for the extraction tool.
With bigger sizes it is recommended to support the impeller.
Size of the extraction tool needed depends on the impeller size.
Please follow the general instructions of the extraction tool care-
fully.
7. Mount the impeller on the motor shaft.
8. Mark the needed overlap to the inlet cone, see the below
illustration and table.
Fan size Overlap [mm]
GMMB GPMB
025 4.5
028 5.0
031 5.6 5.0
035 6.3 6.0
040 7.1 8.0
045 8.0 7.0
050 9.0 9.0
056 10.0 10.0
063 11.2 10.0
071 12.6 12.0
080 14.2
090 16.0
9. Mount the front plate and inlet cone (permanently riveted to each
other).
10. Mount the front plate supports (when applicable).
11. Align the impeller and check that the gap between the impeller and
the inlet cone is as equal as possible around the impeller. Also
check that the overlap is correct.
12. Tighten the motor fixing bolts, reassemble and tighten the end bolt
and washer, tighten the clamp screw.
Before installing and starting the fan, make sure that there is no me-
chanical contact between the impeller and the inlet cone.
7.4 FINAL INSPECTION
Check that:
The impeller is mounted for the correct direction of rotation.
All screws and nuts have been tightened.
No foreign objects have been left in the fan or in the ducting.
OVERLAP
4. Dismantle the old motor from the motor bracket.
5. Mount a new motor to the motor bracket, do not tighten the fixing
bolts.
6. Clean the motor shaft and the impeller hub hole. Use of lubrication
is recommended.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
8
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
8. FAULTS
If any faults occur during operation, they shall be repaired by qualified
maintenance personnel.
Some examples of incorrect use:
- foreign particles inside fan (AHU)
- corrosive media inside AHU
- too low or high temperatures
- too high vibrations
- incorrect maintenance
Possible problems generated:
- bearing damage
- corrosion damage
- vibration generated damage
- broken impeller
9. SPARE PARTS
The following spare parts are available: impeller, inlet cone (including
the front plate) and motor. Please contact FläktGroup sales unit.
FAULTS, SPARE PARTS, RECOMMENDED DISTANCE TO OTHER COMPONENTS
GMMB
Fan size W H ØD L E
025 440 540 218 410 200
028 500 600 248 460 200
031 560 660 278 540 200
035 630 730 312 610 200
040 710 810 352 680 200
045 800 900 397 770 300
050 900 1000 446 870 300
056 1000 1100 496 960 300
063 1110 1210 555 1080 300
071 1250 1350 625 1220 400
080 1410 1510 704 1370 400
090 1590 1690 793 1530 400
GPMB
Fan size W H ØD L E
031 680 780 336 570 200
035 760 860 379 640 200
040 840 940 417 710 300
045 960 1060 480 800 300
050 1070 1170 534 890 300
056 1200 1300 598 1010 300
063 1350 1450 673 1130 400
071 1520 1620 758 1270 400
L
W
H
ØD
E
L
W
H
ØD
E
10. RECOMMENDED DISTANCE TO OTHER COMPONENTS
To achieve the best possible operation of the fan inside of the Air
Handling Unit the following minimum distances shall be followed:
Please note that the base frame length or motor length may exceed
safety distance L. Please ensure min 50 mm free space behind the
motor to secure motor cooling.
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
9
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
11. AIR FLOW MEASUREMENT DEVICE
The airflow sensor is used for measuring the airflow of the plug fans.
The method is based on differential pressure. The pressure is meas-
ured at a specific point in the inlet cone and the reference pressure is
measured upstream of the inlet cone. The air flow sensor is supplied
factory mounted in the inlet cone. The air flow is calculated as a func-
tion of the coefficient k and the differential manometer reading Dp
m
from the equation:
q
v
= air flow m
3
/s
k = k-factor of each fan
Dp
m
= differential pressure reading (Pa)
qv =
1
k
pm
x
Δp
m
Fan size k-factor
GMMB GPMB
025 67.56
028 54.40
031 41.63 36.2
035 36.01 29.1
040 29.62 22.1
045 22.56 18.2
050 18.89 14.9
056 14.56 11.8
063 11.63 9.2
071 9.07 7.3
080 7.35
090 5.77
12.DISPOSAL OF THE PRODUCT
Used product shall be disposed or recycled according to the local
laws and regulations.
AIR FLOW MEASUREMENT DEVICE, DISPOSAL
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
10
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
13. DECLARATION OF CONFORMITY
EC Declaration of incorporation for Partly Completed machinery
Machinery Directive 2006/42/EC, Annex II, sub B
Manufacturer: FläktGroup Finland Oy
Address: Kalevantie 39
FI-20520 Turku, Finland
Name and address of the person authorised to compile the relevant technical documentation:
Name: Heikki Stenberg Address: as above
The design of the Partly Completed Machinery:
GMEB / GMPM /GMEC, GMMB and GPMB with accessories
Induction AC motor
Induction AC motor with VSD
Electronically commutated external rotor motor with integrated controller
Permanent magnet motor with VSD
The following essential requirements of the Machinery Directive (2006/42/EC) are applied and fulfilled:
1.1.2, 1.1.3, 1.1.5, 1.5.1
The specific technical documentation in accordance with Appendix VII B has been written and is available.
The specific documentation will be transmitted to a reasoned request by national authorities.
And that this partly completed machinery is in conformity with the provisions of the following other EC-
Directives:
2014/35/EU Low Voltage Directive
2014/30/EU EMC-Directive
2009/125/EC ErP Directive
(EU) 2017/2102 RoHS Directive
And furthermore, declares that
the following (parts/clauses of) European harmonised standards have been
applied: EN ISO 12100:2010, EN ISO 13857:2008, EN 61000-6-2:2011, EN
61000-6-3:2011 and ISO EN 5801
This partly completed machinery must not be put into service until the final machinery into which it is to be
incorporated has been declared in conformity with provisions of the Machinery Directive 2006/42/EC, where
appropriate.
Turku,1.9.2018 Heikki Stenberg
R&D Manager
CentriFlow 3D / Centriflow Plus 3000 GMMB, GPMB - Installation and Maintenance
11
FläktGroup DC_10279GB_20190304_R0
Specifications are subject to alteration without notice
FG_DC_10279GB_Centriflow GMMB, GPMB_IN-MA_190304_R0 © Copyright 2018 FläktGroup
WWW.FLAKTGROUP.FI GMMB/GPMB 10279
» Learn more on www.flaktgroup.com
or contact one of our offices
A HISTORY OF INNOVATION
AND RELIABILITY
With more than a century of accumulated industry experience, FläktGroup is
in a unique position to deliver energy efficient components and solutions for
integrated performance, reliability and quality. With modern manufacturing
technologies, precise deliveries and technical support, FläktGroup is your
partner – fulfilling and surpassing industry standards and certifications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

FläktGroup CentriFlow 3D GMMB_GPMB Marine Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI