ABB COM600 series User manual

Type
User manual

ABB COM600 series combines the functionalities of a communication gateway, automation platform, and user interface in one device. Here are some of the key capabilities of your newly purchased device:

  • Communication gateway: The COM600 can connect to various substation devices using different communication protocols, allowing seamless data exchange and interoperability. It supports protocols like IEC 61850, DNP3, IEC 60870-5-104, Modbus, and SPA.

  • Automation platform: Equipped with an IEC 61131-3 based logic processor, the COM600 enables the execution of automated sequences and the creation of control programs. It empowers you to implement substation-level automation tasks, such as load shedding or fault isolation, directly through the device.

ABB COM600 series combines the functionalities of a communication gateway, automation platform, and user interface in one device. Here are some of the key capabilities of your newly purchased device:

  • Communication gateway: The COM600 can connect to various substation devices using different communication protocols, allowing seamless data exchange and interoperability. It supports protocols like IEC 61850, DNP3, IEC 60870-5-104, Modbus, and SPA.

  • Automation platform: Equipped with an IEC 61131-3 based logic processor, the COM600 enables the execution of automated sequences and the creation of control programs. It empowers you to implement substation-level automation tasks, such as load shedding or fault isolation, directly through the device.

Station Automation COM600
Product Guide
Power Products
ABB 2
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes
no responsibility for any errors that may appear in this document.
© Copyright 2009 ABB Oy
All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3. Parameter setting . . . . . . . . . . . . . . . . . . . . . . . 5
4. Event and alarm lists .....................6
5. Disturbance record handling ...............6
6. Data historian . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Logic processor .........................8
8. Access control and substation security . . . . . . 8
9. Substation integration ....................9
10. Integration of ABB IEDs. . . . . . . . . . . . . . . . . . 9
11. Commissioning and troubleshooting . . . . . . . 9
12. Communication redundancy .............10
13. Technical data ........................11
14. Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15. Mounting ............................17
16. Ordering .............................18
17. References . . . . . . . . . . . . . . . . . . . . . . . . . . 19
ABB 3
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Issued: January 2009
Revision: B / 23 Oct 2009
1. Description
COM600, the station automation device of
ABB, is an all-in-one communication gateway,
automation platform and user interface solu-
tion for utility and industrial distribution sub-
stations. The gateway functionality provides
seamless connectivity between substation
IEDs and network-level control and manage-
ment systems. The automation platform with
its logic processor makes COM600 a flexible
implementation platform for substation-level
automation tasks. As a user interface solu-
tion COM600 accommodates web technol-
ogy based functionalities providing access to
substation devices and processes via a web
browser based human machine interface
(HMI).
The COM600 design process has been
guided by the IEC 61850 standard for com-
munication and interoperability of substa-
tion equipment. The communication gateway
functionality of COM600 supports a variety
of commonly used communication protocols
of substation devices. For even greater con-
nectivity, OPC data access and OPC alarms
and events are supported to enable informa-
tion sharing and control with, for example, a
distributed control system (DCS).
The IEC 61131-3 based logic processor can be
programmed to execute automatic sequences
directly via communications media. Further,
the logic processor enables the creation of
both simple control programs and more so-
