ABB COM600 series is an all-in-one communication gateway, automation platform and user interface solution for utility and industrial distribution substations. It seamlessly connects substation IEDs and network-level control and management systems. Its IEC 61131-3 based logic processor can be programmed to execute automatic sequences directly via communications media. It supports various communication protocols, including IEC 61850, DNP3, and IEC 60870-5-101/104. It provides a web-based HMI for data and information visualization, single-line diagrams, and control.

ABB COM600 series is an all-in-one communication gateway, automation platform and user interface solution for utility and industrial distribution substations. It seamlessly connects substation IEDs and network-level control and management systems. Its IEC 61131-3 based logic processor can be programmed to execute automatic sequences directly via communications media. It supports various communication protocols, including IEC 61850, DNP3, and IEC 60870-5-101/104. It provides a web-based HMI for data and information visualization, single-line diagrams, and control.

Grid Automation Controller COM600
Product Guide
Power Products
ABB 2
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes
no responsibility for any errors that may appear in this document.
© Copyright 2012 ABB
All rights reserved.
Trademarks
ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Contents
1. Description ............................3
2. Application ............................4
3. Parameter setting .......................5
4. Event and alarm lists .....................6
5. Disturbance and fault record handling .......6
6. Data historian .........................6
7. GOOSE analyzer ........................8
8. Logic processor ........................9
9. Access control and substation security ......9
10. Substation integration ...................9
11. Integration of ABB IEDs ................11
12. Commissioning and troubleshooting ......11
13. Communication .......................12
14. Communication redundancy ............12
15. Smart Grid ...........................13
16. Technical data ........................14
17. Tools ...............................20
18. Mounting ............................21
19. Selection and ordering .................22
20. References ..........................24
21. Document revision history ...............25
ABB 3
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Issued: 2012-05-31
Revision: D
1. Description
COM600, the grid automation controller
of ABB, is an all-in-one communication
gateway, automation platform and user
interface solution for utility and industrial
distribution substations. The gateway
functionality provides seamless connectivity
between substation IEDs and network-
level control and management systems. The
automation platform with its logic processor
makes COM600 a flexible implementation
platform for substation-level automation
tasks. As a user interface solution COM600
accommodates web technology based
functionalities providing access to substation
devices and processes via a web browser
based human machine interface (HMI).
The COM600 design process has been
guided by the IEC61850 standard for com-
munication and interoperability of substa-
tion equipment. The communication gateway
functionality of COM600 supports a variety
of commonly used communication protocols
of substation devices. For even greater con-
nectivity, OPC data access and OPC alarms
and events are supported to enable informa-
tion sharing and control with, for example, a
distributed control system (DCS).
The IEC 61131-3 based logic processor can be
programmed to execute automatic sequences
directly via communications media. Further,
the logic processor enables the creation of
both simple control programs and more so-
phisticated applications like load shedding or
fault isolation and network restoration.
The COM600 hardware platform is based on
ruggedized mechanics with no moving parts
subject to wear and tear. Thus, the compact
and robust design is well adapted for harsh
environments. The preinstalled software
and the off-line configuration performed on
a separate computer contribute to a faster
project execution.
OPC Server
IEC 61850
DNP3 Slave
OPC Client
Web server
HMI application
IEC 61163-3
OPC Client
REMOTE
CONTROL
Standard web-browser
Configuration tool on a PC
Connectivity packages
for ABB IEDs
and/or device profiles
On-line operation
Configuration phase, off-line
IEC 61850-8-1
REF615REF630
REF 543
REF611
Conf
SCL
Fig. 1 Grid Automation Controller COM600 overview
ABB 4
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
2. Application
COM600 provides gateway functions for map-
ping signals between protection and control
IEDs in industrial or utility substations and
higher-level systems. It further includes
an optional HMI that provides data and
information from the substation to the users.
COM600 gathers data from protection and
control IEDs and from process devices
using different communication protocols.
The supported protocols can be combined
freely in one station computer, limited only
by the number of hardware interfaces and
the license. COM600 uses web technology
to display data to different users in a
professional and user-friendly manner. The
optional slave protocols enable the transfer
of information to a network control centre
(NCC) or distributed control system (DCS).
COM600 benefits from the potential of the
IEC61850 standard by using the IEC61850-
6 substation configuration language (SCL)
and IEC61850 -7 communications modeling
regardless of protocol used. As the IEC61850
data modeling is used for all communication
protocols the gateway cross-reference is done
in the same way regardless of the protocol,
for example IEC61850-8-1 or DNP3.
COM600 can by using the optional web HMI
(requires Mozilla Firefox
®
, Opera, Google
Chrome or Microsoft Internet Explorer (IE)
with Adobe SVG viewer 3.03, if IE 9.0 or later
is in use Adobe SVG viewer is not needed)
be used for efficient substation visualization,
monitoring and control. Measured values
from process devices are displayed on the
HMI. Single-line diagrams can be used to
view any available measured values from the
process devices.
All primary single-line diagram (SLD)
devices are displayed in one screen. The
SLD recognizes different voltage levels and
different busbar systems such as single
busbar, double busbar and duplex systems.
The four-mode busbar coloring visualizes the
busbar status. The coloring of the busbar is
user configurable.
EMS/
SCADA
DMS
Ethernet switch
M2M
Gateway
TCP/IP protocols
(DNP3 or IEC 60870-5-104)
TCP/IP protocols
(DNP3 or IEC 60870-5-104)
TCP/IP protocols
(IEC 61850)
TCP/IP protocols
(DNP3 or IEC 60870-5-104)
Serial protocols
(DNP3 or IEC 60870-5-101)
LAN 1
REF615 RIO600REF615 RER620 RER620
RER601 RER601
REF611
Fig. 2 Overview of a utility substation using Grid Automation Controller COM600
ABB 5
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
The single line diagram can be configured
to include an indication for the local/remote
selection switch. Alarm symbols and generic
symbols can be placed in the SLD to give
an even better overview of the status. In
addition, generic control buttons can be
added to control objects. A separate control
dialog is used for controlling the switching
device. It provides information on switching
device identification, reservation status and
interlocking conditions. The select-before-
execute logic is used to prevent unintended
operation. By reserving the switching device
for a single user the risk of controlling
the device from two different locations is
eliminated. Further, COM600 supports the tap
changer function.
Connection examples:
COM600 has by default four serial ports. The
number of serial ports can be increased using
the optional serial card. The four serial ports
enable the connection and combination of
different serial protocols. For example 3 SPA
+ 1 IEC 101 protocol or 2 SPA + 1 IEC 103 +1
IEC 101 protocol.
COM600 can be equipped with an optional
Ethernet interface. The number of Ethernet
interfaces can be increased by choosing the
optional Ethernet extension card.
3. Parameter setting
The parameter setting tool (PST) is used for
viewing and/or setting parameters in IEDs
supporting transparent SPA, Modbus or
IEC61850 parameterization. The PST enables
activation of the parameter setting function
for the chosen IEDs. In addition, it enables
that only selected parameters are shown in
the web HMI of COM600 limiting the number
of visible parameters to the ones that are con-
sidered important for the user. Changes in the
settings require that the user has engineering
or administrator rights in COM600.
REF615 REF615REF615PLC PLCPLC
Ethernet switchEthernet switch
OPC Server
OPC Client / Server
LOCAL
HMI
Electrical
SCADA
DISTRIBUTION
CONTROL
SYSTEM
Fig. 3 Overview of an industrial system using Grid Automation Controller COM600
ABB 6
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
4. Event and alarm lists
Events and alarms are identified by date,
time, bay, device, object description and
status. Furthermore, the events and alarms
can be automatically filtered according to
voltage level or bay criteria. By default 50 MB
of disk space is reserved for events storage.
The storage enables recording up to ca.
500 000 events. The amount of disk space
reserved for the events can be configured by
the user. First-in, first-out logic is used for
overwriting events. The user can export an
event list to a .csv file for further analysis.
COM600 supports printing of events to an
Event Printer for long time archiving.
5. Disturbance and fault
record handling
COM600 automatically downloads distur-
bance records from the connected IEDs. The
disturbance records are saved in the stand-
ard COMTRADE format. In-depth analysis
is enabled using WaveWin ABB software or
any other commercially available disturbance
record analyzer supporting the COMTRADE
format. Downloading of disturbance records
requires use of the IEC61850-8-1 communi-
cation protocol.
COM600 including the optional HMI
functionality supports the viewing of fault
records from the 611 and 615 series IEDs.
The records enable the user to analyze recent
power system events. Each record includes
current, voltage and angle values, etc. The
fault records are marked with consecutive
fault numbers and time stamps indicating
when the faults were detected.
6. Data historian
The COM600 data historian is a real-time
database designed and optimized for process
information management and extensive
history recording. The data historian is
based on ABB’s cpmPlus Knowledge
Manager software. It combines the benefits
of an easy-to-use real-time database
with industrial reliability, performance,
and real-time functionality to provide an
excellent platform for process information
management. The data historian can be used
for accurate process performance monitoring
Ethernet switch
RS-232/RS-485
serial links 1 - 8
link 1 link 8
LAN 1
Web HMI
LAN 2
Ethernet switch
GPS
IEDIED
Fig. 4 Application example
ABB 7
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Fig. 5 COM600 web HMI showing persisting and fleeting alarms
Fig. 6 COM600 Data historian
ABB 8
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
by following process and equipment
performance calculations with real-time and
history values. Better understanding of the
process behaviour by joining time-based
process measurements with production
and maintenance events helps the user
to understand the process dynamics. It
further provides required information for
learning how to keep the process running.
High performance and reliability, together
with maintenance-free operation, provide
a solid platform for trending. The optional
data historian functionality offers means of
storing, analyzing and presenting process
data.
7. GOOSE analyzer
The COM600 GOOSE Analyzer Tool (GAT)
is a professional system-level tool for
monitoring and analyzing GOOSE signals
in an IEC61850 station bus. Analyzing of
GOOSE signals is based on used System
Configuration Description file (SCD).
GAT supports commissioning, operation,
maintenance and upgrade phases of the
system.
GAT consists of a server and a Web-based
HMI (Web HMI). The server incorporates
GOOSE Connection Viewer and GOOSE
Test Manager functionalities. The GOOSE
Connection Viewer presents graphically
GOOSE signal flow from publishers to sub-
scribers on a content page. The Connection
Viewer enables real-time diagnosis of the
GOOSE signal flow presenting the status
of communication between different
network devices, eg. IEDs, COM600 and
the Remote I/O device RIO600. Further, the
viewer provides fast and reliable approach
Fig. 7 GOOSE Connection Viewer
ABB 9
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
to establish a holistic view of all network
devices utilizing GOOSE and the status of the
communication between them. The viewer
also provides a continuous list of latest
sent values and real-time events. Query of
historical events is also supported.
8. Logic processor
COM600 offers straightforward approach to
the languages specified by the IEC 61131-3
standard for programmable logic controllers
(PLC). The programmable logic processor in
COM600 is offered as a selectable software
option. The PLC programming system
enables programming and execution of
automation tasks. In addition, the IEC 61131-
3 programming in COM600 offers on-line
and off-line functionality for engineering and
diagnostics.
The logic processor is suitable for post-
processing of data from the IEDs and for
programmable control of outputs of the
IEDs. Any analog or binary data, collected
from the IEDs, can be processed in the logic
program. The result of the established logic
can be displayed in the HMI and sent as a
command to an IED or to a remote control
center utilizing one of the slave protocols of
COM600.
COM600 offers a framework for sequence
control. The framework includes HMI
functions for controlling and monitoring
sequence execution and a logic processor
library for creating the sequence logic. With
the help of sequences the operator can run
control sequences that will operate multiple
switching devices, e.g. circuit breakers,
sequentially to a certain state.
9. Access control and
substation security
To protect COM600 from unauthorized
access and to maintain information integrity,
COM600 is provided with a four-level,
role-based authentication system with
administrator-programmable individual
passwords for the viewer, operator, engineer
and administrator level. Further, the security
features include host-based firewalls and
communication encryption using the secure
HTTPS (hypertext transfer protocol secure)
protocol.
10. Substation
integration
COM600 provides connectivity to a range
of ABB systems. The connectivity to ABB’s
low voltage motor control center MNS iS is
provided using an OPC server in COM600.
COM600 receives data from the MNSiS
devices and provides a human-machine
interface (HMI) and gateway functionality for
a smooth integration. Further, COM600 offers
connectivity to ABB’s Automation System
800xA and MicroSCADA by means of OPC or
other communication protocols.
ABB 10
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
M M M
REF615 REF615 REF615 REF615
MLink
DISTRIBUTION
CONTROL
SYSTEM
Ethernet switch
Ethernet switch Ethernet switch
GPS
PLANT TCP/IP
7.2 kV
7.2/0.4 kV
0.4 kV
OPC Client/Server
FEEDER 1 FEEDER 2 FEEDER 3
LOCAL
HMI
Fig. 9 Substation integration
EMS/
SCADA
ENGINEERING
Ethernet switch
WAN
LAN 1
ELECTRONIC SECURITY PERIMETER
Built-in firewall
REF 542plus
REF615REF615REF615
REF615
REF630REF611
Fig. 8 Substation security and secured Web HMI for remote access
ABB 11
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
OPC Server
IEC 61850
DNP3 Slave
OPC Client
Web server
HMI application
IEC 61131-3
OPC Client
SCADA
REF630
Web HMI
REF615
REF 543
REF611
Ethernet switch
TCP/IP protocols
(IEC 61850, DNP3,
Modbus
®
)
• Simulation of complete IEDs
• Source data monitoring
• Forcing of source data
• GOOSE Analyzer
• ...
• ...
Fig. 10 Commissioning and troubleshooting
11. Integration of ABB
IEDs
COM600 supports ABB’s connectivity
package concept which simplifies system
configuration and integration of IEDs. A
connectivity package is a collection of
software and specific IED information, which
enable system products and tools to connect
and interact with the IED. The connectivity
packages reduce the risk of errors in system
integration, minimizing device configuration
and set-up times. The engineering in COM600
is done by selecting the connectivity package
for the IED version and configuration or by
importing the configuration file from the IED.
12. Commissioning and
troubleshooting
COM600 offers several tools and functions
to support efficient commissioning and
troubleshooting of the substation. The built-in
IED simulation functionality enables testing
and verifying of the correct operation of the
HMI and gateway configuration of COM600
without any physical connection of IEDs.
Further, communication diagnostic events can
be enabled to track all messages being sent
by or received from the IEDs.
Using the Station Automation Builder
SAB600 provided with COM600 on-line
diagnostic data, real-time process data, the
communication channels and the control
function of the IEDs can be analyzed without
separate protocol analyzers.
ABB 12
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
13. Communication
COM600 is designed to support the
IEC61850 standard, and can thereby
conveniently be integrated in IEC61850
systems. Using the IEC61850-8-1 GOOSE
profile COM600 supports GOOSE messaging
between the IEC61850 compliant IEDs and
the Station Automation device COM600.
Further, COM600 supports GOOSE
messaging between several COM600 devices
in the system. Apart from IEC61850,
COM600 supports a wide range of master
communication protocols. This enables
the connection of both IEC61850 devices
and other devices which are not IEC61850
compliant to the system. For example,
native IEC61850 protection and control
IEDs can be connected to COM600 using
the IEC61850 protocol while meters can be
connected to COM600 using the Modbus
protocol.
Due to the vast amount of by data generated
by modern IEC61850 compliant devices
it may in some cases be necessary to limit
the amount of information presented to
the SCADA-system (Supervisory Control
And Data Acquisition) or DCS (Distributed
Control System) to avoid unnecessary
information overflow. This is achieved by
using the cross-reference tool of COM600
when mapping information to slave
protocols. Reducing information to higher-
level systems not only reduces load but also
increases security as it is possible to, for
example, disable control to a certain system.
COM600 can be configured as an IEC61850
proxy server enabling the connection of
non IEC61850 compliant devices to then
system. COM600 converts the incoming
data according to the IEC61850 protocol.
The IEC61850 proxy server of COM600
is thereby very useful during for example
extensions.
In addition, COM600 offers OPC client and
server connectivity. This enables data access
and data sharing between the non-electrical
system and the electrical system supporting
OPC.
14. Communication
redundancy
To maintain and improve the reliability of the
communication network and the communi-
cation between the IEDs and COM600, IEC
62439/PRP (parallel redundancy protocol)-
based communication is supported. PRP is
based on duplicated networks, where each
message is sent via both networks. The first
of the received messages is accepted whereas
the duplicate is discarded. Message replica-
tion and discarding is done by the DuoDriver
in COM600. Further, the DuoDriver hides
the two networks from upper level applica-
tions. IEC 62439/PRP-based communication
requires that COM600 is equipped with the
optional LAN card and that the IEDs used
support PRP.
In addition, COM600 supports switch fault
tolerance (SFT) provided that the optional
LAN-card and COM600 are connected to
two separate switches. SFT creates a failover
relationship between the two adapters con-
nected to separate switches. The manager
responsibility is transferred from one agent
to the other in case of a failure. The Switch
Fault Tolerance feature of the Intel network
adapter requires the Teaming Feature to be
enabled.
ABB 13
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
15. Smart Grid
COM600 can be ordered with a fault detec-
tion, fault isolation and load restoration
(FDIR) function suitable for radial distri-
bution networks. The FDIR function gath-
ers data from protection and control IEDs
installed in the radial distribution networks
and substations and automatically runs
a fault detection, fault isolation and load
restoration (FDIR) algorithm using the Logic
Processor of COM600. The FDIR function
continuously updates the network status
by receiving switch status and load signals
from the IEDs.
When a fault occurs in the network, the FDIR
function locates the fault based on switch
open and trip information received from the
IED of the affected feeder. Further, the FDIR
analyzes the network and if the fault is found,
the FDIR function isolates the fault from the
network. When the fault is isolated the FDRIR
function tries to restore supply to the healthy
part of the network without overloading the
switches or power sources. After the fault has
been cleared and the return to normal com-
mand has been given the FDIR function sends
commands to the IEDs to restore the network
to the normal pre-fault condition.
Recloser
GridShield
Recloser
GridShield
Recloser
GridShield
Recloser
GridShield
Pole mounted switch
disconnector
Pole mounted switch
disconnector
Recloser
GridShield
COM600
RER620
RER620
RER620
RER620
RER620
(NC)
(NO)
(NC)
(NC)
(NC)
(NC)
Load Load
Load Load
Load
Load
(NC)
RER620
RER620
REF615
REF615
Communication
RER620RER620
Fig. 11 Fault detection, fault isolation and load restoration in radial distribution networks
(NC = normally closed, NO = normally open)
ABB 14
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 2. Power supply
Description Value (Power supply “H”)
U
aux
nominal 110...220 V DC
100... 240 V AC
(50...60 Hz)
U
aux
variation 80...120% of U
n
(88...264 V DC)
90...110% of U
n
(90...264 V AC)
Power consumption Typical 32 W (with 110 V DC) ), max. 55 W (with 110 V
DC)
Power consumption at start-up 220 W
Table 1. Dimensions
Description Value
Width 251.2 mm (284 mm with mounting kit)
Height 103 mm (114 mm with mounting kit)
Depth 313 mm
Weight 7.7 kg
Table 3. Hardware
Description Value
Processor Core 2 Duo 2.26 Ghz ( P8400)
System memory 4 GB RAM
Compact flash memory 16GB Industrial Compact Flash
Real Time Clock Battery Lithium battery
Table 4. Interfaces
Description Value
Serial interfaces 3 x RS-232 interfaces
Serial interface 1 x RS-232/485 serial interface
Ethernet interfaces 2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45
interfaces
USB 4 x USB 2.0 interfaces
16. Technical data
ABB 15
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 5. Optional PCI extensions
Description Value
Serial interfaces
1)
8 x RS-232/485 serial interfaces
Ethernet interfaces
2)
2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45
interfaces
1) Operating temperature 0° C - +55° C
2) Operating temperature 0° C - +55° C
Table 6. Inspection of mechanical structure
Description Reference
Markings and mechanical structure According to IEC 60255-1, -5
Degree of protection by enclosure According to IEC 60529
Clearance and creepage distances According to IEC 60255-5
Table 7. Power supply and module tests
Description Reference
Auxiliary voltage According to IEC 60255-1
Aux. voltage interruptions According to IEC 60255-11
Ripple in auxiliary DC voltage According to IEC 60255-11 15%, f = 2 x fn
Power consumption According to CE EN 61010
Table 8. Insulation tests
Description Reference
Dielectric test According to IEC 60255-5
2 kV, 50 Hz for 1 minute
Impulse voltage test According to IEC 60255-5
5 kV, 1.2/50 μs, 0.5 J
Insulation resistance According to IEC 60255-5
>100 MΩ, 500 Vdc
Protective bonding impedance According to IEC 60255-27
<0.1 Ω.
ABB 16
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 9. Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
Description Reference
1 MHz and 100 kHz burst disturbance test
•Commonmode
•Differentialmode
According to IEC 61000-4-18
and IEC 60255-22-1
2.5 kV
1.0 kV
Electrostatic discharge test
•Contactdischarge
•Airdischarge
According to IEC 61000-4-2,
IEC 60255-22-2
6 kV
8 kV
Radio frequency field immunity According to IEC 61000-4-3
and IEC 60255-22-3
10 V/m (80% amp.mod.)
f=80...2700 MHz
10 V/m (pulse mod.) f=900
MHz
Fast transient
•Powersupply
•RJ-45port
According to IEC 61000-4-4
and IEC 60255-22-4
2 kV
1 kV
Surge immunity
•Powersupply
According to IEC 61000-4-5
and IEC 60255-22-5
2 kV line-to-earth,
1 kV line-to-line
Conducted radio frequency disturbance According to IEC 61000-4-6
and IEC 60255-22-6
10 V (80% ampl. mod.)
f= 150 kHz...80 MHz
Power frequency (50 Hz) magnetic field According to IEC 61000-4-8,
300 A/m, continuous
Voltage dips and short interruptions According to IEC 61000-4-11
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
Emission tests According to EN 55011,
and IEC60255-25, class A
Table 10. Environmental conditions
Description Value
Operating temperature range -25...+70ºC
1) 2)
Relative humidity range, non-condensing 5...95% at +40ºC
Storage temperature -40...+70ºC
1) Without any option cards
2) With Ethernet option card: 0…+55°C, with Serial option card: 0…+55°C
ABB 17
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 11. Environmental tests
Description Reference
Dry heat test According to IEC 60068-2-2
Test values:
•96hat+55ºC
•4hat+70ºC
Cold test According to IEC 60068-2-1
Test values:
•96hat-10ºC
•4hat-25ºC
Damp heat test, cyclic According to IEC 60068-2-30
Test values:
•6cycles(12+12h)at
+25…55°C, humidity >93%
Storage test According to IEC 60068-2-48
Test values:
•72hat+70ºC
•72hat-40ºC
Table 12. Mechanical tests
Description Reference
Vibration tests
•Vibrationresponsetest
•Vibrationendurancetest
According to IEC 60068-2-6 and
IEC 60255-21-1
f = 10...150 Hz, ± 0.035 mm,
10…58 Hz,
5 m/s2 58…150 Hz
f = 10...150 Hz, ± 0.075 mm,
10…58 Hz, 10 m/s2 58…150
Hz
Shock and bump tests
•Shock response test
•Shock withstand test
•Bump test
According to IEC 60068-2-27 ,
IEC 60068-2-29 and IEC 60255-
21-2
peak acceleration = 5 x gn,
pulse duration = 11 ms,
numbers of pulses in each
diretion = 3
peak acceleration = 15 x
gn, pulse duration = 11 ms,
number of pulses in each
direction = 3
peak acceleration = 10 x
gn, pulse duration = 16 ms,
number of pulses in each
direction = 1000
ABB 18
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 13. EMC compliance
Description Reference
Complies with the EMC directive 2004/108/EC
Standards EN 50263 (1999),
EN 60255-26 (2008)
EN 61000-6-2 (2005)
EN 61000-6-4 (2007)
Table 14. Product safety
Description Reference
Complies with the LV directive 2006/95/EC
Standards EN 60255-27 (2005),
EN 60255-1 (2009)
UL recognized component for USA and Canada UL-file number E 231775
Table 15. RoHS compliance
Description Reference
Complies with the RoHS directive 2002/95/EC
Seismic test
•biaxialmulti-frequencyrandomseismictest
According to IEC 60255-21-3
test method B
2 x gn in horizontal direction,
1 x gn in vertical direction
Table 16. Communication protocols
Master protocol Slave protocol
DNP3 LAN/WAN DNP3 LAN/WAN
DNP3 serial DNP3 serial
IEC 61850-8-1
IEC 60870-5-101 IEC 60870-5-101
IEC 60870-5-103
IEC 60870-5-104 IEC 60870-5-104
IEC 61850-8-1 (MMS & GOOSE) IEC 61850-8-1 (MMS & GOOSE)
MNS iS Connectivity
Modbus Serial Modbus Serial
Modbus TCP Modbus TCP
SNMP (
Simple Network Management Protocol
)
SNTP (Simple Network Time Protocol) SNTP
SPA SPA Router
ABB 19
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 17. IEDs with connectivity packages supporting COM600 (applies for the
IEC61850 and SPA protocols)
610 series IEDs
Feeder Protection REF610
Motor Protection REM610
Voltage Protection REU610
611 series IEDs
615 series IEDs
Recloser Protection and Control RER620
Feeder Protection Relay REX 521
SPAJ 140 series relays
Combined Overcurrent and Earth-fault Relay SPAJ 140 C
Combined Overcurrent and Earth-fault Relay SPAJ 141 C
Combined Overcurrent and Earth-fault Relay SPAJ 142 C
Combined Phase and Neutral Overcurrent Relay SPAJ 144 C
Stabilized Differential Relay SPAD 346 C
SACO 16D series units
Digital Annunciator Unit SACO 16D1
Digital Annunciator Unit SACO 16D3
Digital Annunciator Unit SACO 64D4
RE 500 series terminals
Feeder Terminal REF 541 / 543 / 545
Transformer Terminal RET 541/ 543 / 545
Motor and Generator Terminal REM 543 / 545
Feeder Terminal REF 542plus
Table 18. Hardware requirements for SAB600
Hardware Minimum Recommended
Free hard disk space 1 Gb 1 .5Gb
Table 19. Supported operating systems
1)
Description
Microsoft Windows 2000, Windows XP Professional Edition SP2 or later, Windows 2003
Server, Vista, Vista Server 2008, Windows 7
1) Microsoft
®
.NET Framework 3.5 is required for running SAB600. The software is automatically installed during the
installation of SAB600 if not already available on the PC.
ABB 20
Grid Automation Controller
COM600
Product version: 4.0
1MRS756764 D
Table 21. Tools
Description Version
Station Automation Builder SAB600 4.0
17. Tools
Engineering of COM600 is done offline on
a separate computer using the Microsoft
®
.NET-based SAB600 engineering tool sup-
plied with COM600. The configurability and
functionality of COM600 depends on the
communication protocol used for communi-
cation between COM600 and the IEDs. The
connectivity packages for ABB’s protection
and control IEDs enable an efficient configu-
ration of COM600. The connectivity packages
include descriptions of the data and signals
available in the IEDs. The descriptions are
used to automatically configure the master
communication of COM600.
At project engineering SAB600 uses the
potential of the IEC61850 standard by sup-
porting the IEC61850 based SCL (Substation
Configuration Description Language) file
import, including the import of the communi-
cation and graphical parts of the SCL-file. The
finalized projects are updated from SAB600
to COM600 at site or remotely provided that a
secure Ethernet connection is available.
Table 20. Supported web browsers (Web HMI)
Description Version
Microsoft Internet Explorer
(with Adobe SVG viewer 3.03)
1)
6.0 or later
Mozilla Firefox
®
3.0
Opera 9
Google Crome 17.x
1) If IE 9.0 or later is in use Adobe SVG viewer is not needed
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

ABB COM600 series User manual

Type
User manual

ABB COM600 series is an all-in-one communication gateway, automation platform and user interface solution for utility and industrial distribution substations. It seamlessly connects substation IEDs and network-level control and management systems. Its IEC 61131-3 based logic processor can be programmed to execute automatic sequences directly via communications media. It supports various communication protocols, including IEC 61850, DNP3, and IEC 60870-5-101/104. It provides a web-based HMI for data and information visualization, single-line diagrams, and control.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI