4010

Simplex 4010 User manual

  • Hello! I am an AI chatbot trained to assist you with the Simplex 4010 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
4010 Fire Alarm
Service Manual
579-081
Rev. A
Technical Manuals Online! - http://www.tech-man.com
This Page is intentionally blank
Technical Manuals Online! - http://www.tech-man.com
Copyright Simplex Time Recorder Co., 1999. All rights reserved.
Printed in the United States of America.
Information in this document is subject to change without notice. No part of this
document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written consent of
Simplex Time Recorder Company.
Walk Test is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet is patent pending.
TrueAlarm Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To
ensure proper system operation, this product must be tested in accordance with
NFPA72-1996, Chapter 7 after any programming operation or change in site-
specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, repair or adjustment
to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the
installation, operating and programming manuals. These instructions must be
followed to avoid damage to the control panel and associated equipment. Fire
Alarm Control Panel (FACP) operation and reliability depend upon proper
installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. It has
been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
Copyright and Trademarks
Cautions and Warnings
Technical Manuals Online! - http://www.tech-man.com
The 4010 is listed for the following.
UL 864 Listings for Type of System:
UL 864 Power-Limited Fire Alarm Control Unit
Local (formerly NFPA 72A)
Requires the sounding of an alarm via listed notification appliance(s)
Auxiliary (formerly NFPA 72B)
Requires 4010-9809 City Circuit Module
Remote Station - protected premise (formerly NFPA 72C)
Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT
Proprietary - protected premise (formerly NFPA 72D)
Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network
Interface Modules
Central Station - protected premise (formerly NFPA 71)
Requires 4010-9810 or -9816 DACT
Suppression Releasing Service
Requires 4010-9814 Suppression Kit
UL 864 Listings for Type of Service:
Automatic, Manual, Waterflow, and Sprinkler Supervisory
UL 864 Listings for Type of Signaling:
Coded, Non-Coded, March-Time and DACT
DACT requires the 4010-9810 or -9816
Factory Mutual Approved
Same as UL above
Local Approvals
CSFM
MEA
Continued on next page
Codes and Standards
Technical Manuals Online! - http://www.tech-man.com
The installer should be familiar with the relevant codes listed below as well as
any other applicable local codes and standards, when installing a fire alarm
system.
NFPA 72 National Fire Alarm Code
NFPA 11 Standard for Low-Expansion Foam and Combined Agent
Systems
NFPA 11A Standard for Medium- and High-Expansion Foam Systems
NFPA 12 Standard on Carbon Dioxide Extinguishing Systems
NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems
NFPA 13 Standard for the Installation of Sprinkler Systems
NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection
NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler
and Foam-Water Spray Systems
NFPA 16A Standard for the Installation of Closed-Head Foam-Water
Sprinkler Systems
NFPA 17 Standard for Dry Chemical Extinguishing Systems
NFPA 17A Standard for Wet Chemical Extinguishing Systems
NFPA 25 Standard for Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
NFPA 70 National Electrical Code
NFPA 80 Standard for Fire Doors and Fire Windows
NFPA 90A Standard for the Installation of Air Conditioning and
Ventilation Systems
NFPA 90B Standard for the Installation of Warm Air Heating and Air
Conditioning Systems
NFPA 92A Recommended Practice for Smoke-Control Systems
NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and
Large Areas
NFPA 101 Life Safety Code
NFPA 170 Standard for Fire Safety Symbols
NFPA 231C Standard for Rack Storage of Materials
NFPA 1221 Standard on the Installation, Maintenance, and Use of Public
Fire Service Communication Systems
Codes and Standards
(continued)
Technical Manuals Online! - http://www.tech-man.com
This page is intentionally blank
Technical Manuals Online! - http://www.tech-man.com
v
Chapter 1. Power Up Flowcharts
Introduction............................................................................................... 1-1
In this Chapter........................................................................................... 1-1
Initial Power Up Flow Chart......................................................................... 1-2
AC Power Flowchart..................................................................................... 1-4
Chapter 2. Interpreting Trouble Messages
Introduction............................................................................................... 2-1
In this Chapter........................................................................................... 2-1
NAC Troubles............................................................................................... 2-2
Power Supply Troubles................................................................................. 2-4
IDNet Troubles ............................................................................................. 2-8
RS-232 / Modem Troubles.......................................................................... 2-11
SDACT Troubles ........................................................................................ 2-12
Network Troubles ....................................................................................... 2-13
24 Point I/O Troubles ................................................................................. 2-14
LCD Troubles ............................................................................................. 2-15
4009 IDNet NAC Extender Troubles.......................................................... 2-16
Digital Pseudo Point Troubles .................................................................... 2-17
Chapter 3. Crash Codes
Introduction............................................................................................... 3-1
In this Chapter........................................................................................... 3-1
Summary of Crash Codes ............................................................................. 3-2
Appendix A. Compatibility Matrix
Introduction.............................................................................................. A-1
In this Appendix....................................................................................... A-1
Determining Compatibility between Versions 1 and 2 ................................ A-2
Introduction.............................................................................................. A-2
Using the Version 2.x Programmer with Version 1.x Jobs...................... A-3
Table of Contents
Technical Manuals Online! - http://www.tech-man.com
vi
Appendix B. Power Supply Adjustment and
Troubleshooting
Introduction.............................................................................................. B-1
In this Appendix....................................................................................... B-1
Adjusting the AC Power Supply Brownout Potentiometer.......................... B-2
Overview.................................................................................................. B-2
Using a Variac to Adjust the Brownout Potentiometer............................ B-2
Checking AC Power Supply Transformer / Bridge Rectifier....................... B-3
Checking DC Voltage at H1 and H2........................................................ B-3
Checking Connectors............................................................................... B-3
Replacing the Line Voltage Transformer and Bridge Rectifier ............... B-5
Checking EPS Transformer / Bridge Rectifier............................................. B-6
Introduction.............................................................................................. B-6
Checking DC Voltage from EPS Bridge Rectifer.................................... B-6
Checking Connectors............................................................................... B-7
Replacing the EPS Line Voltage Transformer and Bridge Rectifier ....... B-8
Appendix C. Diagnostic Utilities, Basic Service
Procedures, and Known Solutions
Introduction...............................................................................................C-1
In this Appendix........................................................................................C-1
N2 Comm Diagnostics..................................................................................C-2
Procedure ..................................................................................................C-2
IDNet Diagnostics.........................................................................................C-3
Procedure ..................................................................................................C-3
Duplicate Devices .....................................................................................C-3
Weak Answer Devices..............................................................................C-3
IDNet Earth Fault Search Diagnostics ..........................................................C-4
Procedure ..................................................................................................C-4
Network Diagnostics.....................................................................................C-5
Network Diagnostics.................................................................................C-5
Walk Test......................................................................................................C-6
Overview...................................................................................................C-6
Using Walk Test .......................................................................................C-6
Important Notes ........................................................................................C-6
TrueTest........................................................................................................C-7
Overview...................................................................................................C-7
Using TrueTest .........................................................................................C-8
Basic Service Procedures..............................................................................C-9
Restoring the 4010’s Default Programming..............................................C-9
Determining the BIN File Software Revision...........................................C-9
Disabling the Piezo on a Remote LCD Annunciator ................................C-9
Clearing an Event Overflow Trouble........................................................C-9
Technical Manuals Online! - http://www.tech-man.com
vii
Known Solutions.........................................................................................C-11
Supervisory Point Type and Output Devices ..........................................C-11
Incorrect Operation of IDNet Device 124 and 24...................................C-11
Remote LED Connected to a Duct Sensor..............................................C-11
SDACT Conversion Errors .....................................................................C-11
Problems Downloading to the SDACT...................................................C-11
24-Point I/O Incorrect Relay / LED Operation .......................................C-12
System Reset Problems -- IDNet Class A Trouble .................................C-12
System Reset Problems -- Lengthening Reset Timer for Networked
Systems ...................................................................................................C-12
Custom Control Problems Invalid Opcode for IPHOTO or RPHOTO...C-12
Appendix D. Troubleshooting Fiber Optic Links
Introduction.............................................................................................. D-1
In this Appendix....................................................................................... D-1
Overview...................................................................................................... D-2
Introduction.............................................................................................. D-2
Class A LED Displays ................................................................................. D-3
Class B LED Displays ................................................................................. D-5
Introduction.............................................................................................. D-5
Index
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
1-1
This chapter contains two flowcharts, one containing the 4010’s power up
sequence and one that can be used to troubleshoot AC power problems.
Be aware of the following when using these flowcharts.
The power up sequence occurs quickly. On a properly functioning
system, some phases of the power up sequence (for example, the span of
time during which the boot software revision is displayed) appear on the
Liquid Crystal Display (LCD) for only a few seconds. It may be necessary
to run the power up sequence several times, as you read the flow chart, to
properly interpret what is happening.
You can skip these flowcharts if your system has powered up correctly
and is displaying a trouble message on the LCD. Refer to Chapter 2 for
descriptions of the 4010’s trouble messages.
This chapter discusses the following topics:
Topic See Page #
Initial Power Up Flowchart 1-2
AC Power Flowchart 1-4
Chapter 1
Power Up Flowcharts
Introduction
In this Chapter
Technical Manuals Online! - http://www.tech-man.com
1-2
System Displays:
"1.02.xx"
System Displays:
Crash Code A?
System Displays:
Any other
Crash Code
Check cable running from keypad to
SFIO Board.
Replace SFIO Board
System Displays:
"Link Scan" followed by
"Code Scan
C123456789A"
System Displays:
"Warm Start Trouble"
Press ACK Key
AC Power LED ON
System
Displays:
Continuos Link Scan/
Code Scan Loop?
Bin File Corrupt, Damaged, or Missing
Replace BIN File or Replace SFIO.
See Note 4.
No Other Troubles or
Crash Codes Present
System Displays:
Crash Codes
See
AC Power
Flowchart
YES
NO
YES
NO
NO
YES
NO
YES
NO
Do Additional Troubles
Appear?
NO
Do Crash Codes Appear?
Refer to Crash Codes in Chapter 3
Refer to Trouble Descriptions in
Chapter 2
System Displays:
"System is Normal"
YES YES
Refer to
Crash Codes
in Chapter 3
NO
YES YES
YES
YES
YES
System Displays:
CFIG Format Mismatch
(~ 10 Seconds)
Versions of Programmer
and BIN File do not match.
See Note 3 Below.
YES
NO
See Note 2
See Note 1
Initial Power Up Flow Chart
Technical Manuals Online! - http://www.tech-man.com
1-3
Note 1: When the system displays “1.02.xx”, this indicates the revision level of the boot software and does not
indicate the revision level of the panel’s BIN file. Refer to “Determining the BIN File Software Revision,” in
Appendix C of this manual for additional information.
Note 2: Revision 1 systems containing greater than 175 TrueAlarm isolator devices may reboot at this point. If this
occurs, upgrade the BIN file and programmer software to Rev. 2. Refer to Appendix A.
Note 3: Keep the following in mind about mismatched CFIG and BIN files:
- If a Rev. 2 job (CFIG) is downloaded to an SFIO board containing a Rev. 1 BIN file, the system reverts to a
Rev. 1 factory default job.
- If a Rev. 1 job (CFIG) is downloaded to an SFIO board containing a Rev. 2 BIN file, the system reverts to a
Rev. 2 factory default job.
Note 4: The SFIO board must be factory adjusted, tested, and loaded with the latest version of BIN file prior to
shipment. If a new SFIO board is received in the field and there is no BIN file loaded on it (i.e., a system with a
new SFIO enters a continuous link scan/code scan loop), this indicates that the board has not been factory adjusted
and tested. Order a new SFIO board, call Service Support to report the problem, and refer to Appendix B of this
manual for information on brownout potentiometer adjustment.
Note 5: The BIN file is available on the FTP site, the Technical Services Intranet site, or by ordering
Simplex Part # 741-108.
Initial Power Up Flow Chart, Continued
Technical Manuals Online! - http://www.tech-man.com
1-4
Meter AC Power
@ Panel's AC
Terminal Block.
AC Power Less
than 103 VAC?
NO
Contact Individual / Organization
Responsible for Building Electrical
System
Brownout Adjustment
Potentiometer Correctly
Positioned? Refer to
Appendix B.
NO
Adjust Brownout Potentiometer.
Note:
Read Appendix B for
Adjustment Procedure.
YES
Meter DC Power
@ Terminals H1 and H2
DC Power 21-32 VDC?
YES
NO
Check and Replace (if necessary)
Transformer and Bridge Rectifier.
Refer to Appendix B.
AC Power Flowchart
Technical Manuals Online! - http://www.tech-man.com
2-1
Trouble messages are the primary means by which the system indicates that a
problem has occurred.
This chapter organizes trouble messages by major system components. For
example, the section on IDNet troubles contains trouble messages related to
IDNet points, as well as trouble messages for the IDNet channel itself.
This chapter discusses the following topics:
Topic See Page #
NAC Troubles 2-2
Power Supply Troubles 2-4
IDNet Troubles 2-8
RS-232/Modem Troubles 2-11
SDACT Troubles 2-12
Network Troubles 2-13
24 Point I/O Troubles 2-14
LCD Troubles 2-15
4009 IDNet NAC Extender Troubles 2-16
Digital Pseudo Point Troubles 2-17
Chapter 2
Interpreting Trouble Messages
Introduction
In this Chapter
Technical Manuals Online! - http://www.tech-man.com
2-2
Table 2-1. NAC Card and Point Troubles
Type Trouble Message Possible Causes / Troubleshooting
NAC Circuit: SIG1
NAC Circuit: SIG2
NAC Circuit: SIG3
NAC Circuit: SIG4
Remove the field wiring from the NAC. Connect a 10K EOL resistor to
the NAC terminal on the panel and see if the trouble clears. Do one of
the following depending on whether the trouble clears.
If the trouble does not clear, replace the SFIO board.
If the trouble clears, there is a short or open somewhere on the field
wiring running between the NAC terminals on the SFIO and the
notification appliances.
AUX Circuit: AUX1 NAC Card Relay 1 status and configuration.
NAC
Point
Troubles
AUX Circuit: AUX2 NAC Card Relay 2 status and configuration.
Missing Card
Check the baud rate set on the SFIO. This trouble indicates that the
baud rate may be set to some value other than 9600, which is required
for normal operation.
Set the baud rate to 9600, as shown below.
OFF LINE
Black indicates switch
p
osition
9600
19,200
Wrong Card
This trouble indicates that the NAC card returned a card type as
something other than a NAC card type. Indicates either:
Another slave card (LCD Annunciator, 24 Point I/O, RS-232, DACT,
or 4120 Network) has a card address of 1.
The SFIO board is bad.
NAC
Card
Troubles
NACs 1 & 2 Class A
or
NACs 3 & 4 Class A
Check the following:
Verify that a Class A adapter card is actually installed. This error
occurs if the NAC’s device type is Class A and the adapter card is
not installed.
Power down the panel, remove the Class A card and reseat it in the
header on the NAC. Check to see that the pins of the Class A card
are properly seated in the header on the NAC card and power on
the panel. If the trouble does not clear, power down the panel
again and swap another Class A card in place of the suspect card.
If the problem still occurs, replace the SFIO board.
Check the field wiring for opens and shorts.
Continued on next page
NAC Troubles
Technical Manuals Online! - http://www.tech-man.com
2-3
Table 2-1. NAC Card and Point Troubles (continued)
Type Trouble Message Possible Causes / Troubleshooting
NAC
Card
Troubles
NAC 1 Signal Power
NAC 2 Signal Power
NAC 3 Signal Power
NAC 4 Signal Power
Indicates a power trouble on the NAC. Check the following:
Check the load on the NAC in question while it is in the alarm state.
The load on each NAC must not exceed 2A. The SFIO board has
overcurrent protection for each NAC. An overloaded NAC trips this
protection and displays a NAC Signal Power Trouble for the circuit.
Unless the circuit is grossly overloaded, you should have several
seconds to measure the voltage before the protection trips. Measure
the current in either one of the following ways:
- Current Draw for a Single NAC. Use a DC ammeter, connected
in series with the load, to measure the load.
- Current Draw for all NACs. Measure the voltage across R150,
which is located above the LCD on the left-hand side of the SFIO.
Divide the measured voltage by .025. The result is the sum of all
NAC and auxiliary power loads.
If the problem is with NAC 3 or 4, and they are powered by the 4010’s
Expansion Power Supply (EPS), check the following:
- Verify that the red shunt has been removed from connector P13
on the SFIO board.
- Verify that the red (power) harness is connected to P1 on the
EPS and P13 on the SFIO board. Verify the white harness
(communication) is connected to P14 on the SFIO and P2 on the
EPS.
- Remove the harness and visually inspect each female pin on
both harness connectors. Make sure that none of the pins is
pushed back into the connector. Gently tug on each wire at the
back of the connector. If a wire pulls out from the connector,
re-insert it until the pin clicks back into place. Meter each wire for
continuity.
- Verify that no circuit draws more than 2A.
+
2
-
1
+ - + -
NAC Troubles, Continued
P1 (Red
Harness)
P2 (White
Harness)
P13 (Red
Harness)
P14 (White
Harness)
Technical Manuals Online! - http://www.tech-man.com
2-4
Table 2-2. Power Supply Troubles
Type Trouble Message Possible Causes / Troubleshooting
Missing Card
Indicates that the Power Supply card is not communicating with the
master.
Check the baud rate set on the SFIO. This trouble may indicate
that the baud rate is set to some value other than 9600, which is
required for normal operation.
Set the baud rate to 9600, as shown below.
OFF LINE
Black indicates switch
p
osition
9600
19,200
Power
Supply
Card
Wrong Card
Indicates that the Power Supply card returned a card type as something
other than a Power Supply Card type. Indicates either:
Another slave card (LCD Annunciator, 24 Point I/O, RS-232, DACT,
or 4120 Network) has a card address of 2.
The SFIO board is bad.
AC Power
Indicates AC line voltage is too low for proper system operation. Use a
meter to verify that the AC circuit is supplying power to the panel. This
circuit’s voltage must be 120 VAC +10% / -15%.
If the circuit supplying power to the panel has sufficient voltage, check
the adjustment of the AC Voltage Brownout Potentiometer. See
Appendix B of this document.
Power
Supply
Points
Expansion Power Supply
Indicates an Expansion Power Supply (EPS) problem. Try the
following:
Verify that the AC circuit to which the power supply connects is
supplying 120 VAC (+ 10% / - 15%).
- If voltage is present, suspect the EPS transformer, the EPS
bridge rectifier, the connectors, or the harness running from the
EPS to the SFIO. Refer to Appendix B for information on
troubleshooting these components of the EPS.
- If no voltage is present, check the AC circuit feeding the panel.
Verify that the black battery wire on the EPS connects to the – Batt
terminal on the 4010. Even if you are not using battery backup for
the EPS, you must connect the black wire to the – Batt terminal.
Continued on next page
Power Supply Troubles
Technical Manuals Online! - http://www.tech-man.com
2-5
Table 2-2. Power Supply Troubles (continued)
Type Trouble Message Possible Causes / Troubleshooting
Power
Supply
Points
Positive Earth Ground
(Fault condition between
+24 V and Earth)
Negative Earth Ground
(Fault condition between 0V
and Earth)
Run the Earth Fault search diagnostic. If the results of the Earth Fault
search do not isolate the source of the fault, try the following:
Disable each NAC one at a time, checking each time to see if the
fault clears.
Disconnect the AUX power from the panel. Check to see if the fault
clears.
Disconnect the N2 communications from the panel. Check to see if
the fault clears.
If the fault is intermittent, use the Earth Fault Latch, located in the
Function menu, to silence the fault until the intermittent problem can be
isolated and fixed. Note: After fixing the problem, you will need to
perform a system reset to clear the Earth Fault Latch.
If a negative ground is isolated to the dual RS-232 card and one port of
this card attaches to a DC-powered printer and the other port connects
to an AC-powered CRT, upgrade 565-810 to Revision A1 or greater.
You can also remove jumpers P17 and P18 from this card, if ground
detection is not required.
Power
Supply
Points
Expansion Power Supply
Battery
Check the connection of the wires running from the battery to the
expansion power supply, as shown in the illustration below.
+
2
-
1
+ - + -
BLACK
RED
BLACK
RED
Continued on next page
Power Supply Troubles, Continued
Technical Manuals Online! - http://www.tech-man.com
2-6
Table 2-2. Power Supply Troubles (continued)
Type Trouble Message Possible Causes / Troubleshooting
Battery Low
Indicates the battery voltage is low (less than 22.8 V), battery standby
is running low, and action is required.
Note that this may or may not indicate a problem. Do the following:
Note the time of the Battery Low event and determine if the battery
has charged since the event occurred. If the battery is charging,
allow it to charge for a full 48 hours and then check the voltage of
each battery separately.
If this event occurs without an AC Power fail (check the panel’s
history log for AC power failure events), suspect either bad
batteries (i.e., won’t hold a charge) or a battery charger problem.
See the battery charger troubleshooting in the “Battery
Depleted/Disconnected” trouble.
Battery
Depleted/Disconnected
Indicates the battery has a voltage less than 19.5 V. Do the following:
Check the voltage at the battery terminal block on the SFIO board.
The voltage should be 27.6 VDC (+/- 200 mV). If voltage is
present, but less than 27.6 VDC, use R256 to adjust the charger
voltage. See “Battery Charger Trouble” description later in this
section.
Check the fuse and replace if necessary.
Check the voltage of each battery separately from the other
battery. If one battery is good and the other is bad, replace both
batteries. (Note: Batteries are always replaced as a set.)
Power
Supply
Points
Battery Low Cutout
This trouble only occurs if the Depleted Battery system option is
enabled. Indicates the battery has reached a depleted state, and the
system will function in one of two ways:
Shut the system down. This is the ULC-required operation for
Canada. Depleted Battery system option requires a special wiring
harness to function in this way.
When an alarm occurs, the system does not energize the panel’s
NAC circuits. This functionality occurs when the Depleted Battery
option is enabled, but the special harness is not used.
Continued on next page
Power Supply Troubles, Continued
Technical Manuals Online! - http://www.tech-man.com
/