phisticated applications like load shedding or
fault isolation and network restoration.
The COM600 hardware platform is based on
ruggedized mechanics with no moving parts
subject to wear and tear. Thus, the compact
and robust design is well adapted for harsh
environments. The preinstalled software
and the off-line configuration performed on
a separate computer contribute to a faster
project execution.
OPC Server
IEC 61850
DNP3 Slave
OPC Client
Web server
HMI application
OPC Client
REMOTE
CONTROL
Standard web-browser
Configuration tool on a PC
Connectivity packages
for ABB IEDs
and/or device profiles
On-line operation
Configuration phase, off-line
IEC 61850-8-1
REF615
REF 543
REF 542plus
Conf
SCL
Fig. 1 Station Automation COM600 overview
ABB 4
Station Automation
COM600
Product version: 3.4
1MRS756764 B
2. Application
COM600 provides gateway functions for map-
ping signals between protection and control
IEDs in industrial or utility substations and
higher-level systems. It further includes an
optional HMI that provides data and informa-
tion from the substation to the users.
COM600 gathers data from protection and
control IEDs and from process devices us-
ing different communication protocols. The
supported protocols can be combined freely
in one station computer, limited only by
the number of hardware interfaces and the
license. COM600 uses web technology to dis-
play data to different users in a professional
and user-friendly manner. The optional slave
protocols enable the transfer of information
to a network control centre (NCC) or distrib-
uted control system (DCS).
COM600 benefits from the potential of the
IEC 61850 standard by using the IEC 61850-
6 substation configuration language (SCL)
and IEC 61850 -7 communications modeling
regardless of protocol used. As the IEC 61850
data modeling is used for all communication
protocols the gateway cross-reference is done
in the same way regardless of the protocol,
for example IEC 61850-8-1 or DNP3.
COM600 can by using the optional web HMI
(requires Mozilla Firefox
®
, Opera or Microsoft
Internet Explorer with Adobe SVG viewer
3.03) be used for efficient substation visu-
alization, monitoring and control. Measured
values from process devices are displayed on
the HMI. Single-line diagrams can be used to
view any available measured values from the
process devices.
All primary single-line diagram (SLD) devices
are displayed in one screen. The SLD recog-
nizes different voltage levels and different
busbar systems such as single busbar, double
busbar and duplex systems. The four-mode
busbar coloring visualizes the busbar status.
The coloring of the busbar is user configura-
ble.
EMS/
SCADA
DMS,
OMS
REMOTE
ACCESS -
ENGINEERING
Ethernet switch
Ethernet switch
RTU/PLC
RTU/PLC
WAN
TCP/IP protocols
(DNP3, IEC 60870-5-104,
Modbus)
TCP/IP protocols
(IEC 61850, DNP3,
Modbus
®
)
Serial protocols
(DNP3, Modbus
®
,
SPA)
Serial protocols
(DNP3, IEC 60870-5-101,
Modbus)
LAN 1
GPS
RER 111
LON-bus
SPAJ 140
REM 543
REF 542plus
DPU2000R
REF615
NON-ABB
IED
NON-ABB
IED
REF615
REF 543
REF 542plus
Fig. 2 Overview of a utility substation using Station Automation COM600
ABB 5
Station Automation
COM600
Product version: 3.4
1MRS756764 B
The single line diagram can be configured
to include an indication for the local/remote
selection switch. Alarm symbols and generic
symbols can be places in the SLD to give an
even better overview of the status. In addi-
tion, generic control buttons can be added
to control objects. A separate control dialog
is used for controlling the switching device.
It provides information on switching device
identification, reservation status and inter-
locking conditions. The select-before-execute
logic is used to prevent unintended opera-
tion. By reserving the switching device for a
single user the risk of controlling the device
from two different locations is eliminated.
Further, COM600 supports the tap changer
function for the RE 500 series transformer
terminals.
Connection examples:
COM600 has by default four serial ports. The
number of serial ports can be increased using
the optional serial card. The four serial ports
enable the connection and combination of
different serial protocols. For example 3 SPA
+ 1 IEC 101 protocol or 2 SPA + 1 IEC 103 +1
IEC 101 protocol.
COM600 can as an option be equipped with
a LON-card enabling the connection of one
plastic or glass LON interface. Alternatively
the number of Ethernet interfaces can be
increased by choosing the optional Ethernet
extension card.
3. Parameter setting
The parameter setting tool (PST) is used for
viewing and/or setting parameters in IEDs
supporting transparent SPA, Modbus or
IEC 61850 parameterization. The PST enables
activation of the parameter setting function
for the chosen IEDs. In addition, it enables
that only selected parameters are shown in
REMOTE
ACCESS -
ENGINEERING
DISTRIBUTED
CONTROL
SYSTEM
Ethernet switch
Ethernet switch
RTU/PLC
RTU/PLC
WAN
OPC Client/Server
TCP/IP protocols
(IEC 61850, DNP3,
Modbus
®
)
Serial protocols
(DNP3, Modbus
®
,
SPA)
LAN 1
GPS
RER 111
LON-bus
SPAJ 140
REM 543
REF 542plus
DPU2000R
REF615
NON-ABB
IED
NON-ABB
IED
REF615
REF 543
REF 542plus
Fig. 3 Overview of an industrial system using Station Automation COM600
ABB 6
Station Automation
COM600
Product version: 3.4
1MRS756764 B
the web HMI of COM600 limiting the number
of visible parameters to the ones that are
considered important for the user. Changes in
the settings require that the user has engi-
neering or administrator rights in COM600.
4. Event and alarm lists
Events and alarms are identified by date,
time, bay, device, object description or status.
Furthermore, the events and alarms can be
automatically filtered according to voltage
level or bay criteria. Maximum memory ca-
pacity is 65535 events. First-in, first-out logic
is used for overwriting events. The user can
export an event list to a .csv file for further
analysis. COM600 supports printing of events
to an Event Printer for long time archiving.
5. Disturbance record
handling
COM600 automatically downloads distur-
bance records from the connected IEDs. The
disturbance records are saved in the stand-
ard COMTRADE format. In-depth analysis
is enabled using ABB’s Wineve software or
any other commercially available disturbance
record analyzer supporting the COMTRADE
format. Downloading of disturbance records
requires use of the IEC 61850-8-1 communi-
cation protocol.
6. Data historian
The COM600 data historian is a real-time
database designed and optimized for process
information management and extensive his-
tory recording. The data historian is based on
ABB’s cpmPlus Knowledge Manager software.
It combines the benefits of an easy-to-use
real-time database with industrial reliability,
performance, and real-time functionality to
provide an excellent platform for process
information management. The data historian
can be used for accurate process perform-
ance monitoring by following process and
equipment performance calculations with
real-time and history values. Better under-
standing of the process behaviour by join-
ing time-based process measurements with
production and maintenance events helps
Ethernet switch
RS-232/RS-485
serial links 1 - 8
link 1 link 8
LAN 1
Web HMI
LAN 2
Ethernet switch
GPS
IEDIED
Fig. 4 Application example
ABB 7
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Fig. 5 COM600 web HMI showing persisting and fleeting alarms
Fig. 6 COM600 Data historian
ABB 8
Station Automation
COM600
Product version: 3.4
1MRS756764 B
the user to understand the process dynamics.
It further provides required information for
learning how to keep the process running.
High performance and reliability, together
with maintenance-free operation, provide a
solid platform for trending. The optional data
historian functionality offers means of stor-
ing, analyzing and presenting process data.
Please note that displaying of data historian
information using the HMI requires that Mi-
crosoft Internet Explorer is used.
7. Logic processor
COM600 offers an straightforward approach
to the languages specified by the IEC 61131-3
standard for programmable logic controllers
(PLC). The programmable logic processor in
COM600 is offered as a selectable software
option. The PLC programming system ena-
bles programming and execution of auto-
mation tasks. In addition, the IEC 61131-3
programming in COM600 offers on-line and
off-line functionality for engineering and
diagnostics.
The logic process can be used for applica-
tions such as grouping of signals or tripping
of all bus breakers, if one of the breakers
fails to clear the fault. COM600 collects any
analog or binary IED data using standard
serial and TCP/IP based protocols such as
IEC 61850, DNP3 or Modbus. In the created
logic, the logic processor, use the analog and
binary data from the IEDs. The output of the
created logic can be sent to the IEDs for trip-
ping or alarm purposes.
8. Access control and
substation security
To protect COM600 from unauthorized ac-
cess and to maintain information integrity,
COM600 is provided with a four-level, role-
based authentication system with administra-
tor-programmable individual passwords for
the viewer, operator, engineer and admin-
EMS/
SCADA
ENGINEERING
Ethernet switch
RTU/PLC
RTU/PLC
WAN
TCP/IP protocols
(IEC 61850, DNP3,
Modbus
®
)
Serial protocols
(DNP3, Modbus
®
,
SPA)
LAN 1
ELECTRONIC SECURITY PERIMETER
GPS
RER 111
LON-bus
Built-in firewall
SPAJ 140
REM 543
REF 542plus
DPU2000R
REF615
NON-ABB
IED
NON-ABB
IED
REF615
REF 543
REF 542plus
Fig. 7 Substation security
ABB 9
Station Automation
COM600
Product version: 3.4
1MRS756764 B
M M M
REF615 REF615 REF615 REF615
MLink
DISTRIBUTION
CONTROL
SYSTEM
Ethernet switch
Ethernet switch Ethernet switch
GPS
PLANT TCP/IP
7.2 kV
7.2/0.4 kV
0.4 kV
OPC Client/Server
FEEDER 1FEEDER 2FEEDER 3
LOCAL
HMI
Fig. 8 Substation integration
istrator level. Further, the security features
include host-based firewalls and communi-
cation encryption using the secure HTTPS
(hypertext transfer protocol secure) protocol.
9. Substation integration
COM600 provides connectivity to a range
of ABB systems. The connectivity to ABB’s
low voltage motor control center MNS iS is
provided using an OPC server in COM600.
COM600 receives data from the MNSiS devic-
es and provides a human-machine interface
(HMI) and gateway functionality for a smooth
integration. Further, COM600 offers connec-
tivity to ABB’s Automation System 800xA and
MicroSCADA by means of OPC or other com-
munication protocols.
10. Integration of ABB
IEDs
COM600 supports ABB’s connectivity pack-
age concept which simplifies system configu-
ration and integration of IEDs. A connectivity
package is a collection of software and spe-
cific IED information, which enable system
products and tools to connect and interact
with the IED. The connectivity packages re-
duce the risk of errors in system integration,
minimizing device configuration and set-up
times. The engineering in COM600 is done by
selecting the connectivity package for the IED
version and configuration or by importing the
configuration file from the IED.
11. Commissioning and
troubleshooting
COM600 offers several tools and functions to
support efficient commissioning and trou-
ABB 10
Station Automation
COM600
Product version: 3.4
1MRS756764 B
OPC Server
IEC 61850
DNP3 Slave
OPC Client
Web server
HMI application
OPC Client
SCADA
Web HMI
REF615
REF 543
REF 542plus
Ethernet switch
TCP/IP protocols
(IEC 61850, DNP3,
Modbus
®
)
• Simulation of complete IEDs
• Source data monitoring
• Forcing of source data
• ...
• ...
Fig. 9 Commissioning and troubleshooting
bleshooting of the substation. The built-in
IED simulation functionality enables testing
and verifying of the correct operation of the
HMI and gateway configuration of COM600
without any physical connection of IEDs.
Further, communication diagnostic events can
be enabled to track all messages being sent
by or received from the IEDs.
Using the Station Automation Builder 600
(SAB600) tool provided with COM600 on-
line diagnostic data, real-time process data,
the communication channels and the control
function of the IEDs can be analyzed without
separate protocol analyzers.
12. Communication
redundancy
To maintain and improve the reliability of the
communication network and the communi-
cation between the IEDs and COM600, IEC
62439/PRP (parallel redundancy protocol)-
based communication is supported. PRP is
based on duplicated networks, where each
message is sent via both networks. The first
of the received messages is accepted whereas
the duplicate is discarded. Message replica-
tion and discarding is done by the DuoDriver
in COM600. Further, the DuoDriver hides
the two networks from upper level applica-
tions. IEC 62439/PRP-based communication
requires that COM600 is equipped with the
optional LAN card and that the IEDs used
support PRP.
In addition, COM600 supports switch fault
tolerance (SFT) provided that the optional
LAN-card and COM600 are connected to
two separate switches. SFT creates a failover
relationship between the two adapters con-
nected to separate switches. The manager
responsibility is transferred from one agent
to the other in case of a failure. The Switch
Fault Tolerance feature of the Intel network
adapter requires the Teaming Feature to be
enabled.
ABB 11
Station Automation
COM600
Product version: 3.4
1MRS756764 B
13. Technical data
Table 2. Power supply
Description Value
U
aux
nominal 110...220 V DC
100... 240 V AC (50...60 Hz)
U
aux
variation 80...120% of U
n
(88...264 V DC)
90...110% of U
n
(90...264 V AC)
Power consumption 37 W (with 264 V DC)
Power consumption at start-up 220 W
Table 1. Dimensions
Description Value
Width 214 mm (243 mm with mounting kit)
Height 122,4 mm (129.4 mm with mounting kit)
Depth 313 mm
Weight 6.8 kg
Table 3. Hardware
Description Value
Processor Intel
®
Pentium M 1.6 GHz
System memory 1 GB SDRAM
Compact flash memory 8 GB industrial SSD
Table 4. Interfaces
Description Value
Serial interfaces 3 x RS-232 interfaces
Serial interface 1 x RS-232/485 serial interface
Ethernet interfaces 2 x 10/100Base-TX RJ-45 interfaces
USB 4 x USB 2.0 interfaces
Table 5. Optional PCI extensions
Description Value
LON interface
1)
1 x 1 LON interface
Serial interfaces
2)
8 x RS-232/485 serial interfaces
Ethernet interfaces
3)
2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45 inter-
faces
1) Operating temperature 0° C - +70° C
2) Operating temperature 0° C - +55° C
3) Operating temperature 0° C - +55° C
ABB 12
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 6. Inspection of mechanical structure
Description Standard
Markings and mechanical structure According to IEC 60255-5, -6
Degree of protection by enclosure According to IEC 60529
Clearance and creepage distances According to IEC 60255-5
Table 7. Power supply and module tests
Description Standard
Auxiliary voltage According to IEC 60255-6
Aux. voltage interruptions According to IEC 60255-11
Ripple in auxiliary DC voltage According to IEC 60255-11 12%, f = 2 x fn
Power consumption According to CE EN 61010
Table 8. Insulation tests
Description Standard
Dielectric test According to IEC 60255-5
2 kV, 50 Hz for 1 minute
Impulse voltage test According to IEC 60255-5
5 kV, 1.2/50 μs, 0.5 J
Insulation resistance According to IEC 60255-5
>100 MΩ, 500 Vdc
Protective bonding impedance According to IEC 60255-27
<0.1 Ω.
Table 9. Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
Description Standard
1 MHz burst disturbance test
•Commonmode
•Differentialmode
According to IEC 61000-4-18
and IEC 60255-22-1
2.5 kV
1.0 kV
ABB 13
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Electrostatic discharge test
•Contactdischarge
•Airdischarge
According to IEC 61000-4-2,
IEC 60255-22-2
6 kV
8 kV
Radio frequency field immunity According to IEC 61000-4-3
and IEC 60255-22-3
10 V/m (80% amp.mod.)
f=80...1000 MHz
10 V/m (pulse mod.) f=900
MHz
Fast transient
•Powersupply
•RJ-45port
According to IEC 61000-4-4
and IEC 60255-22-4
2 kV
1 kV
Surge immunity
•Powersupply
According to IEC 61000-4-5
and IEC 60255-22-5
2 kV line-to-earth,
1 kV line-to-line
Conducted radio frequency disturbance According to IEC 61000-4-6
and IEC 60255-22-6
10 V (80% ampl. mod.)
f= 150 kHz...80 MHz
Power frequency (50 Hz) magnetic field According to IEC 61000-4-8,
300 A/m, continuous
Voltage dips and short interruptions According to IEC 61000-4-11
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
Emission tests According to EN 55011,
and IEC60255-25, class A
Table 10. Environmental conditions
Description Value
Operating temperature range -25...+70ºC
1) 2)
Relative humidity range, non-condensing 5...95% at +40ºC
Storage temperature -40...+70ºC
1) Without any option cards
2) With Ethernet option card: 0…+55°C, with Serial option card: 0…+55°C, with LON option card: 0…+70°C
ABB 14
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 11. Environmental tests
Description Standard
Dry heat test According to IEC 60068-2-2
Test values:
•96hat+55ºC
•4hat+70ºC
Cold test According to IEC 60068-2-1
Test values:
•96hat-10ºC
•4hat-25ºC
Damp heat test, cyclic According to IEC 60068-2-30
Test values:
•6cycles(12+12h)at
+25…55°C, humidity >93%
Storage test According to IEC 60068-2-48
Test values:
•72hat+70ºC
•72hat-40ºC
Table 12. Mechanical tests
Description Standard
Vibration tests
•Vibrationresponsetest
•Vibrationendurancetest
According to IEC 60068-2-6 and
IEC 60255-21-1
f = 10...150 Hz, ± 0.035 mm,
10…58 Hz,
5 m/s2 58…150 Hz
f = 10...150 Hz, ± 0.075 mm,
10…58 Hz, 10 m/s2 58…150
Hz
Shock and bump tests
•Shock response test
•Shock withstand test
•Bump test
According to IEC 60068-2-27 ,
IEC 60068-2-29 and IEC 60255-
21-2
peak acceleration = 5 x gn,
pulse duration = 11 ms, num-
bers of pulses in each diretion
= 3
peak acceleration = 15 x
gn, pulse duration = 11 ms,
number of pulses in each direc-
tion = 3
peak acceleration = 10 x
gn, pulse duration = 16 ms,
number of pulses in each direc-
tion = 1000
ABB 15
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 13. EMC compliance
Complies with the EMC directive 2004/108/EC
Standards EN 50263 (2000),
EN 60255-26 (2007)
EN 61000-6-2 (2005)
EN 61000-6-4 (2007)
Table 14. Product safety
Complies with the LV directive 2006/95/EC
Standards EN 60255-27 (2005),
EN 60255-6 (1994)
Table 15. RoHS compliance
Complies with the RoHS directive 2002/95/EC
Seismic test
•biaxialmulti-frequencyrandomseismictest
According to IEC 60255-21-3
test method B
2 x gn in horizontal direction, 1
x gn in vertical direction
Table 16. Communication protocols
Master protocol Slave protocol
DNP3 LAN/WAN DNP3 LAN/WAN
DNP3 serial DNP3 serial
IEC 61850-8-1 IEC 60870-5-101
IEC 60870-5-101 IEC 60870-5-104
IEC 60870-5-103 External OPC
IEC 60870-5-104 SPA router
LON – LAG Modbus serial TCP
MNS iS Connectivity
Modbus serial
Modbus TCP
SPA
ABB 16
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Table 17. IEDs with connectivity packages supporting COM600
610 series IEDs
Feeder Protection REF610
Motor Protection REM610
Voltage Protection REU610
615 series IEDs
Feeder Protection Relay REX 521
SPAJ 140 series relays
Combined Overcurrent and Earth-fault Relay SPAJ 140 C
Combined Overcurrent and Earth-fault Relay SPAJ 141 C
Combined Overcurrent and Earth-fault Relay SPAJ 142 C
Combined Phase and Neutral Overcurrent Relay SPAJ 144 C
Stabilized Differential Relay SPAD 346 C
SACO 16D series units
Digital Annunciator Unit SACO 16D1
Digital Annunciator Unit SACO 16D3
Digital Annunciator Unit SACO 64D4
RE 500 series terminals
Feeder Terminal REF 541 / 543 / 545
Transformer Terminal RET 541/ 543 / 545
Motor and Generator Terminal REM 543 / 545
Feeder Terminal REF 542plus
Table 18. Hardware requirements for SAB600
Hardware Minimum Recommended
Free hard disk space 1 Gb 1 .5Gb
Table 19. Supported operating systems
1)
Description
Microsoft Windows 2000, Windows XP Professional Edition SP2 or later, Windows 2003
Server, Vista, Vista Server 2008
1) Microsoft
®
.NET Framework 2.0 is required for running SAB600. The software is automatically installed during the
installation of SAB600 if not already available on the PC.
Table 20. Supported web browsers (Web HMI)
Description Version
Microsoft Internet Explorer
(with Adobe SVG viewer 3.03)
6.0 or later
Mozilla Firefox
®
3.0
Opera 9
ABB 17
Station Automation
COM600
Product version: 3.4
1MRS756764 B
14. Tools
Engineering of COM600 is done offline on a
separate computer using the Microsoft
®
.NET-
based SAB600 engineering tool supplied with
COM600. The configurability and functionali-
ty of COM600 depends on the communication
protocol used for communication between
