Eaton Magnefix MD4 User manual

  • Hello! I am an AI chatbot trained to assist you with the Eaton Magnefix MD4 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MV switchgear
Magnefix MD4
User manual 991.184 G01 03
User manual
Medium-voltage switchgear
Magnefix MD4
991.184 G01 03
Eaton Industries (Netherlands) B.V.
P.O. Box 23, 7550 AA Hengelo, The Netherlands
tel: +31 74 246 91 11
fax: +31 74 246 44 44
Internet: www.eaton.eu
in the event of a malfunction
Eaton Electrical Solutions & Services: tel: +31 74 246 68 88
Installation, connection, operation, checking, commissioning, decommissioning and maintenance of
Magnefix MD4 medium-voltage switchgear should only be carried out by suitably qualified personnel.
2
991.184 G01 03
Magnefix MD4
991.184 G01 03
3
CONTENTS
1. INTRODUCTION ..................................................................................... 7
1.1 General system description .................................................................................. 7
1.2 Using the user manual .......................................................................................... 7
1.2.1 Target group ........................................................................................................... 7
1.2.2 Structure of the user manual ................................................................................... 7
1.3 Safety regulations ................................................................................................. 8
1.3.1 General instructions ................................................................................................ 8
1.3.2 Switch room safety .................................................................................................. 8
1.3.3 Notation guide ......................................................................................................... 9
1.3.4 What to do in the event of a fire............................................................................... 9
1.4 Product information .............................................................................................. 9
1.4.1 The type plate ......................................................................................................... 9
2. SYSTEM DESCRIPTION ....................................................................... 11
2.1 The switchgear .................................................................................................... 11
2.1.1 Type of switchgear ................................................................................................ 11
2.1.2 Configuration of switchgear ................................................................................... 11
2.1.3 The cable panel .................................................................................................... 11
2.1.4 The branch-circuit panel ........................................................................................ 11
2.1.5 The fuse panel ...................................................................................................... 12
2.1.6 The protected panel .............................................................................................. 12
2.1.7 The busbar connecting panel ................................................................................ 12
2.1.8 Switching on and off .............................................................................................. 12
2.1.9 The indicators ....................................................................................................... 13
2.1.10 Earthing ................................................................................................................ 13
2.2 Switchgear safety ................................................................................................ 13
2.2.1 Switchgear operation ............................................................................................ 13
2.2.2 Safety features ...................................................................................................... 14
2.2.3 Use of safety features ........................................................................................... 14
2.2.4 Carrying out work .................................................................................................. 14
2.2.5 Safety markings .................................................................................................... 14
2.3 General technical data ........................................................................................ 15
2.3.1 Electrical data ....................................................................................................... 15
2.3.2 Dimensions and weights ....................................................................................... 16
2.3.3 SEG protection relay ............................................................................................. 18
2.3.4 Heat, radiation, noise and gases ........................................................................... 18
3. SETTING UP THE SYSTEM .................................................................. 19
3.1 Introduction ......................................................................................................... 19
3.1.1 Transport .............................................................................................................. 19
3.1.2 Environmental requirements .................................................................................. 19
3.2 General ................................................................................................................ 19
3.2.1 During operation ................................................................................................... 19
3.2.2 Ventilation ............................................................................................................. 20
3.2.3 During transport and storage ................................................................................. 20
3.2.4 Floor ..................................................................................................................... 21
3.2.5 Ceiling .................................................................................................................. 21
3.3 Assembling the upright frame ............................................................................ 22
Magnefix MD4
4
991.184 G01 03
3.3.1 Parts list of upright frame ...................................................................................... 22
3.3.2 Additional parts for upright frame for systems with Protected panel ....................... 22
3.3.3 Assembling the frame legs .................................................................................... 23
3.3.4 Fixing the front C-sections..................................................................................... 23
3.3.5 Fit the C-sectionsto the frame ............................................................................... 23
3.3.6 Fitting the earth bar to the frame ........................................................................... 23
3.3.7 Fitting the branch earth bar ................................................................................... 24
3.3.8 Fitting the cross coupling ...................................................................................... 24
3.3.9 Fitting the second frame leg .................................................................................. 24
3.3.10 Fitting the earth strip ............................................................................................. 24
3.3.11 Position the switchgear on the frame ..................................................................... 25
3.3.12 Fitting the dust cap ................................................................................................ 25
3.3.13 Fit the C-section to the front of the frame (systems with Protected panel only) ...... 26
3.3.14 Checks.................................................................................................................. 26
3.3.15 Spare panels ......................................................................................................... 26
3.4 Assembling the wall frame ................................................................................. 27
3.4.1 Parts list for the wall frame .................................................................................... 27
3.4.2 Additional parts for upright frame for systems with Protected panel ....................... 27
3.4.3 Assembling the wall frame .................................................................................... 28
3.4.4 Fixing the front C sections ..................................................................................... 28
3.4.5 Fixing the C-sections and earth bar to the frame ................................................... 28
3.4.6 Fixing the branch earth bar ................................................................................... 28
3.4.7 Preparing fixed section .......................................................................................... 29
3.4.8 Fitting the frame .................................................................................................... 29
3.4.9 Fitting the installation to the wall ........................................................................... 29
3.4.10 Fixing the earth strip ............................................................................................. 30
3.4.11 Fitting the dust cap ................................................................................................ 30
3.4.12 Fitting the C-section in lower station (systems with Protected panel only) .............. 30
3.4.13 Checks.................................................................................................................. 30
3.4.14 Spare panels ......................................................................................................... 30
3.5 Connecting the cables, general .......................................................................... 31
3.5.1 Cable connection points ........................................................................................ 31
3.5.2 Fixing the cables ................................................................................................... 31
3.5.3 Fixing the cable cores ........................................................................................... 32
3.5.4 Cable boxes for paper-insulated lead-covered cables (PILC) ................................. 33
3.5.5 Cable boxes for plastic-insulated cables (XLPE).................................................... 34
3.5.6 Cable boxes to non-standard specification ............................................................ 34
3.6 Connecting the paper-insulated lead-covered cables (GPLK) .......................... 35
3.6.1 PILC with copper core up to 3 x 70 mm
2
, universal clamps ................................... 35
3.6.2 PILC with copper cores, 3 x 95 mm
2
up to 3 x 150 mm
2
, concentric clamps .......... 39
3.6.3 PILC with copper or aluminium cores up to 3 x 240 mm
2
, gland entry .................... 44
3.6.4 PILC with copper or aluminium cores up to 3 x 240 mm
2
, with plastic entry bushing47
3.7 Filling the cable box for paper-insulated, lead-covered cables ........................ 51
3.7.1 Materials required ................................................................................................. 51
3.7.2 Procedure ............................................................................................................. 51
3.8 Connection of plastic-insulated cables to C(able) and T(ransformer) panels .. 55
3.8.1 Plastic-insulated cable with copper core up to 3 X 70 mm
2
, universal clamps ........ 55
3.8.2 Connection of plastic-insulated cables with copper cores, 3 x 95 mm
2
up to 3 x
240 mm
2
, concentric clamps .................................................................................. 58
3.8.3 Plastic-insulated cable in a top connection ............................................................ 62
3.8.4 Connecting cables 95 mm
2
and over using alternative materials ............................ 63
3.8.5 Connecting Eaton 16 mm
2
transformer cable to the protected branch of the universal
clamps .................................................................................................................. 64
Magnefix MD4
991.184 G01 03
5
3.9 Connection of plastic-insulated cables to Protected panels ............................ 67
3.9.1 Plastic-insulated cable with copper core up to 3 x 70 mm
2
..................................... 67
3.9.2 Connection of plastic-insulated cables with copper cores, 3 x 95 mm
2
up to 3 x
240 mm
2
............................................................................................................... 71
4. SYSTEM OPERATION .......................................................................... 75
4.1 Safe switching ..................................................................................................... 75
4.1.1 Switching on safely ............................................................................................... 75
4.1.2 Switching off safely ............................................................................................... 75
4.1.3 Safe earthing ........................................................................................................ 75
4.2 Switching ............................................................................................................. 76
4.2.1 Switching on ......................................................................................................... 76
4.2.2 Switching off ......................................................................................................... 79
4.3 Changing a fuse .................................................................................................. 80
4.4 Resetting an overcurrent indicator .................................................................... 81
4.4.1 Electromechanical overcurrent indicator ................................................................ 81
4.4.2 Electronic overcurrent indicator ............................................................................. 81
4.5 Protective relay operation .................................................................................. 81
4.6 Voltage indication ............................................................................................... 82
4.6.1 Voltage indication.................................................................................................. 83
4.6.2 Systemdeadindication ....................................................................................... 83
4.6.3 Phase sequence indicator ..................................................................................... 84
4.6.4 Demonstrate phases are in line ............................................................................. 85
4.7 Earthing ............................................................................................................... 86
4.7.1 Equipment............................................................................................................. 86
4.7.2 Earthing a cable using single-pole slow earthing ................................................... 87
4.7.3 Earthing a cable using three-pole high-speed earthing .......................................... 88
4.7.4 Removing three-pole high-speed earthing ............................................................. 90
4.7.5 Earthing a transformer .......................................................................................... 91
4.7.6 Earthing a protected panel .................................................................................... 92
4.8 Measuring, testing and phase sequence testing ............................................... 94
4.8.1 Measuring ............................................................................................................. 94
4.8.2 Testing .................................................................................................................. 94
4.8.3 Phase sequence testing ........................................................................................ 95
5. SYSTEM COMMISSIONING AND DECOMMISSIONING ..................... 96
5.1 Commissioning ................................................................................................... 96
5.1.1 Acceptance testing ................................................................................................ 96
5.1.2 Inspections ........................................................................................................... 96
5.1.3 Handover .............................................................................................................. 96
5.2 Decommissioning ............................................................................................... 96
5.2.1 Dismantling ........................................................................................................... 96
5.2.2 Procedure ............................................................................................................. 97
5.2.3 Disposal ................................................................................................................ 97
6. INSPECTION, MAINTENANCE AND REPAIR OF THE SYSTEM ........ 98
6.1 Logbook............................................................................................................... 98
6.2 Inspection and maintenance, general ................................................................ 98
6.2.1 Types of maintenance ........................................................................................... 98
6.2.2 Frequency ............................................................................................................. 98
6.2.3 Tools ..................................................................................................................... 99
Magnefix MD4
6
991.184 G01 03
6.3 Cleaning .............................................................................................................. 99
6.3.1 Switchgear has been isolated ................................................................................ 99
6.4 Inspection and maintenance schedule............................................................. 100
6.4.1 Periodic checks ................................................................................................... 100
6.4.2 Periodic check of protected panel ........................................................................ 100
6.4.3 Maintenance ....................................................................................................... 100
6.5 Topping up grease-filled cable boxes for paper-insulated lead-covered cables101
6.6 Fault diagnosis .................................................................................................. 102
6.6.1 What to do in the event of a fault ......................................................................... 102
7. ACCESSORIES ................................................................................... 103
7.1 Spare parts ........................................................................................................ 103
7.2 Accessories ....................................................................................................... 105
8. GLOSSARY ......................................................................................... 106
8.1 Safety and personnel qualification................................................................... 106
8.2 Abnormal Operating conditions ....................................................................... 107
8.3 Equipment and the area surrounding it ........................................................... 107
9. APPENDIX ........................................................................................... 108
9.1 Appendix - Electrical Diagram .......................................................................... 108
9.2 Appendix - Floor plan ....................................................................................... 109
Magnefix MD4
991.184 G01 03
7
1. INTRODUCTION
1.1 General system description
Magnefix switchgear is intended for building compact
switchgear and distribution systems in a medium-voltage
system. This switchgear can be used:
in compact transformer substations in a ring cable
system, decentralised transformer arrangements,
customer connections;
for feeding large buildings;
on the storeys of buildings;
in railway signalling and protection systems.
In distribution panels, Magnefix switchgear is used as cable
disconnector, busbar disconnector and tie circuit breaker.
Magnefix switchgear with a protected panel is used for
protected connections of additional ring cable connectors in
distributions networks and for protected connections of
distribution transformers having powers exceeding
1000 kVA.
1.2 Using the user manual
1.2.1 Target group
The switchgear is designed for use by personnel who are
expert or adequately trained in using switchgear and/or
carrying out electrical operations.
For definitions of these terms, see Chapter 8 Glossary.
1.2.2 Structure of the user manual
The manual contains 9 chapters.
Chapters 1 and 2 contain general information on the
system (design and construction) and the manual, and
general safety aspects. The information is presented in the
form of descriptive texts, supported by illustrations as
necessary. Illustrations are numbered consecutively for
each chapter, and are captioned if necessary.
Chapters 3 to 7 consist mainly of procedures. These
procedures contain step-by-step descriptions of actions in
the order in which they should be carried out. Illustrations
are on the same page as the relevant step and have the
same number.
WARNING
Never take any action without knowing what effect
it will have.
REMARK
Read through all actions first, using the relevant
figures. Contact Eaton if you do not understand
what you have to do.
Further information regarding chapters 3 to 7 is given
below.
Chapter 3 Switchgear set-up
The manual assumes that the switchgear is being
assembled and connected by the user . It also describes
the requirements for the switchroom. This chapter also
includes the procedures for connecting cables.
Chapter 4 Switchgear set-up
This chapter is aimed at the operator who is expected to
operate and monitor the system independently. For that
reason, these activities are described in detail.
Switchgear commissioning and decommissioning
Chapter 5.1 sets out the actions required before the system
can be commissioned.
Chapter 5.2 deals with decommissioning the system. It also
includes recommendations for the safe disposal of the
system or parts of the system.
Chapter 6 - Inspection, maintenance and repair of
the switchgear
This chapter describes only those operations that may be
carried out by the user.
NOTE
Operations not included in the manual must be
carried out by or under the supervision of Eaton.
Magnefix MD4
8
991.184 G01 03
Chapter 7 - Accessories
This chapter gives a summary of available accessories and
spare parts.
Chapters 8 and 9 are explanatory chapters of a general
nature.
Chapter 8 - Glossary
This chapter contains clarifications of specific terms used in
the manual but not explained further.
Chapter 9 Appendix
This chapter contains the appendices.
1.3 Safety regulations
NOTE
Read this user manual carefully before
commissioning the switchgear. Make sure that you
have read and understood all safety instructions
and warnings.
1.3.1 General instructions
Read this user manual carefully before commissioning the
switchgear. Make sure that you have read and understood
all safety instructions and warnings.
Personnel
The user must make sure that personnel are qualified to
carry out the task.
Safety of bystanders
Access to the equipment is to be limited to those directly
involved in operating or maintaining it.
Safety plan
It may be necessary to draw up a safety plan.
Comprehensive advice on this should be obtained from the
relevant authorities (fire brigade, local authorities,
occupational health & safety, company safety department,
first aid service etc.).
Safety standards
Magnefix switchgear without protected panel complies with
the following standards:
IEC 62271-103:
High voltage switches for rated voltages
above 1 kV and less than 52 kV;
IEC 60282:
High voltage fuses;
IEC 62271-105:
High voltage switch-fuse combinations for
rated voltages above 1 kV up to and
including 52 kV.
IEC 62271-1:
Common specifications for high voltage
switchgear and controlgear standard.
IEC 60529:
Degrees of protection provided by
enclosures (IP Code);
IEC 62271-201:
A.C. insulation-enclosed switchgear and
controlgear for rated voltages above 1 kV
and up to and including 52 kV, protection
grade PB1;
Magnefix switchgear with protected panel additionally
complies with the following standards:
IEC 62271-100:
High-voltage alternating-current circuit-
breakers (relevante delen);
IEC 61000:
Electromagnetic compatibility (EMC).
Magnefix switchgear can be used in areas under normal
conditions as described in IEC 62271-1, Chapter 2.1.
1.3.2 Switch room safety
The installation and the switchroom must comply with all
local safety regulations in force.
The switchroom is the room in which the switchgear has
been set up and must meet at least the following
requirements:
Clear space
To the front and rear of the switchgear, and between two
installations sited opposite each other, enough space must
be allowed over the entire length of the installation to allow
operations to be carried out.
Magnefix MD4
991.184 G01 03
9
Escape routes
To the front and rear of the installation and between two
installations sited opposite each other, an escape route at
least 0.5 m wide and 2 m high must be present over the
entire length. The width of the escape route is measured
from the part of the installation which projects furthest. The
escape route must be completely clear and as far as
possible in a straight line.
REMARK
The installation may be set up with the back against a
wall. In that case there will be no clear area or escape
route at the rear.
Entrances
Entrances to the switchroom and escape routes must be
kept clear at all times.
Storage of materials
Items not connected with the installation must not be stored
in the switchroom. Flammable materials, combustible
gases and hazardous chemicals must not be stored.
Availability of extinguishers
Suitable extinguishers must be present in and around the
switchroom. Obtain expert advice (fire brigade) on the best
choice and location of the extinguishers.
1.3.3 Notation guide
This manual uses warning boxes to alert the user to
possible dangers while operating or maintaining the
equipment:
WARNING
Personal (fatal) danger to personnel and
bystanders.
CAUTION
Danger of damage to equipment.
NOTE
Important note for clarification.
REMARK
Useful advice.
1.3.4 What to do in the event of a fire
In the event of a fire in the switchroom, proceed as follows:
Evacuate all personnel from the switchroom.
Call the fire brigade.
Notify specialists who can switch off the installation
completely, i.e. including:
incoming cables;
low-voltage cables;
feedback from the low-voltage side;
any other power sources.
Follow local fire instructions.
WARNING
NEVER ATTEMPT TO EXTINGUISH THE
INSTALLATION BEFORE IT IS COMPLETELY
DEAD.
NEVER extinguish with a water jet.
Make sure that no water flows into the
installation.
Keep well clear of the switchgear while the fire
is being extinguished in the area around
it.
Even when using non-conducting extinguishing
materials, a voltage may pass through the
extinguishing equipment.
Extinguishing:
If possible, leave extinguishing the fire to the fire
brigade.
Use non-conducting extinguishing materials.
If necessary, use extinguishers in the area around the
installation. Never attempt to extinguish the installation
itself, even if it appears to be dead.
1.4 Product information
The main system specifications are indicated on the type
plates. Further information is available from the information
pack which includes this manual.
1.4.1 The type plate
A complete type plate is made up of a main type plate with
supplementary type plates as required. The main type plate
is headed with the Eaton logo and address.
Magnefix MD4
10
991.184 G01 03
type plate (main section) of the fixed part (example)
supplementary type plate (most commonly used) on vacuum circuit-breaker (example)
Variable
Description
unit
(English)
(English)
system
-
-
rel.
release
-
IEC
-
-
serial.no.
Serial number
-
year of constr.
year of construction
-
w.o.no.
work order number
-
U
r
rated voltage
kV
f
r
rated frequency
Hz
I
r
rated normal current
A
I
r
T-off
rated normal current
A
switch/circuitbreaker
I
k
rated short time withstand voltage
kA
t
k
rated duration of short-circuit
s
I
p
rated peak withstand current
kA
U
p
rated lightning impulse withstand voltage (peak value)
kV
peak
U
d
rated power frequency withstand voltage
kV
peak
I
ma
rated short-circuit making current
kA
I
sc
rated short-circuit breaking current
kA
I
c
rated cable charging breaking current
A
Magnefix MD4
991.184 G01 03
11
2. SYSTEM DESCRIPTION
2.1 The switchgear
2.1.1 Type of switchgear
Magnefix is a fully enclosed type of switchgear.. The use of
quartz-powder-filled epoxy resin allows a very compact
configuration.
Magnefix MD4 switchgear is easy to install on site.
Magnefix switchgear offers high operational reliability, even
under adverse operating conditions. Magnefix switchgear is
shock-resistant, tropicalised and safe to touch because of
its double insulation.
2.1.2 Configuration of switchgear
Magnefix switchgear is a modular system built up of
standard panels. The basic modules (basic panels) are:
The cable panel, with bottom or top connection for
feeder cables;
The branch-circuit panel (usually combined with a fuse
or protected panel)
The fuse panel;
The protected panel;
The busbar connecting panel.
The switch panels (cable panel and branch-circuit panel)
are provided with single-pole switch caps; each phase
having one switch cap. A switch cap may be fitted with an
indicator for continuous overcurrents.
An outgoing cable can be connected to the fuse panel (for
example, for connection to a transformer).
Three single core plastic cables having a maximum 240
mm
2
cross section may be connected to the protected
panel.
There are also modules for special uses, such as:
The busbar connecting panel;
The busbar connection for a cable;
The connecting panel (for example, for connection to
an Eaton high-voltage Capitole or SVS busbar
system);
The separate fuse panel (not connected to the
busbars, but having connection facilities for incoming
and outgoing cables).
The assembled modules are mounted in an upright or wall-
mounted frame. The modules can be assembled in any
sequence; a set of screw rods holds them together. Rubber
sleeves are used to ensure that no spark voltages can
develop at the connections between the panels.
The sides are provided with plastic plates, the top being
fitted with a dust cover. These facilities protect the
switchgear against dust, dirt and water drops.
Silver-plated tubular conductors act as busbars; they
create the electrically conductive connections between the
panels. The busbars are situated completely inside the
epoxy resin insulation.
Configuration
Magnefix switchgear comes in two configurations:
Switchgear built up of conventionally cast epoxy resin
insulated modules. These modules have a flat well-
finished outside surface.
Switchgear featuring pressure gelated epoxy resin
insulated modules. The outside of these modules has
a glossy appearance. From a functional point of view
there is no difference between the two configurations.
2.1.3 The cable panel
The cable panel has a three-phase connection point for the
cable (three round pins each measuring 12 mm). Fitted on
the cable panel are three switch caps on which the
connection between the cable and busbar can be seen to
be made or broken.
2.1.4 The branch-circuit panel
The branch-circuit panel is similar to the cable panel, but it
has no three-phase connection point for the cable. The
branch-circuit panel links the fuse or protected panel to the
busbar system. Fitted on the branch-circuit panel are three
switch caps on which the connection between the fuse or
protected panel and busbar can be seen to be made or
broken.
Magnefix MD4
12
991.184 G01 03
2.1.5 The fuse panel
The fuse panel has a three-phase cable-connection point
and three fuse holders with removable caps. A mechanical
interlock ensures that the fuses cannot be replaced until
the switch caps of the branch-circuit panel have been
removed.
The connection contacts on the transformer side of the
fuse holder are deep in the holder so they cannot be
accidentally touched.
2.1.6 The protected panel
The protected panel has a three-phase cable-connection
point, a three-phase vacuum circuit-breaker with
autonomous switch-off function and a mimic diagram.
Using a vacuum circuit-breaker combined with the
protection relay enables overloads, short-circuits and
earthing fault currents to be switched off.
A mechanical lock ensures that the vacuum circuit-breaker
can only be switched on manually when the circuit is dead,
after the switch caps of the branch-circuit panel have been
removed
2.1.7 The busbar connecting panel
The purpose of the busbar connecting panel is to enable
two busbar systems to be connected. The connecting
panel is generally supplied without switch caps.
A connecting panel is used in redundant switchgear.
2.1.8 Switching on and off
REMARK
The following is a description of the switchgear.
For the procedures refer to Chapter 4.
Switching is achieved by fitting or removing switch caps. Be
sure to use a springing handle when performing this
operation. The switch caps ensure a double interruption of
each phase.
The fixed switch contacts are fitted to the busbar and the
cable connection point. They have replaceable arcing
chambers and arcing contacts. The 'on' switch cap is
secured by a strong permanent magnet (hence the name:
Magnefix).
The mobile switch contacts are housed in the switch caps.
They have arcing contacts and internal tripping and contact
force springs.
A ferromagnetic steel plate, to which the permanent
magnet can attach, is also fitted between the mobile
contacts. Fitted to the outside of the cast-resin insulated
member of the switch is a spring-mounted cam.
Switching on the switch caps
To switch on, put a switch cap on the springing handle.
Next, push the switch cap against the cam using the
switching handle. Push the springing handle to compress
its closing spring.
As soon as the force on the switch is more than the
resistance of the cam, the cap is pushed over the cam by
the action of the closing spring in the handle. Now the
switch contacts close: the main contacts first, followed by
the arcing contacts.
When switched on, the magnet and ferromagnetic plate
keep the switch caps in position. Next, remove the
springing handle from the switch cap.
Switching on a protected panel
To enable the panel to be switched on, first remove the
corresponding switch caps by pulling them out using the
springing handle. Next, manually switch on the three
phases of the vacuum circuit-breaker. Now the switch caps
are replaced one at a time.
The protected panel has a position indicator for checking
purposes
Incorrect switching operations are avoided thanks to the
use of mechanical interlocks.
Switching off the switch caps
To switch off, put the springing handle on the switch cap.
Next, pull off the cap. The main contacts are released first.
Simultaneously, the opening springs are tensioned, but the
magnet holds the arcing contacts closed. Pull with more
force to release the ferromagnetic plate. The opening
springs pull the arcing contacts out of the arcing chambers
at high speed.
Switching off a protected panel
A protected panel can be switched off as follows:
automatically by the autonomous switching off
mechanism;
manually by activating the switch-off push button.
Incorrect switching operations are avoided thanks to the
presence of a key interlock.
Magnefix MD4
991.184 G01 03
13
2.1.9 The indicators
The overcurrent indicator.
The switch caps may have an overcurrent indicator at the
front.
Working either electromechanically or electronically, the
overcurrent indicator is fitted under the protection cap of
the switch cap.
REMARK
Fitted with an electronic overcurrent indicator, the
switch cap is 21 mm higher than a switch cap with
an electromechanical overcurrent indicator.
There is a small window in the protection cap.
If the current passing the switch cap exceeds a preset
value, a red flag is displayed in the window. As soon as the
overcurrent situation ceases to exist, the electromechanical
overcurrent indicator can be reset using a magnet.
The electronic version has a self-resetting function.
The position indicator
The protected panel has a position indicator at the front (in
the panel diagram). This position indicator operates
mechanically.
If the position indicator is black, the vacuum circuit-breaker
is switched on.
If the position indicator is white, the vacuum circuit-breaker
is switched off.
2.1.10 Earthing
General
Magnefix switchgear can be earthed via the cable and the
transformer. It is not possible to earth the busbar system.
Cable earthing
The earthing system for the cable consists of a set of three
earthing caps fitted where the switch caps are located, in
the cable panel to be earthed.
Transformer earthing
The earthing system for the transformer consists of a set of
three earthing pins fitted in the corresponding fuse panel.
The earthing caps or pins are connected to the earthing
point of the switchgear using a bolted connection and
special earthing cables.
Earthing of the protected panel
The earthing system for the protected panel consists of a
set of three earthing caps fitted where the switch caps are
located, in the corresponding branch-circuit panel. In order
to start with the standard earthing procedure, the vacuum
circuit-breaker must be switched on and interlocked using a
key.
2.2 Switchgear safety
This paragraph contains a description of the safety
provisions on the Magnefix switchgear and directions on
how to deal with them.
2.2.1 Switchgear operation
Competence
The equipment must only be operated by skilled personnel
and specialist operators.
Actions not described in this manual.
Operating or maintenance actions not described in this
manual may be required:
Actions which are specific to your installation are
described in the operating instructions supplied with it.
See information pack which includes this manual.
Actions which are not described at all may only be
carried out in consultation with an Eaton specialist.
The instructions of this specialist must be followed
exactly.
Special safety measures
In general it will not be necessary to take special safety
precautions when operating the switchgear. It is advisable,
however, to wear suitable ear protection for repeated
switching.
When carrying out work, please observe the following:
Cover open switches (on panels completely or partly
switched off) with protective covers. A protective cover
must be fitted immediately after switching off and it
must not be removed again until just before switching
on.
Always protect cable connection points that are not
used with a dummy cable box.
Magnefix MD4
14
991.184 G01 03
2.2.2 Safety features
The switchgear is provided with the following safety
features:
All-round insulation protecting against touching live
parts.
Mechanical interlocks prohibiting faulty switching
operations.
Visible isolation between busbar and cable (the switch
caps have been visibly removed).
Facilities for earthing cables and transformers.
2.2.3 Use of safety features
Keep the insulation (i.e. the outside of the switchgear)
in a perfectly clean and dry condition.
Replace mechanical interlocks as quickly as possible
if they do not perform optimally.
Cover switched-off cast-resin insulated members that
may still be live, and put-up a warning notice.
Keep earthing caps and earthing cables in perfect
condition. Make sure that the earthing points on the
upright or wall-mounted frame are free from corrosion
and oxidation, and that they are conductively
connected to earth.
2.2.4 Carrying out work
WARNING
ALWAYS check that the equipment is dead.
Fit suitable earthing.
NEVER approach an unearthed installation.
Always work on dead installations.
Ensure maintenance work is carried out in good time, in
accordance with the instructions in this manual.
Replace worn and/or damaged parts only with genuine
Eaton spare parts, or spare parts approved by Eaton.
Take the following minimum precautions when carrying out
work:
Working on live or partly live installation:
Eaton advises, for the necessary safety, never to work
on live or partly live installations. This is described in
NEN 3840 Operation of electrical installations - High
Voltage, Chapter 6.2.
Working on a dead installation:
After switching off a panel, IMMEDIATELY fit a set of
covers to the open switches or fuse holders.
ALWAYS check that the equipment is dead.
Fit earthing; work on earthed panels only.
When performing measurements check that the
vacuum circuit-breaker is switched on and interlocked.
When re-commissioning
Check that all work in the immediate area has been
completed.
Check (if appropriate) that all related work in other
areas has been completed.
Verify the safety of all persons involved.
Remove safety earthing and other safety features.
2.2.5 Safety markings
Fitted to the front of the dust hood placed over the
switchgear is a sign displaying:
PLACE CAP SLOWLY AGAINST STOP
THEN PUSH ON ENERGETICALLY
The following signs indicate possible dangers:
Dangerous electrical voltage.
Electrical safety earth.
Magnefix MD4
991.184 G01 03
15
2.3 General technical data
This section contains general technical data only. For details concerning your own system, please refer to the information pack
supplied with it, which includes this manual.
2.3.1 Electrical data
Rated values:
Voltage
kV
3.6
7.2
12
Impulse withstand voltage
kV
40/46
60/70
75/85
Power frequency withstand voltage
kV
10/12
20/23
28/32
Frequency
Hz
50/60
50/60
50/60
Busbar system
Normal current
A
400
400
400
Short-time withstand current (1s)
kA
14.4
14.4
14.4
Peak withstand current
kA
31
31
31
Single-pole load-break switches
Normal current
A
400
400
400
Breaking current (cos = 0.7)
A
400
400
400
Short-circuit making current
kA
31
31
31
Short-time withstand current (1s)
kA
14.4
14.4
14.4
Capacitive earth fault current
A
240
240
240
Cable charging current
A
25
25
25
No-load transformer breaking current
kVA
1250
1250
1250
Fuses
Normal current
A
57.7
57.7
57.7
Voltage
kV
10/12
10/12
10/12
Dimensions according to DIN43625
Vacuum circuit-breaker
Type
NVX124A-1204
Normal current
A
400
400
400
Short-time withstand current (1s)
kA
14.4
14.4
14.4
Short-circuit breaking current
kA
14.4
14.4
14.4
Direct current component
%
20
20
20
Making current
1)
A
*
*
*
1)
There is no making current when switching on. The vacuum circuit-breaker can only be switched on
when the circuit is dead.
Magnefix MD4
16
991.184 G01 03
2.3.2 Dimensions and weights
Dimensions upright version
Panel name width weight
Cable panel (including switch caps) 91 mm 15 kg
Busbar connection 91 mm 7.5 kg
Connecting panel 91 mm 4.5 kg
Busbar connecting panel (sectional panel including switch caps) 182 mm 19.5 kg
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm 61.5 kg
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
230 mm 37.5 kg
Busbar connecting panel with SVS or HC switchgear 91 mm 9 kg
Height 1517 mm
Depth with fuse panel 517 mm
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator) 423 mm
Depth with protected panel (including earthing interlock) 570 mm (+ 27)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where: K: number of cable panels
T: number of protected branches
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
rd
support point) or maximum weight: 240 kg.
Magnefix MD4
991.184 G01 03
17
Dimensions wall-mounted version
Panel name widths weight
Cable panel (including switch caps) 91 mm 15 kg
Busbar connection 91 mm 7.5 kg
Connecting panel 91 mm 4.5 kg
Busbar connecting panel (sectional panel including switch caps) 182 mm 19.5 kg
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm 61.5 kg
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
230 mm 37.5 kg
Busbar connecting panel with SVS or HC switchgear 91 mm 9 kg
Height (overall height) 1487 mm
Depth with fuse panel 517 mm
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator) 465 mm
Depth with protected panel (including earthing interlock) 605 mm (+ 27)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where: K: number of cable panels
T: number of protected branches
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
rd
support point) or maximum weight: 240 kg
Magnefix MD4
18
991.184 G01 03
2.3.3 SEG protection relay
The protection relay is fitted in a separate secondary
compartment under the switching mechanism for the
protected panel. This protection relay comes with a
separate manual. This manual is part of the information
pack.
Refer to Chapter 9 for electrical diagram.
The secondary compartment consists of the following:
metal cover (11);
protection relay (10);
electric trip indicator (9).
Protection relay and trip indicator.
2.3.4 Heat, radiation, noise and gases
Heat
In general, it can be said that the heat generated in full-
load service will lead to a maximum temperature rise of the
outer surface not exceeding the body temperature.
Radiation
Radiation is well below the safety standard level.
Noise
In general it can be stated that the switchgear does not
generate any noise under operating conditions apart from
switching operations. The noise during switching
operations is less than 70 dB(A), such that noise protection
measures are not required.
Gases
Before service, in service and after service no gases will be
released (except when an electric arc develops).
Magnefix MD4
991.184 G01 03
19
3. SETTING UP THE SYSTEM
3.1 Introduction
3.1.1 Transport
Transport for the Magnefix switchgear can be arranged by
Eaton. Detailed instructions are beyond the scope of this
manual. Please contact Eaton Service if necessary. You
will find the address and telephone number on the title
page of this manual.
CAUTION
Transport the fuses in appropriate (original)
packing only.
The switchgear can be installed by the user's authorised
personnel.
This chapter contains general information on transporting
and setting up Magnefix MD4 switchgear and on
connecting the cables.
3.1.2 Environmental requirements
The switchroom in which the switchgear is set up must
comply with the following:
all safety regulations in force locally;
the requirements set out in the chapter on safety;
the requirements in this paragraph.
3.2 General
3.2.1 During operation
Climate
In accordance with IEC 62271-1 par. 2.1.1 the climate in
the switchroom must comply with the following
requirements:
Humidity:
maximum 90% relative over a period of 1 month. In
new buildings it is essential to dry out the area before
installing the system.
Temperature:
maximum +40°C, measured over a period of 24
hours.
average not more than +35°C.
minimum not less than - 25°C.
The room must be free from dust, corrosive or
flammable gases and salts.
The minimum temperature for Magnefix switchgear with P
panel must not be lower than -5° C.
If the Magnefix switchgear is installed in a switchroom
where unfavourable environmental conditions prevail,
special precautions must be taken to counteract discharges
and the attendant accelerated ageing of the switchgear.
Factors adversely affecting switchgear service life are:
A combination of dust and moisture: installation in
areas of high relative humidity, high groundwater level
or in areas abounding in water;
Temperature variations within the switchroom (which
are liable to cause condensation);
Presence of corrosive substances, for example in the
proximity of chemical plants, farms or alongside large
motorways;
A salty atmosphere; for example, in a coastal region.
Air currents, for instance caused by draughts or
transformer ventilation air, carrying dust liable to
deposit on the switchgear.
The sections that follow describe the main steps that are
required to be taken in order to keep the Magnefix
switchgear in a proper (and therefore reliable) condition for
as long as possible.
Magnefix MD4
20
991.184 G01 03
3.2.2 Ventilation
Magnefix MD4 switchgear does not require ventilation.
However, air circulation around the switchgear may carry
dust liable to deposit on the installation.
Take the following precautions in order to prevent
undesirable air circulation:
General
Ensure that the switchroom doors provide a good seal
in order to prevent draughts.
If located alongside a busy motorway or in the vicinity
of a farm or chemical plant, take action to minimise the
quantity of polluted air entering through the ventilation
slots.
Room without a transformer
Avoid air circulation inside the room; the switchgear
does not need any cooling.
If you decide on having a ventilation slot, position it
low in the room.
Room with a transformer
Position the ventilation slots such that the air flow
intended for transformer ventilation does not pass over
the switchgear.
If ventilation air flow over the switchgear cannot be
avoided, install an adequate dust guard.
Keep the switchgear thoroughly clean.
3.2.3 During transport and storage
If the switch panels are stored temporarily prior to
installation, or during transport:
Do not unpack the switch panels;
Store the switch panels vertically in a dry and dust-
free area;
Ensure that the transportand storage environment
complies as far as possible with the requirements of
IEC 62271-1, par. 2.1.1;
Avoid condensation caused by rapid temperature
changes.
NOTE
Keeping the installation under adverse conditions in
the open air may cause corrosion and deterioration of
the insulation level.
Ventilation:
Left: correct set-up.
Right: air currents deposit dust and dirt.
Ventilation:
Top: correct set-up.
Bottom: air currents deposit dust and dirt.
/