FläktGroup eQ Controls SK62 Installation and Maintenance Manual

Type
Installation and Maintenance Manual
FläktGroup DC_8785GB 20180228_R0 Specifications are subject to alteration without notice
CONTROL EQUIPMENT
STAZ-16, STBZ-16
INSTALLATION AND MAINTENANCE INSTRUCTIONS
ELECTROHYDRAULIC VALVE ACTUATOR SKB62
For type VVF31 and VXF31 valves with a 20 mm lift in heating, air
handling and cooling systems for the regulation of heating and cooling
water.
TECHNICAL/MECHANICAL CONFIGURATION
When the control signal is increasing (0...10VDC/0...1000 Ω) the
hydraulic pump that is built into the actuator pumps oil from the
suction chamber into the pressure chamber. As a result of this the
valve stem is forced inwards and the valve opens.
When the control signal is decreasing (0...10VDC/0...1000 Ω) the return
valve opens and the hydraulic oil in the pressure chamber is forced
to flow back to the suction chamber by the pressure of the return
spring built into the actuator. As a result of this the valve stem is forced
outwards and the valve closes.
The actuator has a factory fitted fail safe function, i.e. if the control
signal or supply voltage are interrupted the actuator returns to the 0
position.
Maintenance free electrohydraulic actuator.
Swing piston pump in the pressure cylinder for opening the valve.
Return spring and return valve for closing the valve.
Equipped with a fail safe function.
Position for integrating double auxiliary contacts and a lift stroke
limiter.
Can be equipped with a stem heater.
Equipped with a manual adjustment knob and position indication.
CONTROL SIGNAL DC 0...10 V AND 0...1000 Ω
The valve opens or closes in proportion to the control signal at Y or R.
At a control signal of 0 VDC or 0 Ω the valve is closed (A AB).
SELECTING A CONTROL CURVE
A logarithmic or linear flow characteristic can be selected using a
blade contact in the circuit board under the housing. The actuator
electronics are supplied set to a logarithmic flow characteristic.
CE MARKING
EMC in accordance with 89/336/EEC
LVD in accordance with 73/23/EEC
010 V
l
in
l
o
g
V
100
420 mA
V
H
Y, RU
H
Y, R
V
V
lin
H
Y
l
o
g
U
H
V
0
01000
Recirculation
Actuator
Valve
Y
=DC 0...10 VV=Flow
R=
0...1000 V100 =Flow 100 %
V0= Flow 0 %
U=
DC 0 ... 10 V
lo =Logarithmic
control curve
Lift (valve)=
H
lin=Linear control curve
(factory setting)
RELATIONSHIP BETWEEN CONTROL SIGNAL
DC 0...10 V AND FLOW:
2
Installation and maintenance instructions
FläktGroup DC_8785GB 20180228_R0 Specifications are subject to alteration without notice
CALIBRATION POTENTIOMETER
The calibration potentiometer is used to obtain conformity between the
supply voltage and valve lift. The potentiometer need only be adjusted
when the voltage on terminal U is being used for external indication,
e.g. for an indication device, management system or for position-de-
pendent switching.
Lift height 0%: permissible voltage on terminal U = min. DC 0.03... max.
0.4 V.
INSTALLATION
Installation must be carried out in accordance with local regulations
and in accordance with the apparatus and connection diagrams.
Safety instructions and constraints for the protection of personnel and
property are to be observed unconditionally!
The stem heater ASZ6.5 has a heat output of 30 VA and will keep the
valve stem free of ice at temperatures in the range 0 °C...-25 °C.
To ensure air circulation the actuator console and stem must not be
insulated. Touching heated components can cause burns. The failure
to comply with these instructions can result in accidents and a risk of
fire!
Observe the permitted temperatures!
ASSEMBLY
There are instructions for fitting the actuator onto the valve on the
actuator enclosure.
MOUNTING POSITIONS
2 mm
A
B
AInställningsskruv
BSexkantnyckel 2 mm
0
1
0
1
netujkstu tleh gnilppoKnegardni tleh gnilppoK
0
1
0
1
netujkstu tleh gnilppoKnegardni tleh gnilppoK
Coupling fully retracted Coupling fully extended
tillåtet tillåtet tillåtet tillåtet ej tillåtet
permitted not permitted permitted permitted not permitted
A Adjustment screw
B Allen key 2 mm
COMMISSIONING
When commissioning check the electrical connection and carry out a
functional inspection.
Check or make the adjustments for auxiliary contacts, the potentiome-
ter and lift stroke limiter.
If the manual crank is turned anti-clockwise to its stop position, the
Landis & Staefa VVF and VXF type valves will close (lift = 0 %).
AUTOMATIC OPERATION
For automatic operation the crank must be fully recessed into the
manual adjustment knob. If this is not the case turn the crank an-
ti-clockwise until neither the adjustment scale nor the crank engage-
ment bar can be seen in the display window.
MANUAL OPERATION
For manual operation lift the crank so that the display window is visi-
ble. By turning the manual adjustment knob or the crank the engage-
ment bar and/or adjustment scale with the lift indicator will become
visible in the display window.
DISPOSAL
Equipment containing electrical and electronic components that must
not be disposed of as household waste. This applies in particular to
the printed circuit board. Statutory regulations or ecological demands
require the separate handling of specific components.
Applicable local legislation must always be observed.
3
Installation and maintenance instructions
FläktGroup DC_8785GB 20180228_R0 Specifications are subject to alteration without notice
TECHNICAL DATA
Power supply AC 24 V ± 20 %
Frequency 50 Hz or 60 Hz
Power consumption 18VA
Signal input, terminal Y 0...10 VDC, max. 0.1 mA
Signal input, terminal R 0...1000 Ω
Signal output, terminal U 0...10 VDC
Runtime (open/closed) 120 s
Emergency closure time 15 s
Positioning force 2,800 N
Lift 20 mm
Permissible fluid temperature -25...+220 °C
Cable lead-ins 4 x Pg 11
Ingress protection class IP 54
Weight without packaging 8.4 kg
Weight with packaging 8.7 kg
Actuator housing and console Die cast aluminium
Plastic
HOUSING AND MANUAL ADJUSTMENT KNOB
ACCESSORIES
Stem heater for fluids below 0°C. Installation between the valve and
actuator.
Power supply 24 VAC ±20%
Power consumption 30 VA
MAINTENANCE
The actuators are maintenance free. To service the actuator:
Disconnect all pumps and the power supply.
Close all shut-off valves in the pipework.
Depressurise the lines and let them cool down.
If necessary disconnect the electrical wiring from
the terminal blocks.
The actuator can only be taken into service again
when it has been correctly installed on the valve.
1Tryckcylinder
2Kolv
3Pump
4Returfjäder
5Returventil
6Koppling
7Handomställare
8Lägesindikator (0…1)
1Handomställare
2Koppling för ventilspindel
3Lägesindikator (0…1)
4Stativ
3
7
1
4
5
2
8
6
1
3
2
0
1
4
1Tryckcylinder
2Kolv
3Pump
4Returfjäder
5Returventil
6Koppling
7Handomställare
8Lägesindikator (0…1)
1Handomställare
2K
oppling för ventilspindel
3Lägesindikator (0…1)
4Stativ
3
7
1
4
5
2
8
6
1
3
2
0
1
4
GO GYRMU
GO GYRMU
24 V
A
C
B
5
6
8
7
5Anslutningsklämmor
6Kontaktdon r val av reglerku
rva«
lin
»
log»
7Plats för lyfthöjdsbegränsare
ASZ62.63
8 Plats för hjälpkontakt
ASC1.6
Permitted ambient
conditions
Operation
IEC 721-3-3
Transport
IEC 721-3-2
Storage
IEC 721-3-1
Ambient conditions Class 3K5 Class 2K3 Class 1K3
Temperature -15...+55 °C -30...+65 °C -15...55 °C
Relative humidity 5...95 % RF < 95 % RF 0...95 % RF
1 Pressure cylinder
2 Piston
3 Pump
4 Return spring
5 Return valve
6 Coupling
7 Manual adjustment knob
8 Position indicator (0…1)
1 Manual adjustment knob
2 Coupling for valve stem
3 Position indicator (0…1)
4 Console
5 Connection terminals
6 Connector for selecting control curve « lin » / « log »
7 Position for lift stroke limiter ASZ62.63
8 Position for auxiliary contact ASC1.6
4
Installation and maintenance instructions
FläktGroup DC_8785GB 20180228_R0 Specifications are subject to alteration without notice
CONNECTION DIAGRAM
The connection diagrams show how the actuators can be connected.
Which diagrams and how many actuators depends on the relevant
installation.
SN
GO
Y...
GY RU
M
1P1N
SP
DC 0...10V
0...1000
R1
RM F1
RM
G Y(Y') RMU
G0
*)
R-M
DIMENSIONS
1
0
235
Ø44 76
127
147
89 137
375*
Pg11
Pg16**
Snitt A
A
Ø178
46
Ø24
Ø10/Ø14
* The height of the actuator from the valve plate without stroke inverter ASK51 = 375 mm
The height of the actuator from the valve plate with stroke inverter ASK51 = 432 mm
= > 100 mm, minimum distance to wall or roof
 = > 200 mm, connection, operation, maintenance etc.
AC 24 V, DC 0...10 V and/or 0...1000 Ω
Section A
WIRING DIAGRAM
G, G0 Supply voltage AC 24 V
G System potential (SP)
G0 System neutral (SN)
Y Control signal input for DC 0...10 V signal
Y` Control signal input for DC 0...10 V V signal (only
for an integrated lift stroke limiter ASZ62.6)
R Signal input for a position indicator or for a frost
protection device with a 0...1000 Ω signal
M Measuring neutral
U DC 0...10 V measuring signal output (at Y=DC
0...10 V and/or R=0...1000 Ω) or DC 4...20 mA
measuring signal output (at R=DC 4...20 mA)
*) The jumper designated R – M on the circuit
board must be cut when terminal R is controlled by 0...1000 Ω