COM600 and the IEDs. The connectivity pack-
ages for ABB’s protection and control IEDs
enable an efficient configuration of COM600.
The connectivity packages include descrip-
tions of the data and signals available in the
IEDs. The descriptions are used to automati-
cally configure the master communication of
COM600.
At project engineering SAB600 uses the
potential of the IEC 61850 standard by sup-
porting the IEC 61850 based SCL (Substation
Configuration Description Language) file
import, including the import of the communi-
cation and graphical parts of the SCL-file. The
finalized projects are updated from SAB600
to COM600 at site or remotely provided that a
secure Ethernet connection is available.
Table 21. Tools
Description Version
Station Automation Builder 600 3.4
15. Mounting
The COM600 computer is designed for
mounting into a control panel by using the
Fig. 10 Top view Fig. 11 Side view
included wall-mount kit. The COM600 is
fastened using the four holes on the unit and
four screws.
ABB 18
Station Automation
COM600
Product version: 3.4
1MRS756764 B
16. Ordering
The type and serial number label identifies
the COM600 units. The order number con-
sists of a string of code generated from the
hardware and software modules of the unit.
Use the ordering key information in Fig. 12 to
generate the order number when ordering.
C O M 6 0 0 H R H 3 2 P B
# DESCRIPTION
1 Power supply
110 - 220 V DC, 100 - 240 V AC H
2 Optional communication cards (PCI)
LON card, PCLTA-20, plastic fi bre, 1 port P
LON card, PCLTA-20, glass fi bre, 1 port G
Ethernet card (RJ-45) 10Base-T, 100Base-TX,
1000Base-T, 2 ports
R
Serial RS-232/RS-485 card, 8 ports S
None N
3 HMI
Web HMI H
None N
4 Master protocols
One master protocol 1
Two master protocols 2
Three master protocols 3
5 Slave protocols
One slave protocol 1
Two slave protocols 2
None N
6 Optional software
Data historian
1)
T
Logic processor L
Data historian and Logic processor
1)
P
None N
7 Version
Version 3.4 B
1)
Requires Web HMI and Internet Explorer 6.0 or later
Fig. 12 Ordering key for Station Automation COM600
ABB 19
Station Automation
COM600
Product version: 3.4
1MRS756764 B
17. References
The www.abb.com/substationautomation por-
tal offers you information about the distribu-
tion automation product and service range.
You will find the latest relevant information
on the COM600 unit on the product page.
The download area on the right hand side
of the web page contains the latest product
documentation, such as user’s guide, opera-
tor’s guide, etc. The selection tool on the web
page helps you find the documents by the
document category and language. The Fea-
tures and Application tabs contain product
related information in a compact format.
Example code: C O M 6 0 0 H R H 3 2 P B
Y
our ordering code:
Digit (#) 1 2 3 4 5 6 7
Code:
C O M 6 0 0
     
Fig. 13 Your ordering code
Fig. 14 Product page
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
Fax +358 10 22 41094
www.abb.com/substationautomation
ABB Inc.
Distribution Automation
655 Century Point
Lake Mary, Florida, U.S.A.
Phone 407-732-2000
Fax 407-732-2335
www.abb.com/substationautomation
1MRS756764 B © Copyright 2009 ABB. All rights reserved.
Contact us
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

ABB COM600 series User manual

Type
User manual

ABB COM600 series combines the functionalities of a communication gateway, automation platform, and user interface in one device. Here are some of the key capabilities of your newly purchased device:

  • Communication gateway: The COM600 can connect to various substation devices using different communication protocols, allowing seamless data exchange and interoperability. It supports protocols like IEC 61850, DNP3, IEC 60870-5-104, Modbus, and SPA.

  • Automation platform: Equipped with an IEC 61131-3 based logic processor, the COM600 enables the execution of automated sequences and the creation of control programs. It empowers you to implement substation-level automation tasks, such as load shedding or fault isolation, directly through the device.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI