12
CC
CC
C
ANNONANNON
ANNONANNON
ANNON
®
Digital Vacuum Regulator Instruction & Operation Manual
Version 1.3 — May, 2009; CANNON
®
Instrument Company
2139 High Tech Road • State College, PA • 16803 • USA
1. Press and hold the SCAN/adj and HOLD/mode keys for 8 seconds,
then release; the display will alternate between “cal” and “noYes” for
ten seconds.
2. To specify “yes” and select “CH1”, press and hold the HOLD/mode
key to display “CH1”.
3. Press the HOLD/mode key to display “ALAr”.
4. Press the HOLD/mode key to display the present value of the Low
Alarm point.
5. Set the LO ALARM Point.
NOTE
The decimal point that was set during calibration (CAL_U, CAL_C) will
be displayed.
Press the SCAN/adj key to move the numbers up (+).
Press the HOLD/mode key to move the numbers down (-).
When the desired number is reached, press the SCAN/adj and
HOLD/mode keys at the same time. The number will flash
repeatedly. Then, press the SCAN/adj key to readjust it or the
HOLD/mode key to accept it.
6. Repeat the same procedure as in Step 5 to set the HI ALARM Point.
After the number is accepted the DATUM 2000™ will resume normal
operation.
Selecting set point values
Control set points for the DVR have been determined empirically.
Selecting new set points to control at a different level of vacuum or at a
different unit of measurement, will involve some trial and error.
Once your control point (desired vacuum setting) is known, you must
select and test new set points. Normal factory set points may provide a
useful reference. The unit is shipped from CANNON
®
with a value of
292.5 mm Hg for LO and a value of 299.6 mm Hg for HI These settings
allow the DVR to control at 300 mm Hg ± the tolerance factor of 0.5 mm
Hg.
Mechanically, the DVR is plumbed so that the solenoid controlled by the Lo
register allows air to bypass the Rate Adjust valve. This feature makes it
possible to achieve a vacuum very close to the desired value in a very short
time. For the HI solenoid, the vacuum source is routed through the Rate
Adjust valve, permitting a finer adjustment. For accurate control, both set
points and the Rate Adjust valve must be set properly.
Remember that the Rate Adjust valve setting will vary depending on the
values chosen for the solenoid set points. When resetting the control
points you must also check/adjust the Rate Adjust knob.
Setting procedure