Simplex SafeLINC 4020 Installation Instructions Manual

Category
Fire protection
Type
Installation Instructions Manual
aSimplex
4020 Fire Alarm System
Contractor‘
Installation Instructions
.
0 1995 Simplex Time Recorder Co.
FA4-21-400 (574-061)
All specifications and other information shown were current as of publication. and are subject to change without notice.
Ed 1 95
Technical Manuals Online! - http://www.tech-man.com
NOTICE
FIRST TIME INSTALLERS OF SIMPLEX 4020 FIRE ALARM PANELS
AFTER READING THE INFORMATION CONTAINED IN THIS MANUAL, CALL YOUR LOCAL
SIMPLEX REPRESENTATIVE BEFORE PROCEEDING TO CONNECT FIELD WIRING!
NOTICE
FOR POWER-LIMITED SYSTEMS: THE 4020 PANEL HAS INTERNAL BARRIERS TO PREVENT
CONTACT BETWEEN POWER-LIMITED AND NON-POWER-LIMITED CONDUCTORS. THE AREA
IN THE RIGHT AND BOTTOM OF THE PANEL IS RESERVED FOR NON-POWER-LIMITED WIRING
DO NOT APPLY AC OR
BAlTERY POWER TO THE 4020
SYSTEM (UNLESS IN THE
PRESENCE OF A SIMPLEX
TECHNICAL REPRESENTATIVE)
I
Technical Manuals Online! - http://www.tech-man.com
TABLE OF CONTENTS
PAGE
Introduction
................................................................................................................................................................
1
Supplied
Documentation
.....................................................................................................................................
1
Installation
Procedure ................................................................................................................................................
1
Inventory
the Delivered
Equipment
....................................................................................................................
.l
Install
the Back Box.. ...........................................................................................................................................
2
Mount the
Electronics
Into the Back Box.. ..........................................................................................................
.2
Install
and Tag All System
Wiring..
.....................................................................................................................
.2
Install
the Peripheral Devices
and E.O.L.
Resistors.. .........................................................................................
.3
MAPNET II@ Address
Chart.. ........................................................................................................................
4
Check
and Terminate All
Field Wiring
................................................................................................................
.5
Neatly
Dress the Panel
Wiring ............................................................................................................................
7
Install
the Retainer ..............................................................................................................................................
7
Install
the Panel Door..
........................................................................................................................................
7
Install
the Door Bumpers..
...................................................................................................................................
7
Ground
the Door to the
Back Box ......................................................................................................................
.7
Close
and Lock the Panel
Door.. .........................................................................................................................
7
Call Simplex ........................................................................................................................................................
7
FIGURES
FIGURE
PAGE
1
4020 Panel Layout
.....................................................................................................................................
2
2
Location of DIP Switches
on
Sensor
Base..
..............................................................................................
.4
3 Device Address Label
................................................................................................................................
4
4
Field Wiring Terminal Locations
................................................................................................................
.5
5
Internal Routing
of Power-Limited and Non-Power-Limited
Wiring..
.........................................................
.6
6
Acceptable Zone and Signal Circuit Meter Readings..
..............................................................................
.7
i
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
CONTRACTOR INSTALLATION INSTRUCTIONS
> I
: i
r:Y
2 “a
*
: :
* IMPORTANT * IMPORTANT * IMPORTANT *
* .”
- :,
. :
:I
::
1x
I
=dc
1N.A CLEAN, DRY, AND SAFE PLACE UNTIL NEEDED.
- “,
_”
*****************it**
_
_’
/
;I)
* (
SYSTEM IS BEING INSTALLED.
INTRODUCTION
This publication provides a logical sequence of procedures to follow when installing a 4020 system. Throughout this
publication, you are often referred to the documentation listed below. In such cases, notes describing use of the
documents will generally follow immediately.
Supplied Documentation
The envelope that contained this publication also contains the following documents:
4020 Fire Alarm Back Box - Installation Instructions (FA4-21-404)
Field Wiring Diagram, 4020 (84 l-842)
l
Wiring diagrams for specific devices are included with the devices.
4020 Fire Alarm - Operating Instructions (FA4-31-401)
Except for the last publication, all of the above documents are required for system installation.
Note:
If you are unfamiliar with fire alarm system wiring, you can order a publication entitled How to Wire a Building
for a Fire Alarm System (Pub No. FA2-91-001) from Simplex.
INSTALLATION PROCEDURE
Note:
If possible, proceed through the installation process in the sequence that follows.
1. Inventory the delivered equipment.
Note:
In addition to the envelope that contained this publication, supplied 4020 material includes an envelope
containing installation hardware.
l
When you are required to use installation hardware during a system installation procedure, that fact is
noted at the start of the procedure.
Technical Manuals Online! - http://www.tech-man.com
2. Install the back box.
l
See accompanying document entitled 4020 Fire Alarm Back Box lnsfallation Instructions.
. Note the restrictions for routing of Power-Limited Wiring (see Figure 1).
Note:
The installation hardware envelope contains the panel keys.
3. Mount the electronics into the back box.
l
See Figure 1 for panel layout.
l
Connect the ground (green) wire from the CPU bay to a grounding screw on the back box.
l
Per article 250 of the National Electrical Code, a dedicated equipment ground conductor must connect to the
other grounding screw
(consult NEC Table 250 for conductor size).
CPU BAY z
CPU/EXPANSION BAY-
INTERCONNECTION
PLUG
EXPANSION BAY -
Figure 1
4020 Panel Layout
\
GROUNDING
SCREWS
NON-POWER-LIMITED FIELD WIRING
E IN SHADED AREA.
POWER-LIMITED FIELD WIRING ONLY
IN NON-SHADED AREA.
4. Using the SYSTEM POINT SUMMARY (supplied by your local Simplex Rep.) and the appropriate pages
in the enclosed 4020 Field Wiring Diagram, connect terminals and tag all system wiring.
General Notes
A.
The index for the 4020 Field Wiring Diagram is found on the document’s first page.
B.
The 4020 Field Wiring Diagram includes pages titled “4020 Precautions for Wiring.”
C.
At both ends of each circuit, tag wires with I/O terminal number or MAPNET@ channel number and polarity (if
polarity applies).
l
For example, I/O 4+ and I/O 4-.
D.
T-tapping is permitted only for Style 4 (formerly Class B) MAPNET II@ circuits.
2
Technical Manuals Online! - http://www.tech-man.com
________________________________________-..-----------------------------------------------------------.-----------------------------
22145559 rev: 1
SYSTEM POINT SUMMARY Page 4
15:36:30, FRI, 06-MAR-92
POINT SUMMARY
System Point Summary (ascending by zone name): ZONE
Zone Name Custom Label
___-----_____-.
________________________________________---------------------
101
CENTER HALLWAY
102
NORTH HALLWAY
103 SOUTH HALLWAY
104 ALL SIGNALS
Ml-l PRINCIPALS OFFICE
Ml-2 CAFETORIUM
Ml-3 KITCHEN
. .
.
M;-37
.
.
JANITORS CLOSET
Point
Tw=
PULL
PULL
PULL
SSIG
SMOKE
SMOKE
HEAT
.
.
.
HEAT
Device
PNIS
Tn=e
Code
__________ _________________-___
ADRDET
ADRDET
MBZAM
.
.
.
MBZAM
Note:
Land zone 101 on terminal block I/O 1; land zone 102 on terminal block I/O 2; etc.
5. Install the peripheral devices and E.O.L. resistors.
Note 1:
The installation hardware envelope contains the required resistors.
l
3.3K resistors are color coded orange, orange, red (and have a gold tolerance band); 1 OK resistors
are color coded brown, black, orange (and also have a gold tolerance band).
l
Resistors other than those described above will be used by the Simplex Rep during installation
checkout.
Note
2: Except for devices that connect to MAPNET II@ channels (devices named Ml -1, M2-15, etc.), wire
peripherals in accordance with the appropriate 4020 Field Wiring Diagram (84 7-842).
l
Wire a MAPNET II@ device in accordance with the diagram that accompanies the device.
THEN SET
THE DEVICE’S ADDRESS SWITCHES (see Figure 2 on page 4).
Note
3: A MAPNET II@ device’s address is represented by the final digit(s) in the zone’s name.
Examples:
The device that connects to a zone named Ml -2 must have its switches set to address
2; the device that connects to a zone named Ml -117 must have its switches set to
address 117.
l
See page 4 for a complete listing of MAPNET II@ addresses.
Note
4: Use a small screwdriver or ball point pen to set device address switches.
Note
5: After setting the device address, mark the device’s address label to agree with the address switches
(see Figure 3 on page 4).
3
Technical Manuals Online! - http://www.tech-man.com
DIP SWITCHES
Address Label
(Marked for Address 5)
Figure 2
Location of DIP Switches
on Sensor Base
Figure 3
Device Address Label
MAPNET II@ Address Chart
Note
1: Address zero (all switches turned OFF) is not a valid address.
Note 2:
Switch number 8 is never turned ON.
SWl-1
SW,-2 SW,-3 SW14 SW14 SW,-5 SW,-7 SW,-8
ON OFF OFF OFF
OFF OFF OFF OFF = ADDRESS 1
0 = OFF
n = ON
Technical Manuals Online! - http://www.tech-man.com
6. Check and terminate ail field wiring (see Figure 4 for terminal ‘locations).
a. Check each circuit for voltages, shorts, or opens as follows:
1. With the meter set on 3OOVAC, read the voltage across the circuit.
Meter must read 0 volts.
2. With the meter set on 60 VDC, read the voltage across the circuit again (this time in both directions).
Meter must read 0 volts.
3. With the meter set on OHMS x 10 and its (+) and (-) leads connected to the circuit’s (+) and (-) wires,
respectively, check resistance.
l
Readings must compare favorably with those shown in Figure 6 (see page 7).
Note:
if reading indicates an open in a circuit that includes a smoke detector, make sure the detector
head(s) are properly mounted and seated.
l
Circuits always read “open” (infinity) if detector power is absent and separately-powered
devices (four-wire smoke detectors) are involved.
b. Connect the wires to their terminals
in accordance with the SYSTEM POINT SUMMARY and the
appropriate field wiring diagrams.
c. For Power-Limited systems,
you must not route Power-Limited field wiring in the shaded areas of
Figures
4 (see Figure 5 for routing information).
INPUT POWER TERMINALS
(REMOVE COVER FOR ACCESS)
DooR GRoUND MAPNET” CHANNEL 1
\ \
INPUT POWER GROUND
COMM, CITY, TEL
(Ml-1 THRU M-127)
(120124j VAC)
‘THRU l/O12
I
I/O 17 THhJ I/O 20
I
I/O 13 THRU I/O 16 I/O 21 THRU I/O 24
I/O 1 THRU I/O 4
MAPNET@ CHANNEL 2
W-1
THRU M2-127)
Figure 4
Field Wiring Terminal Locations
5
Technical Manuals Online! - http://www.tech-man.com
d. Use Figure 5 as a reference when routing field wiring inside a 4020 panel for Power-Limited Systems. Use
the top left and left-side knockouts for Power-Limited wiring only. The right-side knockouts are reserved for
Non-Power-Limited wiring. Use additional knockouts when needed.
CONDUIT ENTRANCE
FOR POWER-LIMITED
WIRING
POWER-LIMITED
WIRING
SEE NOTES 2 & 3
c
TIE WRAP
/ /WIRING
CONDUIT ENTRANCE
FOR NON-POWER-
LIMITED WIRING
/
NON-POWER-LIMITED
I
1
TIE POINT
TERMlNATlON
SEE NOTE 3
Figure 5
internal Routing of Power-Limited and Non-Power-Limited Wiring
Notes:
1. Non-power limited field wiring (AC power, Battery Wiring, City Connection) must be installed and routed in the
shaded area only.
2. Power limited field wiring (all connections in the unshaded area except the city) must be installed and routed as
shown.
3. Keep slack to a minimum inside the enclosure. Using tie wraps (supplied), neatly dress and bundle the wiring
together. Anchor power-limited wiring to the tie points.
4. Tie the wiring located between the bays to the internal wiring troughs (if applicable.)
5. When switching power through relay contacts, power for these circuits must be provided by the system power
supply that is listed for Fire Protective Signaling use.
Technical Manuals Online! - http://www.tech-man.com
CIRCUIT TYPE
METER READING
Style B
Style D
Style Y
Style Z
(formerly Class B) Initiating Device (Zone) Circuit
From zone + to zone - (each zone)
From zone + to ground
From zone -to ground
(formerly Class A) initiating Device (Zone) Circuit
From zone + to zone - (each zone)
From zone + to ground
From zone -to ground
From zone + to + A
From zone - to - A
(formerly Class B) Notification Appliance Circuit
(each signal circuit)
From + to ground
From -to ground
Resistance across circuit
In one direction
In opposite direction
(formerly Class A) Notification Appliance Circuit
(each signal circuit)
From + to ground
From -to ground
From + to + A
From-to-A
Resistance across circuit
In one direction
In opposite direction
3.3K ohms
Infinity
Infinity
Infinity
Infinity
Infinity
Less than 50 ohms
Less than 50 ohms
Infinity
Infinity
1 OK ohms
Less than 200 ohms
Infinity
Infinity
Less than 50 ohms
Less than 50 ohms
Infinity
Less than 200 ohms
Infinity
Infinity
More than 50K ohms
More than 50K ohms
More than 50K ohms
Shielding
(twisted shielded pair wiring)
From OV to ground
From OV COMMON to ground
MAPNET ii@ Loops
(ZAMs, and IAMs)
From MAPNET@ + to ground
From MAPNET@ -to ground
Style D (formerly Class A) Monitor ZAMs
(6wire detectors)
Figure 6
Acceptable Zone and Signal Circuit Meter Readings
7. Neatly dress the panel wiring.
8. install the retainer.
9. install the panel door.
10. Using the two adhesive disks and the two rubber bumpers (from the hardware envelope), affix the
bumpers to upper and lower left-hand corners of the door.
11. Using the green wire from the hardware envelope, ground the upper right-hand corner of the door to the
back box.
12. Close and lock the panel door.
13. Call your local Simplex Branch Office (listed in the yellow pages) to check out, test, and program the
system.
* l l DO NOTAPPLY AC OR BATTERY POWER TO THE SYSTEM l * *
7
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
BeSimplex
Simplex Plaza
l
Gardner, Massachusetts 01441-0001 U.S.A.
FA4-21-400
(574-061)
1
Technical Manuals Online! - http://www.tech-man.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Simplex SafeLINC 4020 Installation Instructions Manual

Category
Fire protection
Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI