FläktGroup CAIRfricostar Controller Quick start guide

Type
Quick start guide
CAIRplus SE Controller
QUICK GUIDE
Contents
CAIRplus
2FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
1 Safety ................................................................................................. 3
1.1 Identification of safety instructions .................................................................. 3
1.2 Safety-conscious work procedures ................................................................. 3
1.3 Proper use ....................................................................................................... 4
1.4 Modifications and changes .............................................................................. 4
1.5 Spare parts ...................................................................................................... 4
1.6 Disposal .......................................................................................................... 4
1.7 Selection and qualification of personnel .......................................................... 5
2 Operation ........................................................................................... 6
2.1 Login / Access unit operation .......................................................................... 6
2.2 Basic operation ............................................................................................... 7
2.3 System user interface ..................................................................................... 8
2.4 Setup wizard ................................................................................................... 8
2.5 Flowchart ....................................................................................................... 12
2.6 Tiles ............................................................................................................... 13
2.7 I/O-Forcing .................................................................................................... 17
2.8 Alarms ........................................................................................................... 17
2.9 Event ............................................................................................................. 18
2.10 Trend ............................................................................................................. 18
2.11 Scheduler ...................................................................................................... 19
2.12 Settings ......................................................................................................... 20
2.13 Information .................................................................................................... 21
3 Service and Maintenance ............................................................... 22
3.1 Maintenance .................................................................................................. 22
3.2 Disassembly and Disposal ............................................................................ 22
– Original Operation Manual –
Copyright note
This document may not be distributed or reproduced, nor may its contents be used for commercial purposes
or otherwise disclosed, unless expressly permitted. Infringement of the above will incur liability to pay dam-
ages. All rights reserved in the event of grant of patent, utility model or design.
Safety
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 3
1 Safety
The monitoring and controlling system ISYteq is built according to the state of technol-
ogy and the recognized safety engineering rules.
Operate the ISYteq System only in fully acceptable technical condition for its intended
use. Observe all relevant safety instructions and precautions in the operating manual.
Use proper safety measures to prevent hazardous situations which, if not avoided,
could result in a threat to life and limb of the user or third parties or damage the system
itself, connected units, or other property!
Have all faults repaired by an authorized specialist without delay!
1.1 Identification of safety instructions
The following symbols and notices are provided in appropriate places throughout this
document to designate the safety instructions.
1.2 Safety-conscious work procedures
Observe the following instructions when carrying out installation, adjustment or repair
work:
For carrying out work near low-voltage networks:
For work on the electronic components:
For all kinds of work:
Observe all assembly instructions.
Fluctuations and imbalances of the supply voltage must not exceed the tolerance
limits specified in the technical data.
ELECTRICAL HAZARD!
This symbol indicates a risk of electric shock when working on the equipment.
RISK OF ELECTROSTATIC DISCHARGE!
This symbol precedes activities where there is a danger of damage to the elec-
tronic equipment by static discharge.
DAMAGE TO THE UNIT!
This section specifies procedures and precautions regarding the prevention of
equipment damage.
PERSONAL INJURY!
This section specifies procedures and precautions for the prevention of personal
injury.
ELECTRICAL HAZARD!
Disconnect all electric power to the unit and ensure that the power cannot be inad-
vertently switched on, earth, short-circuit, and block off all neighbouring live parts.
Non-compliance can lead to death or serious injury.
RISK OF ELECTROSTATIC DISCHARGE!
While carrying out adjustment work, make sure that you discharge yourself stati-
cally before touching the circuit board and electrical components.
Safety
CAIRplus
4FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
1.3 Proper use
The FläktGroup controls system ISYteq has been specifically designed to suit all prod-
ucts within the FläktGroup portfolio, and is primarily intended to be performing the fol-
lowing functions:
to regulate the room/supply-air temperature
to regulate the fan speed (volume flow/duct pressure)
filtering normally polluted air
air heating and/or cooling
humidifying and/or dehumidifying of air
heat rejection or heat recovery
or combination of the above-mentioned functions.
Proper use also includes observance of the operating manual and the inspection and
maintenance conditions stipulated by FläktGroup.
IMPROPER USE Any use other than that described above is considered improper. The manufacturer/
supplier is not liable for any damages arising from improper use. The user alone bears
the risk.
1.4 Modifications and changes
Changes, alterations or modifications of the FläktGroup controls platform are forbid-
den.
Any changes or modifications will invalidate the CE conformity and void warranty.
1.5 Spare parts
Only original FläktGroup spare parts are allowed, since FläktGroup is not liable if third-
party spare parts are used.
1.6 Disposal
Equipment and operating supply materials must be disposed of according to the mate-
rial type in a safe and environmentally friendly manner.
PERSONAL INJURY!
It is forbidden to operate the FläktGroup controls platform in the following condi-
tions:
in areas subject to explosion risk
in environments with conductive dust
in environments with strong electromagnetic fields
in environments with corrosive and/or aggressive atmosphere
in humid rooms and wet areas
in areas with high dust content
Safety
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 5
1.7 Selection and qualification of personnel
Ensure that every person commissioned to work on the controlling system has com-
pletely read and understood this operating manual – especially the chapter on safety.
Please read this document fully before commencing any work, and not while perform-
ing a task.
Electrical connections may only be carried out by qualified licensed staff or other indi-
viduals with proper professional training and experience in the following areas:
Occupational health and safety regulations
Accident prevention regulations
Directives and recognized codes of practice
All skilled staff must be able to assess the work entrusted to them and must be able to
recognise and avoid all associated dangers.
Operation
CAIRplus
6FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2 Operation
2.1 Login / Access unit operation
Either use 7”HMI or Notebook connect to the unit.
(Default address of the unit: 192.168.0.1, 255.255.255.0, 0.0.0.0)
After the first start of the unit the controller provides first the setup wizard. It can be
skipped by using the “skip setup wizard” button or accessed by enter credentials and
press the “LOGIN” button.
Fig. 2-1
Users have a dedicated user role. The following users are defined as standard:
Tab. 2-1
The different roles have the following rights for the system:
Tab. 2-2
Level Name User name Password
1Guest Guest
2Operator Operator Operator
3Admin Admin Admin
Restart
Backup
Restore
File access (FTP)
Time
synchronization
Simplified View
General
Network
Project
User database
Alarms
Diagnostic
Guest ----------R
Operator - - - - - X - - - - R/W R
Admin X - - - X X R/W R/W R/W R/W R/W R
X = yes; R = read; W = write
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 7
2.2 Basic operation
User Login Login with your assigned role
Flowchart Main menu 1
Tile menu Main menu 2
In-/Outputs Forcing of all configured I/O’s
Energy monitoring Displays the energy consumption if configured
Smart menu Setup wizard / Documentation generator
(EDE File, Service Report) etc.
Operating data Unit configuration
Alarm list List with open fault and maintenance messages
Events History List with all notified fault and maintenance
messages
Trendlogs To collect data and then store the records
Switching times Different scheduler
Web configuration Advance system settings
Operation
CAIRplus
8FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.3 System user interface
Two different user interface start-up screens can be selected. The setting is made in
the wizard or manually in the configuration.
Flowchart
Fig. 2-2
Tiles
Fig. 2-3
The individual screens are described in more detail later in this document.
2.4 Setup wizard
With the Setup Wizard it is possible to configure the system. You are automatically
guided through the following pages.
Note:
All current settings will be overwritten!
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 9
2.4.1 Skip setup wizard
After pressing skip button it it possible to keep it alive and start automatically the wizard
after the next restart of the browser or keep it continuously off.
Fig. 2-4
When the wizard is executed, please note the further points.
2.4.2 Language settings
Choose a country by selecting a flag, and press the green check button to acknowl-
edge and go ahead with the next page.
Fig. 2-5
2.4.3 Components not available for CAIRplus
Reset selection
Acknowledge language
and go ahead
Skip language settings Leave wizard
Operation
CAIRplus
10 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.4.4 Control settings
Choosing of fan control type, temperature, humidity control type and enabling of air
quality if necessary.
Fig. 2-6
Classical guide values related to the guideline VDI 2089 are:
30 °C air temperature
28 °C water temperature
at a room humidity of 54% rH
2.4.5 Time, date & units
Selecting of time settings and choosing units.
Fig. 2-7
Reset selection
Acknowledge selections
and go ahead
Skip settings Leave wizard
Reset selection Acknowledge selections
and go ahead
Skip settings Leave wizard
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 11
2.4.6 Edit Profiles
Setting parameters for different operating modes, at least “Idle Mode” and “Pool Mode”
should be reviewed and adjust according the unit data. Profile data are pending of unit
configuration.
Fig. 2-8
2.4.7 Unit operation scheduler
The active times for the pool mode profile and idle mode profile can be set here. It can
be changed afterwards via the switching times menu. They can be changed afterwards
via the scheduler. A start time is always entered. The end time is automatically deter-
mined by the start time of the new time block.
Fig. 2-9
2.4.8 Start up settings
Changing the values defined for the start-up phase.
Fig. 2-10
Operation
CAIRplus
12 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.4.9 Default page
Select which start page is to be set as the default. Flowchart and tile selection possible.
Fig. 2-11
2.5 Flowchart
This screen is dynamically structured. Only the units or parts of the system that are
available in the system are displayed (according to the system configuration).
Fig. 2-12
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 13
2.6 Tiles
This screen is dynamically structured. Only functions that have been configured in the
system (profile) are displayed.
Fig. 2-13
Manually changes in the tiles will be overwritten when the profile will be changed (e.g.
Scheduler).
If values needs to be changed permanently, the relevant profile has to be modified.
2.6.1 Fan Tile
Displays the setpoint and the present value.
Fig. 2-14
The setpoint can be adjusted manually using the arrow keys
(up/down) or by moving the volume adjustment ring. After
changing the profile, the setpoint will be overwritten with the one
specified in the profile.
Fig. 2-15
Operation
CAIRplus
14 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.6.2 Profile bypass Tile
With this feature you can start separate profile as bypass for a
certain time.
For example, spectator operation with high fresh air rate.
Fig. 2-16
The time of the bypass and the required profile can be selected.
Fig. 2-17
2.6.3 Temperature Tile
Displays the setpoint and the present value.
Fig. 2-18
The setpoint can be adjusted manually using the arrow keys
(up/down) or by moving the volume adjustment ring. After
changing the profile, the setpoint will be overwritten with the one
specified in the profile.
Fig. 2-19
2.6.4 Controller Mode Tile
Displays the active controller mode.
Fig. 2-20
A different controller mode can be selected manually.
In automatic mode, the control mode is taken from the active
profile in the scheduler.
Fig. 2-21
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 15
2.6.5 Edit Profile Tile
To operate the unit the program has five adjustable profiles,
which contains group of setpoints that specifies the intended op-
erating mode.
Fig. 2-22
The following profiles are possible:
Tab. 2-3
2.6.6 Operating mode Tile
Displays the active operating mode (profile) and the next switch-
ing time.
Fig. 2-23
The operating mode can be changed manually.
In the automatic mode, the switching times of the scheduler are
active.
Fig. 2-24
Name Default
Idle Mode Operation 0% Fresh air rate
Pool Mode Operation 30% Fresh air rate
Construction Mode Operation 100% Supply air (No exhaust air!)
Free Profile 1 free
Free Profile 2 free
Boost
For preheating the room.
With this function it is possible to calculate a pre-switching time
and set the unit in a boost profile, before the normal operation will
be started.
Room Frost Protection Standby profile
Operation
CAIRplus
16 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.6.7 Extract air humidity Tile
Display of the setpoint (displayed in large) and the current value
(displayed in small).
Fig. 2-25
The setpoint can be adjusted manually using the arrow keys
(up/down) or by moving the volume adjustment ring. After
changing the profile, the setpoint will be overwritten with the one
specified in the profile.
Fig. 2-26
2.6.8 Outdoor air amount Tile
Display of the setpoint (displayed in large) and the current value
(displayed in small).
Fig. 2-27
The minimum and maximum outdoor air volume can be set
manually by using the arrow keys (up/down) or by moving the
volume adjustment ring. After changing the profile, the setpoints
will be overwritten with the one specified in the profile.
Fig. 2-28
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 17
2.7 I/O-Forcing
Forcing of all configured I/O’s. To check the function of the unit, values can be “forced”
manually.
Fig. 2-29
2.8 Alarms
In this screen, the current fault messages (alarms) are displayed in a list.
The term “current” means in this case either still pending or not yet acknowledged.
Fig. 2-30
Operation
CAIRplus
18 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.9 Event
Fig. 2-31
2.10 Trend
You use a trend log to collect data and then store the records. A trend log can log each
I/O variable.
The specific values to be displayed in the trend can be selected here.
Fig. 2-32
Trend-Visualization
Fig. 2-33
Operation
CAIRplus
FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications 19
2.11 Scheduler
Fig. 2-34
Fig. 2-35
In order to prevent the primary and/or secondary pumps and the valves from blocking,
they are automatically activated for a short time at a certain interval. The time and dura-
tion of the blocking protection depend on the settings selected in the next two sched-
ulers.
Unit Operation Mode Scheduler
Weekly Schedule: Setting of the weekly program
Exception Schedules: It is possible to add special switching times.
Date / Rate Range / Week and Day
Smoke Bypass Damper Exercise Scheduler
Blocking protection of the Valve
Time and duration of the blocking protection can be set in this scheduler.
Change Over Scheduler
You can specify summer or winter operation in the exception scheduler. This
has an effect on the control mode.
Pump Kick Scheduler
Blocking protection of the Pump
Time and duration of the blocking protection can be set in this scheduler.
Valve Lime Kick Scheduler
Blocking protection of the Valve
Time and duration of the blocking protection can be set in this scheduler.
Operation
CAIRplus
20 FläktGroup DC-10607-GB 2021-11-17/R0 • Subject to modifications
2.12 Settings
Fig. 2-36
– Configuration
Device : Device information, set date and time or set geographical
location, set general settings of the webconfiguration.
Network : Configure the interfaces of the device
Syslog : Set Syslog settings
User : Change your own password here and choose your preferred
language.
Setup Wizard : Start Setup Wizard for commissioning support
Note:
All current settings will be overwritten!
– System
Device information : Extended device information, e.g. hardware
Activation code : Use an activation number to activate additional functions.
BACnet : Show BACnet runtime data, status and access to the user
program.
Diagnosis : e.g. Read the last restart reason of your system.
Restart : Initialize a device restart, for example after changing con-
figuration data.
Backup & Restore : Create or restore a backup
– Documents
Documentation of the product are stored here.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24