Danfoss ECL Comfort 301 - L32 Operating instructions

Type
Operating instructions
ECL COMFORT
ECL COMFORT
ECL Comfort
Installation and
Maintenance
L32
Heating and cooling controller
VI.BC.VI.02
2004.05
User's Guide
L32
Table of Contents
Sections of the Installers part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections relevant to
your ECL Comfort controller are included here.
Before you start
Installation
10
Identifying the system type
11
Mounting the ECL Comfort controller
12
Electrical connections 230 V a.c.
14
Connecting and placing the temperature sensors
15
Inserting the ECL Card
Basic Set-up
16
Adjusting the ECL Card settings
17
Setting the time and date - Line A
18
Monitoring temperatures and system units - Line B
19
Manual control - Line B
20
Setting the heat curve - Line C
21
Heating cut-in and cut-out - Line 1
22
Flow temperature limits - Line 2
23
Room temperature in uence - Line 3
26
Setting the PI regulation - Lines 4 - 7
Control & Overviews
29
Check list
30
ECL Card settings
31
Service parameters
Extended Service
32
Adjusting the service parameters
Miscellaneous
34
Copying with the ECL Card
Daily use,
turn the guide over for sections 1-7
1
Choose your favourite display
2
Select controller mode
3
Adjust your room temperature
4
Set your personal day plan
5
Advantages of the ECL Card
6
Hot points
7
De nitions
Table of Contents
Daily use
Section
1
Choose your favourite display
2
Select controller mode
3
Adjust your room temperature
4
Set your personal day plan
5
Advantages of the ECL Card
6
7
Hot points
De nitions
The documentation for the ECL Comfort controller is composed of
numbered sections. Only sections that are relevant to your ECL Comfort
controller are included here.
Installation and maintenance.
Grey sections 10 and onwards.
Turn the guide over.
Your personal week plan:
This guide is associated to ECL Card 087B4854
Installer:
By:
Date:
*087B4854*
*vibcvi02*
*087B4854*
*vibcvi02*
Note!
The functions can only be realized with ECL Comfort 301 - and as
of ECL Card version CI05 and controller version 2.03.
Day plan II
0
3
6
9
12
15
18
21
24
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
Factory settings are grey
Comfort
0
3
6
9
12
15
18
21
24
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
A
B
C
1
2
3
4
5
6
7
The shown diagram is a fundamental and simpli ed example
and does not contain all components that are necessary in a
system.
If the system you are about to install di ers from the shown
diagram of a standard heating system, feel free to sketch an
outline for comparison. Adaptation of systems, see section 10.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
+ 1
Override cooling
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
circuit I and II.
Circuit indicator
Circuit
selector
Shift
button
Adjustment
Controller
mode
Room temperature
System information
Today's program
Day plans

A
Line indicator
Line indicator
Circuit
A
5 036
B
1
1
ON
2
ON
2
3
ON
-

--


-
    
    
1
2
3
4
0 3 6 9 12 15 18 21 24
5
1
2
3
4
6
0 3 6 9 12 15 18 21 24
0
5
0
6
8
0 3 6 9 12 15 18 21 24
0
7
0
6
8
0 3 6 9 12 15 18 21 24
0
7
0
The ECL Card
For daily use and your personal adjustments, the yellow side of
the ECL Card must face you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Heating / cooling - circuit I
Circuit II
The circuit indicator
shows the selected circuit.
List of components:
ECL Comfort 301
S1
Outdoor temperature sensor
S2
Room temperature sensor
S3
Flow temperature sensor
S4
Surface temperature sensor
P1
Circulation pump
M1
Motorized control valve
V1
Heating cut-in / cut-out
V2
Cooling cut-in / cut-out
The ECL Card: Installers instruction
The grey side of the card must face you
when you change settings. For daily
use and during start-up the yellow side
of the card must face you.
8
9
10
199
Extended service parameters,
see section 31.
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Heating / cooling operation
Constant reduced temperature
Standby mode
+ 1
Override cooling
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
circuit I and II.
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller series is designed by Danfoss for
temperature control of heating, hot-water, ventilation and
cooling systems.
The ECL Comfort controller ensures you of the following;
Room, hot-water, ventilation or cooling temperatures will
be adjusted to your personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy resources.
Sketch your application
The ECL Comfort controller series is designed for a wide
range of heating, hot-water, and cooling systems with
di erent con gurations and capacities.
If your system di ers from the diagrams shown in section
10, you may want to make a sketch of the system about to
be installed. This makes it easier to use the Installers Guide,
which will guide you step-by-step from installation to  nal
adjustments before the end-user takes over.
The controller is pre-programmed with factory settings that are
shown in the relevant sections of this guide.
However, you might come across some settings that are not listed
in this instruction. These settings could be related either to recent
updates or the use of optional modules (which are described in
the instructions in question).
How to use this guide
This guide is divided into two parts:
Users Guide (turn the guide over)
Yellow sections 1-7
Installation and Maintenance:
Grey sections 10 and onwards
Basic principles of the L32 application
Typical use:
Typically the  ow temperature is always adjusted according to
comfort requirements. The colder it gets outdoor, the higher
the  ow temperature of the  oor circuit will be. When heating
is required, the heat generator (which typically is the boiler) is
activated.
When the outdoor temperature increases and heating operation
no longer is required, the controller can switch to cooling.
Chilled water is then circulated in the system to keep the room
temperature on the comfort level. When cooling is required,
the cooling generator (a water chiller) is activated. The  ow
temperature is controlled with due consideration to the air
humidity. The controller avoids condensation on the  oor.
Humidity and room temperature are measured by the remote
control ECA 63.
Program for the drying of  oor pavement:
A special program for the drying of newly made concrete  oor
pavement can be activated. For 3 days the  oor temperature will
typically be held at 25
o
C and for the next 4 days typically at
50
o
C. In section 32 you can read more about activation, advice
and settings.
Before you start
VI.BC.VI.02
Card L32
2004.05
Installation
The ECL Comfort controller is a universal controller that can
be used for various systems. Based on the shown standard
systems, it is possible to con gure additional systems.
In this section you  nd the most frequently used systems. If
your system is not quite as shown below,  nd the diagram
which has the best resemblance with your system and make
your own combinations.
The systems can only be realized with ECL Comfort 301 - and as of
ECL Card version CI05 and controller version 2.03.
10.1
Heating / cooling considering dew point and
surface temperature (
typical system)
System settings
Circuit
Line
Description
I
1
Limit for heating cut-in / cut-out
I
24
Gear motor / thermo actuator
I
56
Surface temperature limitation during cooling
I
60
Surface temperature limitation during heating
I
64
Max. limitation of  ow temperature during
heating
I
81
-82
Accumulation constants, outdoor and room
temperatures
I
156
-157
Activation / deactivation of cooling, outdoor
and room temperatures
System diagrams in this instruction are principal drawings and do
not contain all components which are necessary in your systems.
Identifying the system type
10a
Installation
10b
10.2
Weather compensated heating. Room and
surface temperature sensors can be connected
(simple system)
System settings
Circuit
Line
Description
I
1
Limit for heating cut-in / cut-out
I
24
Gear motor / thermo actuator
I
(57)
Surface temperature limitation during cooling
I
64
Max. limitation of  ow temperature during
heating
I
81
-82
Accumulation constants, outdoor and room
temperatures
10.3
Heating and cooling operation irrespective of
dew point and surface temperature
System settings
Circuit
Line
Description
I
1
Limit for heating cut-in / cut-out
I
24
Gear motor / thermo actuator
I
60
Surface temperature limitation during heating
I
64
Max. limitation of  ow temperature during
heating
I
81
Accumulation constants, outdoor temperature
I
156
Activation / deactivation of cooling, outdoor
temperature
Installation
For easy access, you should mount the ECL Comfort
controller near the system. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the  xing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 93 x 139 mm. Pull o
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and  x it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting the ECL Comfort
controller
11a
Installation
11b
Installation
12a
Typical circuit diagram
Establish these jumpers:
Jumper from 1 to 5 - jumper from 5 to 8 - jumper from 8 to
10 - jumper from 10 to 12 - jumper from 12 to 14 - and jumper
from 2 to common N-terminal.
If the ECA 80 relay module is applied, jumpers 14 to 26 and 26
to 29 also need to be established.
Simpli ed circuit diagram
Establish these jumpers:
Jumper from 1 to 5 - jumper from 5 to 8 - jumper from 8 to
10 - jumper from 10 to 12 - jumper from 12 to 14 - and jumper
from 2 to common N-terminal.
Circuit diagram with dehumidi er
Establish these jumpers:
Jumper from 1 to 5 - jumper from 5 to 8 - jumper from 8 to 10
- jumper from 10 to 12 - jumper from 12 to 14 - jumper from
14 to 26 - jumber 26 to 29 and jumper from 2 to common
N-terminal.
Electrical connections -
230 V a.c.
Heating
Signal
Signal
Outdoor
/cooling
zone 1
zone 2
temp. OFF
Optional
Output R5 is active as humidistat, see section 32, lines 78-80.
Heating
Signal
/cooling
zone 1
Heating
Signal
Signal
/cooling
zone 1
zone 2
Dehumidi er
Dehumidi er
Optional
Installation
Terminal
Description
Max. load
1
(L)
Voltage supply
230 V a.c.
2
(N)
Voltage supply
230 V a.c.
3
(M1)
Gear motor - open
max. 0.2A / 230 V a.c.
4
(M1)
Gear motor - close
alternative: ABV thermo
actuator
max. 0.2A / 230 V a.c.
5
230 V a.c. supply for M1
6
Output signal for heating
V.1 (active during heating
operation)
max. 0.2A / 230 V a.c.
7
Output signal for cooling
V.2 (active during cooling)
max. 0.2A / 230 V a.c.
8
230 V a.c. supply for
output signal
9
Circulation pump (P1)
4(2) A / 230 V a.c.
10
(R1)
230 V a.c. supply for pump
output R1
11-12
(R2)
Signal, heating / cooling,
closed: cooling operation
open: heating operation
4(2) A / 230 V a.c.
13-14
(R3)
Signal, normal / reduced
operation,
closed: reduced operation
open: comfort operation
4(2) A / 230 V a.c.
ECA 80
24-
25-26
(R4)
Follows R2 or time
program 2, see line 84
4(2) A / 230 V a.c.
27-
28-29
(R5)
Outdoor temperature
dependent switch or
humidistat, see line 78
4(2) A / 230 V a.c.
Wire cross section:
0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminal 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
12b
Option:
Relay module ECA 80 (contacts max. load 4(2) A / 230 V a.c.)
25-26: Relais R4 complies with relay R2 directly (heating / cooling).
Closed:
Reduced operation
Open:
Comfort operation
Installation
14a
Connecting and placing the
temperature sensors
Connecting the temperature sensors and the bus
*
Activation: see setting in line 10
**
If the remote control (ECA 60, 61 or 63) is connected, this input has
no function
Establish the jumper from 16 to common terminal.
Wire cross section for sensor connections:
Min. 0.4 mm
2
Total cable length:
Max. 125 m (all sensors incl. system device bus)
Note:
Cable lengths of more than 125 m may cause noise sensibility
(EMC).
Connecting the room panel / remote control
The ECA 60-63 is powered by the system device bus which means
that the bus must be active.
The bus is activated by connecting the outdoor temperature
sensor. See also line 199.
Terminal
Description
Type
(recomm.)
15 and 16
System device BUS,
Room panel*
Room panel (incl. humidity
sensor)*
Remote control*
Remote control (incl.
humidity sensor)*
ECA 60
ECA 62
ECA 61
ECA 63
17 and 16
S1
Outdoor temperature
sensor
ESMT
18 and 16
S2
Room temperature sensor**
ESM-10
19 and 16
S3
Flow temperature
sensor
ESMU/ ESM-11/
ESMC
20 and 16
S4
Surface temperature sensor
ESMB-12
Installation
It is important that the sensors are mounted in the correct
position in your system.
The temperature sensor mentioned below are sensors used
for the ECL Comfort 200 and 300 series which not all will be
needed for your application!
Outdoor temperature sensor (ESMT)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows or
air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends that the
ESMU-type to be inserted into the exchanger  ow outlet.
Make sure that the surface of the pipe is clean where the
sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return sensor should always be placed in / on a pipe with
return water  ow.
Room temperature sensor (ESM-10, ECA 60 / ECA 62
room panel or ECA 61 / ECA 63 remote control)
Place the room temperature sensor in the room where the
temperature is to be controlled. Do not place it on outside
walls or close to radiators, windows or doors.
Hot-water temperature sensor (ESMU or ESMB)
Place the hot water sensor according to the
manufacturers speci cation.
Boiler temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturer’s
speci cation.
Flow / air duct temperature sensor (ESM-11, ESMB,
ESMC or ESMU types)
Place the sensor close to the exchanger.
Surface temperature sensor (ESMB-12)
Place the sensor in the surface of the  oor.
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
14b
Installation
Override inputs
Terminal
Description
21 and 16
Day plan override.
Closed contact: Switch to comfort operation
22 and 16
Circulation pump override.
Closed contact: The pump is switched OFF.
Open contact: The pump function is normal
The override function is not active if the controller mode is set to
“Standby” or “Manual operation”.
Connection example with ECA 9010:
If a good override switch (with gold-plated contact surfaces)
ist not available, it is necessary to make use of an override
module.
14c
Installation
Installation
How to insert your ECL Card the  rst time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data. The
controller immediately starts to copy the system type and
factory settings from the ECL Card. After copying, the display
will show the system type the controller is set to control. After
approx. 10 sec. the display will change to display line C.
Display examples:
C
C 99
Y
0
P
C 73
08 108
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
Application type
Software version,
controller
Software version,
ECL Card
Line
Circuit
Time
Outdoor
temperature
Desired room
temperature
The controller is now ready to be set to control your system.
Inserting the ECL Card
15a
Installation
15b
Understanding the ECL Card
The ECL Card contains factory settings for a standard
system. If the actual system di ers from the standard
system, the controller must be adjusted accordingly. After
the adjustment, the new settings should be stored on the
ECL Card.
For ECL Card copying and daily use including adjustment of
temperatures and time periods, insert the ECL Card with the
yellow side facing you.
For system set-up adjustments, the grey side of the ECL
Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in the
controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings cannot be changed after approx.
25 min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the system you can
write a title on the ECL Card with a permanent ink pen.
Do not remove the ECL Card while copying!
When you store your personal settings on your ECL Card, your
factory settings will be overridden.
The grey
side of the
ECL Card
Basic set-up
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the grey
side of the ECL Card (see the example below).
Use the arrow buttons to move from line to line of
the ECL Card, for example line 2:



Circuit
Line
Settings to be
adjusted
Value in range
indicator
Use the plus / minus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually.
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details
about copying, see section 34.
Adjusting the ECL Card
settings
16
The grey
side of the
ECL Card
Basic set-up
Go to line A.
05
01
2 220
5
A
3
1
Actual time
Year
Month, day
Use the shift botton to switch between minutes,
hours, years, months and days.
Set the correct time and date.
In case of a power break, which lasts longer than 12 hours, the
time and the date have to be set again. All other settings are
stored as programmed.
Use the yellow side of the card to enter the day plan settings.
See User’s Guide, section 4.
Setting the time and date -
line A
17
The grey
side of the
ECL Card
Basic set-up
Go to line B.
5
1 2
036
B
3
ON
1
ON
2
ON
Flow temperature
Surface temperature
State indicator
Controlled units
Push the shift button to see:
- the calculated  ow temperature
- the desired return temperature limitations.
The activity of the motorized control valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display will
indicate it as “- -”.
If the sensor is short-circuited, the display will indicate
it as “- - - “.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 7
5 100 125 150
˚C
808
846
884
921
961
1000
1039
1078
1117
1155
1194
1232
1271
1309
1347
1385
1423
1462
1501
1539
1578
˚C
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
Monitoring temperatures
and system units - line B
Monitoring temperatures
and system units - line B
Monitoring temperatures
18
The grey
side of the
ECL Card
Basic set-up
Go to line B.
Shift to manual mode.
5
1 2
036
B
3
ON
1
ON
2
ON
Controlled
Controller
units
mode
Choose the unit you want to control. The selected
unit symbol will  ash.
Controlled units are switched
OFF or
ON
ON
when the relevant button is pushed.
The motorized actuator (gear motor /
damper)
closes
or opens
the controlled unit as long as
the relevant button is pushed. If pushed for more
than 3 seconds, the actuator remains active.
The thermo actuator
activates
the valve as long as the
button is
pushed. If pushed for more than 3 seconds, the
actuator remains active.
Check the activation direction of the actuator either by
looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits, if available.
During manual operation, all control functions are deactivated.
Manual control -
line B
19
The grey
side of the
ECL Card
Basic set-up
Go to line C.
The symbol for the slope of the heat curve will
ash.
1 2
8
C
0
0
3
ON
1
ON
2
ON
Slope
Displacement
Slope
Circuit
Setting range
Factory setting
I
0.2 ... 3.4
1.8
Adjust the slope of the heat curve, if required.
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
How to determine another heat curve, if necessary:
Choose the calculated  ow temperature for your system and
the determined min. outdoor temperature for your area.
Pick the heat curve closest to the crossing point of these two
values.
The setting of the desired room temperature has an in uence
on the calculated  ow temperature (heat curve), no matter if a
room temperature sensor is connected or not.
Floor heating systems
This controller is factory set for radiator systems, which typically
are high  ow temperature systems.
To control  oor heating systems, which typically are low  ow
temperature systems, you need to change the heat curve
according to your type of system.
Slope
Circuit
Setting range
Typical setting
I
0.2 ... 3.4
1.0
Setting the heat curve -
line C
Setting the heat curve -
line C
Setting the heat curve -
20a
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Danfoss ECL Comfort 301 - L32 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI