Reznor RDDA Operating instructions

Type
Operating instructions

This manual is also suitable for

Form CP-MAPS II-GC (01-15), P/N 209417R4, Page 1
Applies to: Gas Heat Section Sizes 100, 150, 200, 250,
and 300 on MAPS
®
II Model RDCA and Model RDDA
Form CP-MAPS II-GC (01-15)
Obsoletes Form CP-MAPS II-GC (Version A)
All gas conversion must be done by a qualied service person in accordance with
these instructions and in compliance with all codes and requirements. In Canada, gas
conversion shall be carried out in accordance with the requirements of the Provincial
Authorities having jurisdiction and in accordance with the requirements of the CAN/
CGA-B149.1 and .2 installation code.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause property damage, injury, or death.
For assistance or additional information, consult a qualied
installer, service agency, or the gas supplier.
Application and Kit
Selection
HAZARD INTENSITY LEVELS of Warnings
1. DANGER: Failure to comply will result in severe personal injury or death
and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or
death and/or property damage.
3. CAUTION: Failure to comply could result in minor personal injury and/or
property damage.
The gas conversion kits in these instructions are for an optional heat section (Sizes
100-300) of MAPS
®
II Model RDCA packaged cooling/heating and MAPS
®
II Model
RDDA cooling/reheat/heating systems. (NOTE: For converting larger heat section
sizes, contact the factory service department.)
Natural gas heat sections have either three-stage heating or modulating heating con-
trol. Propane fueled heat sections are only available in three-stage heating.
Verify that the kit being used is the appropriate one for the installation.
Comply with all warnings and follow the instructions carefully.
Components - Gas
Conversion Kits for
MAPS
®
II Models
RDCA and RDDA
with Gas Heat
Sizes 100 - 300
Gas Conversion Kits and Instructions
TABLE 1A - Natural Gas TO Propane Conversion Kits (NOTE: If equipped with Option AG57, 6:1 modulating gas
control, modulation must be disabled before gas conversion. Follow instructions on page 2.)
Gas Section Capacity (MBH) / Size 100 150 200 250 300
Conversion Kit P/N 269845
Description of Component Qty P/N Marking P/N Marking P/N Marking P/N Marking P/N Marking
Gas Orice for small burner section 1 205862 1.7 mm 124967 2.1 196852 #39 196853 #37 205720 2.9 mm
Gas Orice for larger burner section 1 205859 3/32 205860 2.9 mm 205716 3.3 mm 205717 3.75 mm 205718 4.1 mm
Gas Valve Conversion Spring Kit 2 98720, Honeywell #393691, for VR8105, VR8205, & VR8305 Single-Stage Valves
Gas Valve Conversion Spring Kit 2 260605, Honeywell #396221 for a VR8215 Single-Stage Valve (replacement valve)
Propane Conversion Disk 1 37752
Sheetmetal Screw (for attaching disk) 1 11813
Conversion Kit Tape 1 64391 (ll out and adhere near to heat section rating plate)
High Altitude Adjustment Label 1 197062 - Use if elevation is above 2000 ft (610M).
TABLE 1B - Propane TO Natural Gas Conversion Kits (3-stage system only)
Gas Section Capacity (MBH) / Size 100 150 200 250 300
Conversion Kit P/N 269859 209418 209419
Description of Component Qty P/N Marking P/N Marking P/N Marking P/N Marking P/N Marking
Gas Orice for small burner section 1 205863 2.75mm 120146 3.4mm 120152 #23 205719 4.4MM 120158 #10
Gas Orice for larger burner section 1 205857 #23 205858 #12 205713 7/32 205714 6.2MM 205715 6.9MM
Gas Valve Conversion Spring Kit 2 98721, Honeywell #394588, for VR8105, VR8205, & VR8305 Single-Stage Valves
Gas Valve Conversion Spring Kit 2 261651, Honeywell #396222 for a VR8215 Single-Stage Valve (replacement valve)
Secondary Combustion Air Restrictor 2 N/A 205492 205493
Natural Gas Conversion Disk 1 1401
Sheetmetal Screw (for attaching disk) 1 11813
Sheetmetal Screws (for restrictors) 8 N/A 11813
Conversion Kit Tape 1 64391 (ll out and adhere near to heat section rating plate)
High Altitude Adjustment Label 1 197062 - Use if elevation is above 2000 ft (610M).
Form CP-MAPS II-GC (01-15), P/N 209417R4, Page 2
Instructions apply to all sizes unless noted.
1. Turn off the external gas supply valve to the heater. Turn off the electric power
supply to unit (turn disconnect switch to OFF).
Remove the heat section access panel and open the electrical box on the side of
the unit.
2. Locate the burner orices and remove them from the brass adapter ttings. (Use
two wrenches to prevent rotation of the gas valve.) See FIGURE 2.
Preparation for
Conversion FROM
Natural Gas with
Option AG57, 6:1
Turndown Modulating
Gas Control TO
Propane
When converting a heat section equipped with a natural gas modulating control to pro-
pane gas, the modulation feature must be disabled. To disable the modulation feature
complete the ve steps below:
1. Turn off the external gas supply valve to the heater and turn off the power supply
the unit (turn disconnect switch to OFF).
2. Open the door to the electrical box on the side of the unit. Between terminal No. 60
and the 40 VA conditioner transformer, locate the 2.5 amp fuse. Remove and dis-
card the fuse.
3. Remove and discard the red wires from terminal Nos. 63 and 64 and the
modulating gas valve.
Conversion FROM
Natural Gas TO
Propane or FROM
Propane TO Natural
Gas -- applies to
heat section with 3-
stage heating or with
modulation disabled
FIGURE 2 - Gas
Orices
Gas Orice - There are two
burners. Orices sizes are
different. Check the size and
match the threads with the
adapter. Use two wrenches to
remove and replace orices.
5. Proceed to the instructions below for
conversion of a heater with three-stage burner
control.
3. Using the orices in the conversion kit, follow
these instructions.
NOTE that there are different sizes of orices.
Match the pipe threads of the orice to the
brass adapter thread and verify that the size
stamped on the orice matches the specied
size (See TABLE 1A or 1B on page 1).
Install both orices. Use two wrenches to
prevent rotation of the gas valve.
Tighten securely but do not over tighten.
(NOTE: When the
conversion is complete, the
propane fueled heat section
will function with three
stages of heating.)
DANGER
The conversion kit is to be selected and installed by a qualied
service person in accordance with these instructions and in
compliance with all codes and requirements of authorities having
jurisdiction. Failure to follow instructions could result in death,
serious injury and/or property damage. The qualied agency
performing this work assumes responsibility for this conversion.
Gas Conversion
Instructions
Check kit contents for agreement with the parts list and the size of heat section being serviced.
Conversion of a unit using these kits will not alter the input rate. Refer to the rating plate on the heater for input rate and
other appropriate information. (NOTE: If adjusted for high altitude operation, input rate will be affected; for high altitude
input ratings and capacities refer to TABLE 3 on page 4.)
4. Remove the modulating gas valve and replace
with eld-supplied black iron pipe.
FIGURE 1-
Modulating Gas Valve
on Natural Gas Unit
with Option AG57
Remove Maxitrol Modulating
Gas Valve
4. Combustion Air Restrictors - Sizes 250 and 300 only
If you are converting units that have either a 250 or a 300 mbh heat section
from natural gas to propane, the secondary combustion air restrictors must be
Form CP-MAPS II-GC (01-15), P/N 209417R4, Page 3
removed. If converting from propane to natural gas, the secondary combustion
air restrictors must be added. See the illustrations in FIGURE 3 showing the
locations of the upper and lower secondary air restrictors.
Restrictors are attached with screws. Either remove or add as required.
FIGURE 3 - Secondary
Air Restrictors on
Heat Section Sizes
250 and 300
5. Install Spring Kits - One at a time, remove the regulator adjustment spring from
each of the combination gas valves and replace with the appropriate Honeywell
Spring Kit (See component list on page 1 to verify spring kit application. Correct
spring kit must be used). Follow the instructions included with the spring kit.
6. Adjust Gas Valve Outlet Pressure -To adjust the gas valves to their proper
outlet pressure (see TABLE 2), both sections of the burner must be operating. To
facilitate operation without interruption from the system controller, the controller
must be overridden. Follow these steps to override the controller:
a) Place the remotely located OFF/AUTO control switch in the “OFF” position.
b) In the electrical box, remove the yellow wire from terminal No.10 and place a
jumper between terminal Nos. 8 and 10. (This will cause the blower to operate
when the electric supply is established.)
c) Place a jumper between terminal Nos. 40 and 42.
d) Place a jumper between terminal Nos. 40 and 43.
e) Prepare a jumper for placement between terminal Nos. 12 and 14. Do not put
the jumper in place until you are ready to adjust the gas valves. (Jumpering
terminals No. 12 and 14 will energize the heat section.)
7. Turn on the gas supply and the electric supply.
8. Put the jumper on terminals No. 12 and 14. This will initiate a “call for heat” and
when the start-up sequence is completed, both sections of the burner will be
operating.
9. After the burner has “red”, check for gas leaks using a leak detecting solution. If
a leak is found, for safety purposes, correct the leak before proceeding.
10. Using a uid-lled manometer, with both burner sections operating, check to be
certain that the inlet gas pressure is correct for the unit being converted. (The
inlet gas pressure may be checked at the inlet gas pressure tap of either gas
valve. See FIGURE 4.) Do not proceed until the inlet gas pressure is within
the correct pressure range. Natural gas pressure must be 5.5” to 14” w.c. and
propane pressure must be 11” to 14” w.c.
11. With both burner sections operating, adjust the outlet gas pressure of each
combination gas valve as specied in TABLE 2, page 4. Connect a uid-lled
manometer to measure the outlet gas pressure (See FIGURE 4 left). Adjust
pressure adjustment screw as required. Cycle the gas valves several times to
ensure the outlet pressure is correct. (A convenient way to cycle the gas valves
is to remove one of the valve wires momentarily.
CAUTION: DO NOT bottom out the gas valve regulator adjusting
screw. This can result in unregulated manifold pressure causing
excess overre and heat exchanger failure.
Check the outlet pressure of each valve. The turned-off burner section will relight
from the operating section.)
Lower Secondary
Air Restrictor
Upper
Secondary Air
Restrictor
1/8” Output
Pressure
Tap
Inlet Pressure Tap
Pressure
Adjustment
Screw
FIGURE 4 - View of
Single-Stage Valves
showing Outlet
Pressure Tap and
Adjustment Locations
Remove
or add both upper
and lower restrictors.
1/8” Outlet
Pressure
Tap
Inlet
Pressure
Tap
Adjust Outlet Pressure
Form CP-MAPS II-GC (01-15), P/N 209417R4, Page 4
www.ReznorHVAC.com; (800) 695-1901
©2015 Reznor LLC, All rights reserved.
Trademark Notes: Reznor
®
, TCORE
, and are registered in at least the United
States. All other trademarks are the property of their respective owners.
Form CP-MAPS II-GC (Version 01-15)
Gas Conversion
Instructions
(cont’d)
TABLE 2 - Valve Outlet Pressure Settings by Altitude
FIGURE 5 - Attach the
Gas Conversion Disk
Gas conversion disk
attached to heaters
header panel.
TABLE 3 - BTUH Inputs and Capacities by Altitude
12. Remove all wire jumpers and reconnect the yellow wire to terminal No. 10.
13. Use permanent ink to ll in the necessary information on the Conversion Kit Tape.
Include both orice sizes on the tape. Place the tape in a conspicuous location
inside the heat section.
If the unit is located at an altitude above 2000 feet, ll out the High Altitude
Adjustment Label. See TABLE 3. Adhere label near the heat section rating plate.
14. Attach the gas conversion disk. See FIGURE 5 (left).
15. Adhere the gas valve conversion stickers supplied with the Honeywell kit to the
gas valves.
The unit is ready to place into service. Check for proper operation.
Altitude Natural Gas Propane
Feet Meters Outlet Pressure of Single Stage Valves at FULL RATE
Manifold Pressure Settings by Altitude for the UNITED STATES
0-2000 0-610 3.5” w.c. 10.0” w.c.
2001-3000 611-915 3.1” w.c. 8.8” w.c.
3001-4000 916-1220 3.0” w.c. 8.5” w.c.
4001-5000 1221-1525 2.8” w.c. 8.1” w.c.
5001-6000 1526-1830 2.7” w.c. 7.7” w.c.
6001-7000 1831-2135 2.6” w.c. 7.4” w.c.
7001-8000 2136-2440 2.5” w.c. 7.1” w.c.
8001-9000 2441-2745 2.4” w.c. 6.7” w.c.
9001-10000 2746-3045 2.3” w.c. 6.7” w.c.
Manifold Pressure Settings by Altitude for CANADA
0-2000 0-610 3.5” w.c. 10.0” w.c.
2001-4500 611-1373 2.8” w.c. 8.1” w.c.
BTUH Inputs and Capacities by Altitude in the UNITED STATES for Optional Heat Section
ALTITUDE
Normal
Input
Thermal Output
Capacity
Minimum
Input
Normal
Input
Thermal Output
Capacity
Minimum
Input
Normal
Input
Thermal Output
Capacity
Minimum
Input
Feet Meters Size 100 Size 150 Size 200
0-2000 0-610 100000 83000 70000 150000 124500 105000 200000 166000 140000
2001-3000 611-915 94000 78020 65800 141000 117030 98700 188000 156040 131600
3001-4000 916-1220 92000 76360 64400 138000 114540 96600 184000 152720 128800
4001-5000 1221-1525 90000 74700 63000 135000 112050 94500 180000 149400 126000
5001-6000 1526-1830 88000 73040 61600 132000 109560 92400 176000 146080 123200
6001-7000 1831-2135 86000 71380 60200 129000 107070 90300 172000 142760 120400
7001-8000 2136-2440 84000 69720 58800 126000 104580 88200 168000 139440 117600
8001-9000 2441-2745 82000 68060 57400 123000 102090 86100 164000 136120 114800
9001-10000 2746-3045 80000 66400 56000 120000 99600 84000 160000 132800 112000
Feet Meters Size 250 Size 300
0-2000 0-610 250000 207500 175000 300000 249000 210000
2001-3000 611-915 235000 195050 164500 282000 234060 197400
3001-4000 916-1220 230000 190900 161000 276000 229080 193200
4001-5000 1221-1525 225000 186750 157500 270000 224100 189000
5001-6000 1526-1830 220000 182600 154000 264000 219120 184800
6001-7000 1831-2135 215000 178450 150500 258000 214140 180600
7001-8000 2136-2440 210000 174300 147000 252000 209160 176400
8001-9000 2441-2745 205000 170150 143500 246000 204180 172200
9001-10000 2746-3045 200000 166000 140000 240000 199200 168000
BTUH Inputs and Capacities by Altitude in CANADA for Optional Heat Section
ALTITUDE
Normal
Input
Thermal Output
Capacity
Minimum
Input
Normal
Input
Thermal Output
Capacity
Minimum
Input
Normal
Input
Thermal Output
Capacity
Minimum
Input
Feet Meters Size 100 Size 150 Size 200
0-2000 0-610 100000 83000 70000 150000 124500 105000 200000 166000 140000
2001-4500 611-1373 90000 74700 63000 135000 113400 94500 180000 151200 126000
Feet Meters Size 250 Size 300
0-2000 0-610 250000 207500 175000 300000 249000 210000
2001-4500 611-1373 225000 189000 157500 270000 226800 189000
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Reznor RDDA Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI