Danfoss ECL Comfort 200 - P30 Operating instructions

Type
Operating instructions
ECL COMFORT
Table of Contents
Daily Use
Section
1 Choose favourite display
2 Select controller mode
3 Adjust room temperature
4 Set personal day plan
6 Hot points
7 Definitions
Your personal week plan:
This guide is associated to ECL Card 087B4653
Installer:
By:
Date:
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Table of Contents
Sections of the Installers part of this guide.
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
13 Electrical connections 24 V a.c.
14 Placing the temperature sensors
15 Adapting the ECL Comfort controller
Basic Set-up
16 Adjusting the ECL settings
17 Setting the time and date - Line A
18 Monitoring temperatures and system units - Line B
19 Manual control - Line B
20 Setting the heat curve - Line C
21 Heating cut-out - Line 1
22 Flow temperature limits - Line 2
23 Room temperature influence - Line 3
26 Setting the PI-regulation - Line 4-7
Check & Overviews
29 Check list
30 ECL settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Daily use, turn the guide over sections 1-7
1 Choose favourite display
2 Select controller mode
3 Adjust room temperature
4 Set personal day plan
6 Hot points
7 Definitions
ECL Comfort
Users Guide
P30
Mixing controller
P30
VI.7B.C4.02
2001.03
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Installation and maintenance. Grey sections 10 and
onwards. Turn the guide over.
Heating 03691215182124
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Factory settings are grey.
6-8 16 - 22
823-
The shown diagram is a fundamental and simplified example
and does not contain all components that are necessary in
heating systems.
If the system you are about to install differs from the shown
diagram of a standard heating system, feel free to sketch
an outline for comparison. Adaptation of heating systems,
see section 10.
List of components:
ECL Comfort 200
S1 Outdoor temperature sensor (ESM-10)
S2 Room temperature sensor (ESM-10)
S3 Flow temperature sensor (ESM-)
S4 Return temperature sensor (ESM-)
P1 Circulation pump for heating circuit
M1 Control valve with actuator
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Extended service parameters,
see section 31
The ECL Card: Installer’s guide
The grey side of the card must face
you when you change settings. For
daily use and during start-up, the
yellow side of the card must face you.
User setting
indicator
User/
service
settings
Shift
button
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switch between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Switch between user settings (yellow card
side) and service settings (grey card
side).
The circuit indicator lamp shows the selected card side.
The ECL Card
For daily use and your personal adjustments the yellow side
of the ECL Card must be facing you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switch between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Switch between user settings (yellow card
side) and service settings (grey card
side).
Line indicator
Room temperature
Heating system
information
Today’s programme
Day plans
A
B
C
1
2
3
4
5
6
7
6
7
1
2
3
4
Heating circuit
Service setting
indicator
3 91-
0
A
2
5
1
1
ON
036
B
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
6
0 3 6 9 12 15
0
5
0
8
0 3 6 9 12 15 18 21 24
0
7
0
Adjustment Controller
mode
8
9
10
199
Before you start
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating systems.
The ECL Comfort controller ensures you of the following;
Room temperatures will be adjusted to your personal
settings
.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with different configurations and
capacities.
If your heating system differs from the diagrams shown in
section 10, you may want to sketch an outline of the system
about to be installed. This makes it easier to use the
Installers Guide, which guides you step-by-step from
installation to the final adjustments before the end-user
takes over.
Note! The controller is pre-programmed with factory
settings that are shown in the relevant sections of this guide.
Operating the ECL Controller and the ECL Card
The ECL Card has a yellow side for the daily use and a
grey side for the installation and maintenance.
However, you might come across some settings that
are not listed in this instruction. These settings are used in
connection with optional modules, and you can find a
description of the settings and the corresponding
parameters in the instruction for the optional module in
question.
Select the side of the ECL Card you want to operate.
The light diode below the inserted ECL Card
indicates the chosen side, ie. left light for daily
use and right light for the installation and maintenance.
(See sections 15 and 16).
Both sides of the ECL Card are divided into lines
representing the different options of control and
programming.
How to use this guide
This guide is divided into two parts:
Daily Use (turn the guide over)
Yellow sections 1-7
Installation and maintenance:
Grey sections 10 and onwards
VI.7B.C4.02
2001.03
Installation
Heating system type 3
Heating circuit with boiler and 3-way valve
Heating system type 4
Heating circuit with boiler and 4-way valve
Note!
System diagrams in this instruction are principal drawings
and do not necessarily contain all components for heating
systems.
Installation
Identifying the system
type
10a
Heating system type 2
District heating circuit - direct connection
Heating system type 1
District heating circuit with heat exchanger
In this section you find the most frequently used systems.
If your system is not quite as shown below, find the diagram
which has the best resemblance to your system and make
your own combinations.
Alternatives using the same settings:
Heat exchanger or direct district heating
2-, 3-, or 4-way control valve
10b
Installation
Installation
Mounting the ECL Comfort
controller
11a
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
11b
Connecting the temperature sensors
Installation
Wire cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Cable type: Copper cable.
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Establish the jumper from 16 to common terminal.
Terminal Description Type (recommended)
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
Connecting the 230 V a.c. units
12a
Electrical connections -
230 V a.c.
Installation
Wire cross section: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted in each screw terminal.
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
Terminal Description Max. load
1 L Supply voltage 230 V a.c.
(Phase)
2 N Supply voltage 230 V a.c.
(Neutral)
3 M1 Gear motor - open 0.2A/230 V a.c.
4 M1 Gear motor - close
alt.: ABV thermo actuator 0.2A/230 V a.c.
5 Phase for M1
9 P1 Circulation pump 4(2)A/230 V a.c.
10 Phase for pump relay
12b
Connecting the temperature sensors
Installation
Wire cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
Cable type: Copper cable.
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Establish the jumper from 16 to common terminal.
Connecting the 24 V a.c. and 230 V a.c. units
13a
Electrical connections -
24 V a.c
Wire cross section: 0.75 - 1.5 mm
2
Cable length: Max. 50 m
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted in each screw
terminal.
Installation
* K1 auxiliary relay
Coil: 24 V a.c.
Contacts: 4A/230 V a.c.
Establish these jumpers:
Jumper from 1 to 5
Jumper from 5 to 10
Jumper from 2 to common N-terminal
13b
Terminal Description Max. load
1 L Supply voltage 24 V a.c.
2 N Supply voltage 24 V a.c.
3 M1 Gear motor - open 1A/24 V a.c.
4 M1 Gear motor - close
alt.: ABV thermo actuator 1A/24 V a.c.
5 24 V a.c. supply for M1
9 K1* Relay for circulation pump P1
10 24 V a.c. supply for relay
Terminal Description Type (recommended)
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESM-10
18 and 16 Room sensor (S2) ESM-10
19 and 16 Flow sensor (S3) ESMU/ESM-11/ESMC
20 and 16 Return sensor (S4) ESMU/ESM-11/ESMC
15
Adapting the ECL Comfort
controller
While the set-up is in operation, the data transfer-display
will appear.
After initialising, the display will return to the standard
display line C (the yellow side of the ECL Card).
The controller is now ready to control the selected
application type. You can make your own adjustments /
settings for daily use in the basic set-up and change the
extended service settings.
Installation
Switch on the power for the controller. The display shows
the heating system application and the software version.
P
60
03
1
P03
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
Select the application type printed on your ECL
Card.
Accept to set up the selected application.
Insert the ECL Card with the grey side facing you.
See section 16 for general principles of operation and
section 17 for setting the time and date.
Choose the grey side of the ECL Card for the
basic set-up and the extended service
parameters.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the correct
position in your heating system.
Special attention should be paid to the following sensors.
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows
or air outlets.
Flow temperature sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean where the
sensor is mounted.
Note!
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed in / on a pipe
with return water flow.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls nor
close to radiators, windows or doors.
Installation
17
Setting the time and date -
Line A
Basic set-up
In case of a power failure which lasts longer than 12 hours,
the time and date have to be set again.
All other settings are stored when programmed.
Go to line A.
Use the shift button to switch between hours,
minutes, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See Users Guide, section 4.
01
01
3700
5
A
3
1
Actual time
Month, day
Year
Basic set-up
16
Adjusting the ECL
settings
If several controllers are installed in the heating system you
can write a title on the ECL Card with a permanent ink pen.
Changing from one side of the ECL Card to the other
When changing from the grey side of the ECL Card to the
yellow side, you will always enter line C and the standard
display.
Changing from the yellow side to the grey side, you will
always enter line A - Time and date.
See opposite page.
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings
referring to the grey side of the ECL Card. Select the grey
side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Use the minus / plus buttons to adjust the
setting(s).
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options. The chosen value flashes
in the range indicator.
8
0 3 6 9 12 15 18 21 24
1
3
5
C
3
19
Line
indicator
Settings to
be adjusted
Value in
range indicator
0
1
094
2
1
ON
The grey
side of the
ECL Card
Basic set-up
Go to line B.
Shift to manual mode
Controlled
units
Controller mode
5
1
1
ON
036
B
Basic set-up
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as
- -.
If the sensor is short-circuited, the display will indicate it as
- - - .
If you are in doubt, remove the controller and check the
ohmic value between the relevant sensor terminals.
Go to line B.
Push the shift button to see:
- the calculated flow temperature
- the return temperature set point
5
1
1
ON
036
B
Controlled units
Return temperature
Flow
temperature
State indicator
Relationship between temperature and ohmic value
-10 °C 961 Ohm
0 °C 1000 Ohm
10 °C 1039 Ohm
20 °C 1078 Ohm
30 °C 1117 Ohm
40 °C 1156 Ohm
50 °C 1195 Ohm
60 °C 1234 Ohm
70 °C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
19
Manual control - Line BMonitoring temperatures
and system units - Line B
18
The grey
side of the
ECL Card
The grey
side of the
ECL Card
The gear motor
opens or closes
the valve as long as the the relevant button is
pressed.
The thermo actuator
(according to version *)),
closes (NO) or opens (NC)
the valve as long as the relevant button is
pressed.
*) NO - normally open
NC - normally closed
Pumps are switched off or on
when the relevant button is pressed.
1
ON
1
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
Note!
During manual operation, the pump motion is OFF.
Select the unit you want to control. The selected
unit symbol will flash.
1
1
11
Basic set-up
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Basic set-up
Setting the heat curve
- Line C
20a
Go to line C.
The symbol for the slope of the heat curve will
flash.
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Make your adjustment
1
1
ON
8
C
1
0
Slope
Displacement
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Floor heating systems
This controller is factory set for radiator systems which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your system type.
20b
Slope
Setting range Factory setting
0.2 ... 3.4 1.8
Parallel displacement
Setting range Factory setting
-9 ... +9 0
Slope
Setting range Typical setting
0.2 ... 3.4 1.0
Parallel displacement
Setting range Typical setting
-9 ... +9 0
Basic set-up
Go to line 2.
The left end of the range indicator flashes. Adjust
the min. limit of your heating system.
Select the max. limit. The right end of the range
indicator will flash.
Adjust the max. limit.
0
1
094
2
1
ON
Max. flow
temperature
Min. flow
tem-
perature
Temperature
range for flow
temperature
Basic set-up
1
1
ON
8
1
1
Go to line 1.
Set the value for outdoor temperature at which
you want the heating system to stop.
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Flow temperature limits
- Line 2
22
Heating cut-out - Line 1
21
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated T
out symbolises the heat stored in the
building.
18 ˚C
Temp
Actual T
out
Accumulated T
out
Time
Heating Heating off Heating
2 Flow temperature min.-, max. limits
Setting range Factory setting
10 ... 110
0
C min. 40 °C max. 90 °C
1 Limit for heating cut-out (based on high outdoor
temperature)
Setting range Factory setting
10 ... 30 °C 18 °C
Basic set-up
The room sensor in the reference room
registers the difference between the desired
and the actual room temperature. The flow
temperature reference will be corrected to
eliminate this difference.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
Set a positive value for min. influence and a
negative value for max. influence.
+
_
Influence
Min. limitation
Set T
ROOM
T
ROOM
Max. limitation
Example 1
The actual room temperature is 2 degrees too low.
The influence at max. limitation (right corner of the display) is
set to
-20.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x 0.1 x H = 7.2 degrees.
Example 2
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-35.
The influence at min. limitation (left corner of the display) is
set to 35.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x 0.1 x H = -12.6 degrees.
Basic set-up
This section is only relevant if you have installed a room
sensor or ECA 60 / 61. There are two basic principles for
control of the room temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a
max. limitation of the room temperature. The controller will
allow for free heat gains, i.e. solar radiation or heat from a
fire place, etc.
The max. influence determines how much the
room temperature should influence the flow
temperature.
Go to line 3.
Select the max. influence.
The bar below the range indicator flashes in
the right side of the display.
Adjust the max. influence.
+
_
Influence
Max. limitation
T
ROOM
Set T
ROOM
Example
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to
-40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x
-40 x 0.1 x H = -14.4 degrees.
1
1
ON
-040
3
Min.
influence
Max.
influence
Room temperature
influence - Line 3
23a 23b
The grey
side of the
ECL Card
The grey
side of the
ECL Card
3 Room temperature influence
Setting range Factory setting
0 ... 99 / -99 ... 0 min. 0 max. -40
Basic set-up
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value
in the critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.
Note! Make sure there is a consumption when you set the
parameters.
Time
Temp
Critical time period
How to calculate the running time of the motorized valve
The running time of the motorized valve is calculated using the
following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec./mm)
Example: 5.0 mm x 15 sec./mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec./degr.)
Example: 90 degrees x 2 = 180 sec.
Valve type Valve Actuator Actuator Running
stroke type speed time
(mm) (sec./mm) (sec.)
VS2 15 3.0 AMV 100 90 270
VS2 15...25, VM2 15...25, AMV(E)
VB2 15...20 5.0 10, 20 15 75
VS2 15...25, VM2 15...25,
VB2 15...20 5.0 AMV(E) 30 3 15
VM2 32, VB2 25 7.0 AMV(E) 20 15 105
VM2 32, VB2 25 7.0 AMV(E) 30 3 21
Basic set-up
Setting the PI-regulation
Line 4 - 7
(only gear motor)
26a 26b
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Set the proportional band
A higher value will result in a stable, but slow
regulation of the flow temperature.
Go to line 7.
Set the neutral zone to a high value if you can
accept a large variation in flow temperature.
When the actual flow temperature lies within the
neutral zone, the controller does not activate the
motorized valve.
Note! The neutral zone is symmetrical around
the flow reference value.
Go to line 6.
Set the running time of the motorized valve
according to the example on opposite page. This
is the time it takes the valve to move from closed
to fully open position.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A low integration time constant will make the
controller react fast but with less stability.
Go to line 4.
Setting to be adjusted
Line
indicator
1
1
ON
4
80
4 Proportional band
Setting range Factory setting
1 ... 250 K 80 K
5 Integration time constant
Setting range Factory setting
5 ... 999 sec. 30 sec.
6 Running time of the motorized valve
Setting range Factory setting
5 ... 250 sec. 35 sec.
7 Neutral zone
Setting range Factory setting
0 ... 9 K 3 K
Adapting the ECL Comfort controller to the heating
system
Control & overviews
Turn the ECL Card so that the grey side faces
you.
Select basic setup and extended service
settings.
Set the time and the date (Line A)
See section 17.
Check all settings referring to the grey side of the
ECL Card.
See sections 20 to 26.
If your heating system differs from the diagram
shown on the overleaf of the cover, you should
check and alter the service parameters, if
required.
Please pay special attention to line 35 and 36.
Control & overviews
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 and 2.
See section 12 or 13
.
Check that valve and pump are connected to the
correct terminals.
See section 12 or 13.
Check that all temperature sensors are
connected to the correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you, and push
, if necessary.
Select manual operation in the controller mode.
See section 2
in the Users Guide.
Check that the valve opens and closes, and that
the pump starts and stops when operated
manually.
See section 2
in the Users Guide.
Check that the temperatures shown in display A
and B match the actual sensors.
See section 1
in the Users Guide.
29b
Check list
29a
Check list
Control & overviews
10 Choice of room panel / remote control
0 ... 5 0
11 Reduced temperature dependent
on outdoor temperature
OFF / -29 ... +10 °C -15 °C °C
12 Boost
0 ... 99% 0% %
14 Optimising time constant
OFF / 10 ... 59 OFF
15 Adaptive function of room
temperature
OFF / 1 ... 30 OFF
20 Optimisation based on room /
outdoor temperature
ON / OFF OFF
21 Total stop
ON / OFF OFF
22 Pump motion
ON / OFF ON
23 Valve motion
ON / OFF OFF
24 Gear motor / thermo actuator
ON / OFF ON
30 Return temperature limitation
10 ... 110 °C 50 °C °C
35 Return temperature
influence - max
-9.9 ... 0 ... +9.9 -2
36 Return temperature
influence - min
-9.9 ... 0 ... +9.9 0
37 Adaptive function of return
limitation
OFF / 1 ... 50 25
52 Closed valve / normal operation
ON / OFF OFF
141 Override input selection
OFF / 1 ... 4 OFF
174 Motor protection
OFF / 10...59 min OFF
196 Service pin LON
ON / OFF OFF
197 LON reset
ON / OFF ON
198 Summer time change
ON / OFF ON
199 Slave address
0 ... 9 15
Circuit I
Line Setting range Factory seting Your setting
Control & overviews
Heat curve - Slope
0.2 ... 3.4 1.8
Set the slope of the heat curve,
see section 20
Heat curve - Parallel displacement
-9 ... +9 K 0 K
Set the parallel displacement of the
heat curve, see section 20
1
Limit for heating cut-out
10 ... 30 °C 18 °C
Saves energy by stopping the heating system
when the outdoor temperature gets above
a certain limit, see section 21.
2
Flow temperature min.-/max. limits
10 ... 110 °C min. 40, max. 90 °C
The limits for min. and max. flow
temperature, see section 22.
3
Room temperature influence
0 ... 99/-99 ... 0 min. 0, max. -40
The room temperatures influence on the
flow temperature control, see section 23.
4
Proportional band
1 ... 250 K 80 K
Set the PI-regulation, see section 26.
5
Integration time constant
5 ... 999 sec. 30 sec.
Set the PI-regulation, see section 26.
6
Running time of the motorized valve
5 ... 250 sec. 35 sec.
Set the PI-regulation, see section 26.
7
Neutral zone
0 ... 9 K 3 K
Set the PI-regulation, see section 26.
A Time and date
B System information
C Heat curve
Setting range Factory setting Your setting
See sections 16 & 17
See sections 18 & 19
See section 20
Service parameters
31
ECL settings
30
Extended Service
Service parameters 10-11
Extended service
-29 to +10 °C
The setting of the reduced temperature
depends on the outdoor temperature, when the
outdoor temperature is higher than the set limit.
The lower the outdoor temperature, the less the
temperature reduction. When the outdoor tem-
perature is below the set limit, there is no tem-
perature reduction.
OFF: The reduced temperature setting will be
constant at all outdoor temperatures.
100%
0%
-20 -10-29 0 10 2015
Reduction
Outdoor
temp.
o
C
Adjusting the service
parameters
In addition to the settings in line 1 to 7 on the grey side
of the ECL Card, there is an extended service menu
from line 10 and onwards.
Push repeatedly to reach the lines numbered
10 and onwards.
Set the parameter value.
When you have entered all your personal settings, turn
the ECL Card over so that the yellow side faces you.
Select daily use settings
Extended service
Line
number
Value
Range
indicator
01
0
The grey
side of the
ECL Card
32a 32b
10 Choice of room panel / remote control
Setting range Factory setting
0 ... 5 0
Decides the communication with the room panel or remote
control. Choose either 1 or 2 if you have installed a room
panel or remote control.
11 Reduced temperature dependent on outdoor
temperature
Setting range Factory setting
OFF / -29 ... +10 °C -15 °C
The outdoor temperature at which the reduced
temperature setting is switched off. Below this outdoor
temperature, the reduced temperature setting has no
influence.
Choose between
0 ECL Comfort controller - week plan
1 Room panel ECA 60 or remote control
ECA 61 on address A
2 Room panel ECA 60 or remote control
ECA 61 on address B
3 ... 5 Not used
The adaptive function will eliminate the difference between
the required and actual room temperature by integrating
the difference and adjusting the reference for the flow
temperature.
OFF: No optimisation. The heating starts and stops at
the times set in the week plan.
Extended service
OFF: The adaptive function is cancelled.
1: The desired temperature is adapted
quickly.
30: The desired temperature is adapted
slowly.
41
25
Dimensioning temperature: The lowest outdoor
temperature at which the heating system can secure
the desired room temperature.
Service parameters 14-15
Adjust the optimising time constant. The value
consists of a number of two digits. You can select
the following values:
11, 12, ..... 59.
The two digits have the following meaning:
1. digit (system type and heat accumulation of
the building)
1. digit Heat accumulation System type
of the building
1
light
Radiator
2
medium
system
3
heavy
4
medium Floor
5
heavy system
2. digit (capacity of the heating system)
2. digit Dimensioning Capacity
temperature
0 -50 °C large
.. .
.. .
5 -25 °C normal
.. .
.. .
9 -05°C small
In order to shorten the heating-up period after a reduced
temperature period, the flow temperature can be increased
temporarily.
If a room sensor is installed the boost stops, when the
optimisation period is over or the room temperature has
been reached.
Extended service
Set the percentage at which you want the flow
temperature to be increased temporarily.
Service parameter 12
32c 32d
The grey
side of the
ECL Card
The grey
side of the
ECL Card
12 Boost
Setting range Factory setting
0 ... 99 % 0%
Shortens the heating-up period by increasing the flow
temperature by the percentage you set.
14 Optimising time constant
Setting range Factory setting
OFF / 10 ... 59 OFF
Optimises the start and stop times for the reduced
temperature period to obtain the best comfort at the
lowest energy consumption.
15 Adaptive function of room temperature
Setting range Factory setting
OFF / 1 ... 30 OFF
Controls how fast the room temperature adapts to the
desired temperature.
Extended service
Set the anti-blocking function to ON or OFF.
ON: The pump is switched on for 1minute
every third day.
OFF: The pump motion is not active.
In district heating systems, you have to choose OFF to
avoid unnecessary heat consumption.
Set the anti-blocking function to ON or OFF.
ON: The valve receives a signal to open and
close every third day.
OFF: The valve motion is not active.
Select actuator type:
ON: Gear motor.
OFF: Thermo actuator.
Service parameters 22-24
Select total stop function:
ON: Total stop function is ON. At total stop the
flow temperature reference is lowered to
10 °C and the minimum setting of the flow
temperature limit of line 2 (see section
22) is overruled in the reduced
temperature period.
OFF: No total stop.
Extended service
Select calculation method:
ON: Calculation based on the room
temperature (only if a room sensor is
used).
OFF: Calculation based on the outdoor
temperature. Use this setting if you have
no room sensor.
Service parameters 20-21
32e 32f
The grey
side of the
ECL Card
The grey
side of the
ECL Card
20 Optimisation based on room / outdoor temperature
Setting range Factory setting
ON / OFF OFF
The optimised start and stop time calculation can be based on
either the room temperature or outdoor temperature.
T
ref
10 °C
Time
Flow temp. ref.
T
ref
T
min
10 °C
Time
22 Pump motion
Setting range Factory setting
ON / OFF ON
Exercises the pump to avoid blocking in periods without
heat demand.
23 Valve motion
Setting range Factory setting
ON / OFF OFF
Exercises the valve to avoid blocking in periods without
heat demand.
21 Total stop
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop during the reduced
temperature period.
24 Gear motor / thermo actuator
Setting range Factory setting
ON / OFF ON
Choose the type of actuator for the valve.
Flow temp. ref.
T
min
Extended service
Set the influence of the min. return temperature
limitation.
If the displayed value does not equal 0, the
function prevents the return temperature from
getting below the setting in line 30.
Influence higher than 0:
The reference for the
flow temperature is increased, when the return
temperature gets below the setting in line 30.
Influence lower than 0:
The reference for the flow
temperature is decreased, when the return
temperature gets below the setting in line 30.
Adjust the adaptive function of the return
limiter. The setting will eliminate the difference
between the accepted and actual return
temperature by integrating the difference and
adjusting the reference for the flow temperature.
OFF: The flow temperature reference will not
be adjusted any further.
1: The flow temperature reference will be
adjusted quickly.
50: The flow temperature reference will be
adjusted slowly.
Service parameters 36-37
When the limit of the return temperature is exceeded, the
controller automatically changes the flow temperature
reference to obtain a set reference of the required return
temperature. The factors for the definite function of the
return limiter are set in lines 35 and 36.
Extended service
Set the acceptable return temperature limit.
Set the influence of the max. return temperature
limitation.
If the displayed value does not equal 0, the
function prevents the return temperature from
getting above the setting in line 30.
Influence higher than 0:
The reference value for
the flow temperature is increased when the
return temperature gets above the setting in line
30.
Influence lower than 0:
The reference value for
the flow temperature is decreased when the
return temperature gets above the setting in line
30.
+
0
_
Influence
Max. limitation > 0
Return limit
Max. limitation < 0
Return temp.
Service parameters 30-35
32g 32h
+
0
_
Influence
Min. limitation > 0
Return limit
Min. limitation < 0
Return temp.
The grey
side of the
ECL Card
The grey
side of the
ECL Card
30 Return temperature limitation
Setting range Factory setting
10 ... 110 °C 50 °C
Set the return temperature you accept for the heating circuit.
35 Return temperature influence - max. limitation
Setting range Factory setting
+/- 0 ... 9.9 -2
How much the flow temperature reference should be influenced.
36 Return temperature influence - min. limitation
Setting range Factory setting
+/- 0 ... 9.9 0
How much the flow temperature reference should be influenced.
37 Adaptive function of return limitation
Setting range Factory setting
OFF / 1 ... 50 25
Controls how fast the return temperature adapts to the
desired temperature.
Example
The return limit is active from 50
o
C.
The influence is set to
-2.
The actual return temperature is 2 degrees too high.
Result:
The flow temperature reference is changed by 2 x
-2 = -4
degrees.
Example
The return limit is active up to 50
o
C.
The influence is set to 2.
The actual return temperature is 2 degrees too low.
Result:
The flow temperature reference is changed by 2 x 2 = 4
degrees.
Normally, the setting in line 36 is 0 in district heating
systems and lower than 0 in boiler systems.
Normally, the setting in line 35 is lower than 0 in district
heating systems and equals 0 in boiler systems.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28